862 Qaybta kVA-13.8/0.48 kV|USA 2025
Awoodda: 750 / 862 kVA
Voltage: 13.8-0.48/0.277kV
Muuqaalka: oo leh saliid FR3

Awoodda Wacan, Kaydinta Sare. Beddelayaasha Qaybteena.
01 Guud
1.1 Sharaxaada Mashruuca
750/862 kVA unug unug koronto-bixiye ah ayaa la geeyey Kanada 2025. Awoodda lagu qiimeeyey taransfooriyuhu waa 750/{4}} kVA oo leh KNAN/KNAF qaboojin. Korantada aasaasiga ah waa 13.8 kV oo leh ± 2 * 2.5% garaacista (NLTC), danab labaad waa 0.48 / 0.277 kV, waxay sameeyeen koox vector ah Dyn1.
Loogu talagalay waxqabadka sare iyo isku halaynta, 750/{1}} unugga kVA-ta beddelka qaybiyaha wuxuu keenaa xal koronto oo dhammaystiran oo loogu talagalay dalabaadka ganacsiga iyo codsiyada warshadaha. Waxay ka kooban tahay dareeraha ester-ka dabiiciga ah ee FR3® ee loogu talagalay badbaadada dabka ee la xoojiyey iyo nolosha dahaarka la dheereeyey, oo ay weheliso waxqabadka kulaylka ee la hagaajiyay (Salida Sare: 45K, Winding Avg: 50K, Hot Spot: 63K) si loo hubiyo waxtarka iyo cimri dhererka xaaladaha culeyska ugu sarreeya. Transformer-ku waa iska caabin -ku qotoma ilaalinta nidaamka wanaajinta wuxuuna si buuxda u qalabaysan yahay -oo ay ku jiraan kabadhka CT ee cabbiraadda iyo ilaalinta, radiyeeriyeyaasha la go'i karo ee qaboojinta marawaxada, taayirrada loogu talagalay meelaynta fudud, kor u kaca cadaadiska degdega ah ee ka hortagga khaladaadka gudaha, iyo xidhayaasha hillaaca ilaalinta qallafsan - bixinta xidhmo koronto ah oo diyaarsan, looguna talagalay in lagu rakibo{1}{1} badbaadada, isku halaynta, iyo fududaynta dayactirka.
1.2 Tilmaamaha Farsamada
750/862 nooca kVA substation-ka tafaasiisha nooca iyo xaashida xogta
|
loo geeyey
Ameerika
|
|
Sannadka
2025
|
|
Nooca
Transformer Substation
|
|
Heerka
ANSI C57.12.00
|
|
Awood lagu qiimeeyay
750 / 862 kVA
|
|
Soo noqnoqoshada
60HZ
|
|
Marxaladda
3
|
|
Nooca qaboojinta
KNAN/KNAF
|
|
Korantada aasaasiga ah
13.8 kV
|
|
Voltage Secondary
0.48/0.277 kV
|
|
Qalabka dabaysha
Copper
|
|
barokaca xagal
Dyn1
|
|
Caqabada
6%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
In ka yar ama la mid ah 1.16kW
|
|
Load Lumista
In ka yar ama la mid ah 7.08kW
|
1.3 Sawirro
750/862 jaantuska jaantuska unugga kVA-ga
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Xuddunta waa sax{0}}waxaa lagu dhisay{1}} darajo, qabow{2}} hadhuudh duuban{3}} bir silikoon ku jihaysan. Maaddadan, oo ay weheliso naqshadda horumarsan ee dahaadhka ah, waxay yaraynaysaa khasaaraha magnetic iyo tamarta hadda. Dhismaheeda adag wuxuu xaqiijinayaa heerarka sanqadh hooseeya iyo xoogga farsamada, siinta dariiqa magnetka ah oo deggan oo hufan taas oo aasaas u ah isku halaynta iyo waxqabadka beddelka.
2.2 Dabaylaha
Dabaylaha ayaa si wanaagsan loogu dhisay waxqabad iyo isku hallayn. Dabaysha hoose ee -Voltage-ga waxa ay adeegsataa bireed{2}}naqshad boogta, oo bixisa awood farsamo oo aad u wanaagsan, kulaylka sareeyo, iyo gaab gaaban{3}}awood u adkeysiga wareegga wareegga. Dhammaystirkeeda, dabaysha sare{5}}korontada dabaysha waxay shaqaalaysaa lakab sax ah{6}}farsamo dhaawac leh oo leh dahaar adag{7}}, hubinta beddelka korantada saxda ah iyo kor u qaadida awooda dielectric. Isku dhafkan la xaqiijiyay wuxuu keenaa wax ku ool gaar ah, xasillooni, iyo adkeysi.

2.3 Haanta

Haangu waa qaab-dhismeed bir ah oo adag, alxanka leh oo loogu talagalay adkeysiga iyo waxqabadka. Waxay u adeegtaa sidii xero ilaalin u ah xudunta iyo dabaylaha, waxay siisaa kayd xidhxidhan oo dareeraha dahaarka ah, waxayna leedahay hiitarka si ay u daadiyaan kulayl hufan. Loo farsameeyay si ay ugu adkeysato culaysyada deegaanka iyo shaqada, haanta waxay hubisaa muddada dheer ee beddelka{2}} daacadnimada iyo isku halaynta.
2.4 Kulanka ugu dambeeya
Kulanka kama dambaysta ahi waa is dhexgalka saxda ah ee xudunta u ah, dabaylaha, taangiga, iyo agabka loo isticmaalo nidaam midaysan oo adag. Marxaladdan muhiimka ah waxay hubisaa in dhammaan isku xirka korantada gudaha la sugay, qaab-dhismeedyada makaanikada ah ay dhawaq yihiin, iyo xayndaabku si fiican ayaa loo xidhay. Natiijadu waa mid si buuxda isugu jirta{2}}ka kooban, diyaarsan{3}}oo ah{4}}qaybta awooda hawlgalka ee keenta hawl qabad, adkeysi, iyo isku hallayn.

