Farqiga u dhexeeya heerarka CSA iyo Ieee ee sedex weji ah
Jun 30, 2025
Fariin ku dhaaftid
Farqiga u dhexeeya heerarka CSA iyo Ieee ee sedex weji ah

gogoldhig
Pad - Transformers-ka la rakibay waa qaybo muhiim ah oo ku saabsan nidaamyada qaybinta korantada, iyadoo la siinayo isbadal amaan ah oo hufan oo loogu talagalay shabakadaha dhulka hoostiisa ah. Machadka machadka korantada iyo injineerada elektiroonigga ah (Ieee) iyo Ururka Heerka Heerka Kanada (CSA) waxay dejiyeen heerar ay ku xukumaan qaabeynta, tijaabada, iyo waxqabadka. Si kastaba ha noqotee, kala duwanaanshaha muhiimka ah ayaa ka dhex jira heerarka IEEE (Ieee C57.12.34} 2022) iyo heerarka CSA (CSA C227.4-21) marka loo eego awoodda lagu qiimeeyo, iyo dhismaha. Kala duwanaanshahaasi waxay ka tarjumayaan baahiyaha nidaamka korantada ee gobolka, tixgelinta amniga, iyo ku dhaqanka hawlgalka. Wadahadalkani wuxuu sahaminayaa kala soocaya heerarka IEEE iyo Heerarka CSA ee Transform-ka Gawaarida Gawaarida, iyadoo diiradda lagu saarayo qeexitaankooda farsamo iyo saameynta qaabeynta qaab dhismeedka qaab dhismeedka.
I.Farqiga Awoodda

Heerarka CSA: 3000 kVA, 34.5 kv iyo hoosta.

Heerarka Ieee: 10000 kVA, korantada sare 34.5 kv, korantada hoose ee 15 kV iyo hoosta.
Ⅱ. Farqiga u dhexeeya
Shaxda 1: Heerarka CSA ugu hooseeya ee Transformer
|
Cabbirka Transformer, KVA |
Kartida ugu yar ee Transformer,% |
|
0-150 |
1.8 |
|
225-300 |
2.0 |
|
500 |
3.0 |
|
750-1000 |
4.0 |
|
>1000 |
5.0 |
Jadwalka 2: Ieee Heerarka Khilaafaadka Kartiga
|
Qiimayn (KVA) |
Loogu talagalay --}} qiimeynta korantada 600 v iyo hoosta |
Loogu talagalay -}}} koranta 2400 Δ dhex marid 4800 Δ |
Loogu talagalay -}}} koranta 6900 Δ dhex marid 13800 gdy / 7970 ama 13800 Δ |
|
45 |
2.70–5.75 a |
2.70–5.75 a |
2.70–5.75 a |
|
75 |
2.70–5.75 a |
2.70–5.75 a |
2.70–5.75 a |
|
112.5 |
3.10–5.75 a |
3.10–5.75 a |
3.10–5.75 a |
|
150 |
3.10–5.75 a |
3.10–5.75 a |
3.10–5.75 a |
|
225 |
3.10–5.75 a |
3.10–5.75 a |
3.10–5.75 a |
|
300 |
3.10–5.75 a |
3.10–5.75 a |
3.10–5.75 a |
|
500 |
4.35–5.75 a |
4.35–5.75 a |
4.35–5.75 a |
|
750 |
5.75 |
5.75 |
5.75 |
|
1000 |
5.75 |
5.75 |
5.75 |
|
1500 |
5.75 |
5.75 |
5.75 |
|
2000 |
5.75 |
5.75 |
5.75 |
|
2500 |
5.75 |
5.75 |
5.75 |
|
3750 |
5.75 |
5.75 |
6.00 |
|
5000 |
6.00 |
6.50 |
|
|
7500 |
6.00 |
6.50 |
|
|
10000 |
6.00 |
6.50 |
aQiyamkan xiisaha leh waxaa loogu talagalay in lagu soo buuxiyo faqradda 7.1.4.1.4.4.2 ee Ieee Std C57.12.00 {{{3 {3}, kaasoo qeexaya ugu badan wareegga wareega ee ka hortagga awoodda. Transforms-ka Transform-yada waxaa loogu talagalay in ay tahay qaybta Transforms-ka Nooca I iyo nooca II ee II in kasta oo qiimeynta KVA ay ka sarreyso sida lagu qeexay qodobbadan. Waxaa lagu talinayaa in isticmaale dhamaadka uu qiimeeyo shuruudaha kale sida qaanuunka korantada, nidaamka carqaladeeya, ama cilad la heli karo hadda marka la isticmaalayo qiimahan.
Ⅲ. Qaab-dhismeedka guud
Heerarka CSA:
1. Cabbir
Transformers oo leh 125 KV Bil iyo hoosta ayaa ah in hoos lagu muujiyo cabbirrada lagu muujiyoShaxda 3. Transformers oo leh 150 KV Bil ayaa la kulmi doona Ieee C57.12.34 Cabbirada ugu yar iyo qaabeyntaMarka laga reebo in carqalad u dhexeysa qaybo ka mid ah HV iyo LV looma baahnahaddii aan si kale loo cayimin iibsadaha.
Jadwalka 3aad: Cabbirka jidhka ee Transformersers
|
Ku habboon awooda KVA |
Noocyada quudinta |
Beddelka ugu badan ee Bil, KV |
Ballac, mm |
|
75,150 |
Shuuxiis |
95 |
1280* |
|
75,150,225,300 |
Loop |
95 |
1480 |
|
75,150,225,300,500 |
Shuuxiis |
125 |
1480 |
|
75,150,225,300,500 |
Loop |
125 |
1480 |
|
750,1000,1500,2000,2500,3000 |
Shuuxiis |
125 |
1730 |
|
750,1000,1500,2000,2500,3000 |
Loop |
125 |
1730 |
* Forradialfidenttrantersredsrergaratersreat75,150kva, Awidthof1480mmsouldBolowedihagerifaningby.
Xusuusin: Heerka Ieee ma soo rogo wax shuruudo ah oo ku saabsan cabirka guud.
2. Shaqo-xumaynta iyo Qeexitaanka Qodobbada
Heerarka CSA:
Daacadnimada isbedelka iyo heerarka gelitaanka fiilada ee fiilada ah waa mid waafaqsan Ieee C57.12.28, marka laga reebo taas
a) Albaabadu waa inay ahaadaan qiyaastii isku qiyaas;
b) Ma jiri doonto wax carqalad ah oo u dhexeeya qaybaha HV iyo LV, haddii uusan ku cayimin iibsadaha;
c) Albaabada waa in lagu dhejiyaa saddex goobood (sare, dhexda, dhexe, iyo hoosta), hal goob ayaa lahaan doonta siinta padlock (saddex-} ah oo aan loo baahnayn);
d) Xiritaanka gooni ah ee albaabka HV looma baahna;
e) Nin xusuus ah pentaheed oo buuxsamay {{0}- {}} {}} {}} {}} {}} {}} {}} {}} {{}} {}} {}} {{}} {}} {} {}} {}} {}} {}} {}} ah oo ka samaysan bir bir ah ama silikon naxaas ah, oo leh koobab (s) go'an ayaa bixin doona sida lagu muujiyeyJaantus 1. Bolt pentahead Bolt waa la qabsan doonaa si looga hortago in laga saaro iyo xargaha waxyeelada inta lagu gudajiro albaabka albaabka, oo ay kujirto xidhitaan xoog leh; iyo
f) Bogagga birta ee birta ah ee bir-qaadka bir bir aan bir qalooca lahayn lama oggola, haddii aan lagu daboolin saliidaha ku habboon si looga hortago suurtagalnimada xanta.

Jaantus 1A: Caadi ahaan loo xushay pentahead Bogl Det {{1- Qeybta - Qeybta Koobka Dib-u-eegida

Jaantuska: Caadiga ah ee loo yaqaan 'pentahead' pentahead Bogt Frefftions - qaybta isku-dhafka - qeybta {{2} ee qayb ka mid ah koobka mashruuca go'an
Heera IEEE:

Qaabeynta qolka
A pad-mounted, compartmental-type transformer shall consist of a tank with high-voltage and low-voltage cable terminating compartments, as shown in this standard. Qolka waa in lagu kala saaraa carqalad bir ah ama shey kale oo adag. Sare {- koronto iyo hoos u yar {{7- waa inuu ku yaal dhinaca - dhinaca - dhinaca dhinac ka mid ah ee haanta transport-ka. Markii laga daawado hore, hoose {11}- qolka korantada leh ee koontaroolka kontaroolka ah
Awood isticmaal
Qolwal kasta wuxuu lahaan doonaa albaab sidaas oo loo dhisay sidii loo heli lahaa helitaanka sare-} ah oo keliya qolka korantada ka dib albaabka- qolka korantada ah. Waxaa jiri doona hal ama in ka badan oo dheeri ah oo loo cayimay aalado xajisi oo dheeri ah oo ay tahay in la kala baxo ka hor inta sare - albaabka korantada lagu furi karo. Haddii qolka hunguriga hoose uu u soo ifbaxay qaybo nool oo ka badan 600 V,- waa in la dhigaa si loo helo ka-saaristiisa ama furitaanka ka hor inta uusan marin u dhigin qolka hoose ee {7}. Halka hoose {{9}- albaabka koontaroolka korantada leh ee loo yaqaan 'patement', albaabku wuxuu lahaan doonaa seddex {{10 {10 {10} oo leh wax dhibic leh oo lagu siiyay aaladda qufulka. Albaabada qolku waa inay ahaadaan cabir ku filan oo ay ku bixiyaan meel ku filan oo hawlgal ah oo shaqeynaya markii laga saaro ama furan yahay. Albaabadu waa inay u qalabeysan karaan xidhitaanka booska furan ama loogu talagalay ka saarida gacanta.

Ⅳ. qusamiciisa
Heerarka CSA:

1. Joojinta Goobaha Spade
Laba jibbaaran oo toosan oo toosan oo lagu dhejiyay Mid ka mid ah meesha sare iyo kan hooseeya, Loogu talagalay GRDY Transformers, Terminalka dhinaca korantada sare waa in loo qoondeeyaa oo la calaamadeeyaa H0. Labada dhurasho waa in laga soo baxaa, oo laga soo qaadin bir bir aan caadi ahayn, oo leh ballac ugu yar oo ah 40 mm iyo dhumucda ugu yar ee 6 mm, oo lagu bixiyo laba mm (9/16 gudaha) godad, oo u dhexeeya 44.5 mm.
2. Shirkadda
Golaha dhulka ayaa ka kooban basbaas oo adag oo ku xidhan oo ku biiraya labada garoon ee salka ku haysa. Dhammaan godadku waa inay ahaadaan 14 mm (9/16 gudaha) dhexroor.
Bracket dhulka sida ka muuqata Jaantuska 2 waa in lagu dhejiyaa baska dhulka si loo fududeeyo lifaaqa ciladaha dhulka shaqada.
Terminals 3.suurax
Terminalka dhexdhexaadnimada ah X0 waa in lagu xiraa baska dhulka uu ka ganacsado ammadda ku habboon.

Jaantus 2A: Rakibaadda baska dhulka {{1- quudinta loop

Jaantus 2b: Rakibaadda baska dhulka - quudinta radial

Jaantus 2c: Rakibaadda baska dhulka - geesaha dhulka

Heera IEEE:

Qodobbada dhulka
1. 500 KVA iyo ka hooseysa laba gogo 'oo bir ah, mid walbana leh 1/2-kulan
2. Above 500 kVA Two unpainted, copper-faced steel or stainless-steel pads, 51 × 89 mm (2.0 × 3.5 in) each with two holes spaced on 44 mm (1.75 in) centers and tapped for 1/2-in 13 UNC thread shall be provided. Furuunka ugu yar ee naxaasta ee jahwareerka leh wuxuu noqon doonaa 0.5 mm (0.02 gudaha). Qoto dheer ee ugu yar ee godadku waa 13 mm (0.5 gudaha).
3. Goobta Pads-ka dhulka waa in lagu dhejiyaa ama u dhawyahay saldhigga Transformerform, mid ka mid ah heerka sare- qolka korantada iyo mid hoose -} ah koontaroolka korantada. Xaaladaha halka haanta transporthformer-ka iyo waaxda waa kala duwan yihiin, xaashidan waa in kolon koronto lagu xidhaa.
Feejignaanta: Qodobkani wuxuu tilmaamayaa heerarka CSA C227.4-21 iyo Ieee C57.12.34-2022.