03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
% |
Qiyaasta dheelitir la'aanta iska caabbinta ugu badan |
3.19 |
Gudub |
|
2 |
Imtixaanada saamiga |
% |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% |
-0.05~0.01 |
Gudub |
|
3 |
Wajiga{0}}imtixaamaadka xidhiidhka |
/ |
Dyn1 |
Dyn1 |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% |
I0 :: bixiyaan qiime la qiyaasay |
0.47 |
Gudub |
|
kW |
P0: bixi qiimaha la qiyaasay |
0.938 |
|||
|
/ |
Dulqaadka wax qabad la'aan waa +0% |
/ |
|||
|
5 |
Khasaaraha culeyska, korantada impedance, khasaaraha guud iyo waxtarka |
/ |
t:85 darajo Dulqaadka xannibaadda waa +7.5% dulqaadka wadarta rarka luminta waa +0% |
/ |
Gudub |
|
% |
Z%: qiimaha la qiyaasay |
6.20 |
|||
|
kW |
Pk: qiimaha la qiyaasay |
6.903 |
|||
|
kW |
Pt: qiimaha la qiyaasay |
7.841 |
|||
|
% |
Waxtarka aan ka yarayn 99.16% |
99.21 |
|||
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
HV: 34kV 60s LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV):0.96 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
Muddada:40 |
|||||
|
Inta jeer (HZ): 180 |
|||||
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV -LV ilaa Dhulka: |
8.18 |
Gudub |
|
LV-HV ilaa Dhulka: |
3.79 |
||||
|
HV&LV ilaa Dhulka: |
8.98 |
||||
|
9 |
Tijaabada daadinta |
/ |
Cadaadis la dabaqay: 50kPA |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
Muddada:12h |
|||||
|
10 |
Tijaabada dareenka hillaaca |
kV |
hir buuxa |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
11 |
Tijaabada Saliida |
kV |
Xoogga Dielectric Qiimaha la cabbiray Ka weyn ama la mid ah 45 kV |
68.4 |
Gudub |
|
mg/kg |
Nuxurka qoyaanka |
168.6 |
|||
|
% |
Qodobka Burburinta |
3.751 |
|||
|
mg/kg |
Falanqaynta Furan |
/ |
|||
|
/ |
Falanqaynta Chromatography ee Gaaska |
/ |


04 Baakaynta iyo dhoofinta
4.1 Xirxirida
Transformer-ka unuggu waxa uu ku xidhan yahay iyada oo diiradda la saarayo ilaalinta sugan iyo hufnaanta wax ka qabashada. Caadi ahaan waxa lagu dul dulsaarnaa sal adag, sal-qaboojin ah oo loogu talagalay hufnaanta qaab-dhismeedka iyo gelitaanka forklift. Qaybaha muhiimka ah waa la isku duuban yahay, unug dhanna waa cimilo{2}la caddeeyey si loo hubiyo gaadiidka badbaadada leh iyo kaydinta, imanaya - goobta u diyaarsan in la rakibo.
4.2 dhoofinta
Transformer-ka unugga waxa loo diyaariyey xamuulka badda ee loo aadayo Maraykanka oo wata cimilo adag, cimilo{0}} oo lagu xafiday weelka dhoofinta caalamiga ah. Waxaa si cad loogu calaameeyay dhibcaha qaadista, xarunta -- tilmaamayaasha cufisjiidka, iyo dukumeentiyada kastamka si loo hubiyo in si badbaado leh loo maamulo, gaadiidka xasiloon, iyo nadiifin hufan marka laga yimaado dekeda Maraykanka.
05 Goobta iyo Kooban
In ka badan hal qayb, Beddelka Qaybaha Unuggu waa wadnaha la isku halayn karo ee kaabayaasha korantada. Waxay ka tarjumaysaa ballanqaadka adkeysiga, badbaadada, iyo hufnaanta, looguna talagalay in lagu bixiyo awood aan kala go' lahayn hawlahaaga muhiimka ah. U dooro inuu noqdo rukunka mashruucaaga waxqabadka waara.
Nala soo xidhiidh maanta si aad u farsamayso xal ku habboon baahiyahaaga gaarka ah.

Hot Tags: Substation Unit, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
50 kVA Transformer Cirif koronto-13.8 / 0.347 kV|Kan...
2000 kVA Qaybinta Subsformer-44/0.48 kV|Kanada 2025
3000 kVA Substation koronto-44 / 0.6 kV|Kanada 2025
3750/4250 kVA Substation Transformer-13.8/0.48 kV|US...
2000/2300kVA Beddelka Saldhigga Korontada-13.8/0.48 ...
1000/1150 kVA Qaybinta Beddelka Substation-13.8/0.48...
U dir sooji