25 kVA Beddelka Cirifka Korontada-13.8/0.12*0.24 kV|Guyana 2024
Awoodda: 25kVA
Voltage: 13.8/0.24kV
Feature: oo leh dabayl naxaas ah

Hal -Tiirka Wajiga{1}Ku rakiban Transformers: Rukumada heerka sare ee qaybinta awooda casriga ah.
01 Guud
1.1 Asalkii Mashruuca
Transformer-ka 25 KVA ee ku rakiban tiirka ayaa la geeyey Guyana sanadka 2024. Awoodda la qiimeeyay ee tiirarka ku rakiban transformer waa 25 KVA oo leh qaboojinta ONAN, korantada aasaasiga ah waa 13.8 kV oo leh ± 2 * 2.5% cabirka garaaca (NLTC), korantada labaad waa 0.12/0.24 kV, waxay sameeyeen koox litir ah. Single{9}}Transformers tiirarka wejiga ayaa si weyn loogu isticmaalaa hababka qaybinta korantada si loo yareeyo danab si loo daboolo baahiyaha korontada ee isticmaalayaasha ganacsiga yaryar. Inta badan waxaa lagu rakibaa tiirka gudbinta korontada iyo shabakada qaybinta, sidaas darteed waxaa loogu magac daray "Transformer".
Nooca Transformer-ka ahi waxa uu u beddelaa danab sare oo hadda jira una beddela danab shaqaynaya oo hooseeya iyada oo loo marayo hal - sahay koronto ah, isaga oo hubinaya khasaaraha ugu yar ee tamarta inta lagu jiro gudbinta. Waxay ka kooban tahay dabaysha aasaasiga ah, dabayl labaad iyo xudunta birta. Transformers-yada ulaha ah waa kuwo cufan oo fudud in la rakibo, taasoo ka dhigaysa inay ku habboon yihiin qaybinta korontada ee magaalooyinka iyo miyiga.
Intaa waxaa dheer, transformers-ka tiirka wejiga ah{0}waji yar ayaa fudud xagga hawlgalka iyo dayactirka, waxayna ku shaqayn karaan si degan iyadoo ay hoos yimaadaan xaalado deegaan oo kala duwan. Naqshadeeda ilaalinta waxaa badanaa loogu talagalay inay u adkeyso cimilada daran iyo saameynta dibadda, hubinta kalsoonida tamarta korontada. Marka la soo koobo, transformers-yada noocan oo kale ah ayaa ah lama huraan iyo qayb muhiim ah oo ka mid ah shabakadaha tamarta casriga ah.
1.2 Tilmaamaha Farsamada
25 KVA tafatirka tafatirka nooca iyo xaashida xogta
|
loo geeyey
Guyana
|
|
Sannadka
2024
|
|
Nooca
Transformer ku rakiban tiirarka
|
|
Heerka
IEEE C57.12.00
|
|
Awood lagu qiimeeyay
25KVA
|
|
Soo noqnoqoshada
60HZ
|
|
Marxaladda
3
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
13.8KV
|
|
Voltage Secondary
0.12/0.24 KV
|
|
Qalabka dabaysha
Aluminium
|
|
barokaca xagal
li0
|
|
Caqabada
2.2%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
0.098KW
|
|
Load Lumista
0.289KW
|
|
Agabka
Habaynta caadiga ah
|
1.3 Sawirro
25 tiir KVA ah oo ku rakiban jaantuska beddelka sawirka iyo cabbirka.
![]() |
|
02 Wax-soo-saarka
2.1 Core
Xudunta gariiradda ayaa ku dhaawacantay lakabyo badan oo bir silikoon ah oo xidhxidhan si ay u sameeyaan wareeg ama wareeg-magnet wareeg ah. Habka dabaysha kaliya ma hagaajin karo magnetism-ka iyadoo la dhimayo xajmiga hadhuudhka ee maaddada, laakiin sidoo kale waxay kordhisaa heerka buuxinta xudunta birta. Si loo yareeyo khasaaraha hadda jira, xaashida birta silikoon waxaa loo habeeyaa si dhow cadaadis sare inta lagu jiro dabaylaha, qaababka qaarkoodna waa "xiirid" ama "cadaadis", taas oo ku xidhan shuruudaha naqshadeynta beddelka. Lakab kasta oo xaashida birta ah ee silikoon ee xudunta u ah waxaa badanaa lagu dahaadhay dahaar dahaadh ah si looga hortago qulqulka qulqulka ee u dhexeeya lakabyada. Wareegga birlabeedka xiran ee ka kooban xudunta birta duuban waxay xoojisaa cufnaanta birlabeedka waxayna ka dhigtaa mid aad waxtar ugu leh soo-saarka korantada. Iyada oo la wanaajinayo xulashada walxaha iyo qaabaynta qaabdhismeedka, xudunta gariiradda waxay si wax ku ool ah u yaraynaysaa lumitaanka tamarta (sida luminta hysteresis iyo luminta hadda jirta) ee abuurma inta lagu jiro hawlgalka beddelka. Naqshadaynta xudunta birta waxay ku lug leedahay saamiga leexashada ee dabaylaha aasaasiga ah iyo kan sare si loo hubiyo in saamiga beddelka korantada ee beddelka uu buuxiyo shuruudaha. Sababtoo ah qaabdhismeedku waa mid xiran, buuqa ka soo baxa xudunta gariiradda inta lagu jiro hawlgalka waa yar yahay.

2.2 Dabaylaha

Wareegga bireed ee cadaadiska hooseeya
Mashiinka dabaylaha bireed ee otomaatiga ah, alxanka TIG argon arc, xiirid rogid hagaha, nidaamka xakamaynta PLC, nidaamka sixitaanka tooska ah ee koronto, xawaare sare iyo dabaylo sax ah oo sarreeya. Isbeddelka soo noqnoqda ee jaangooyooyinka xawaaraha-xawaaraha-la'aanta ah, hagaajinta tooska ah ee korontadu. Marka dabaysha la dhammeeyo, dusha sare ee hogaanka gudaha iyo dibadda ee gariiradda ayaa la duubaa. Dhammaadka dabaysha bireedku waa nadiif oo biyo-baxa aakhirkiisu waa yar yahay, taas oo ka dhigaysa mid gaaban oo degdeg ah -xoogga wareegga wareegga mid yar iyo ka-hortagga-gaaban- awoodda wareegga waa la xoojiyey. Korontada u dhaxaysa lakabyada gariiradda foil waxay la mid tahay danabka u dhexeeya wareegyada, iyo danab u dhexeeya lakabyada ayaa hooseeya. Silig{8} alaabada dhaawaca ah, sababtoo ah danabku maaha mid sarreeya, way fududahay in la naqshadeeyo oo la sameeyo.
2.3 Haanta
Haanta waxa ay ka samaysan tahay bir tayo sare leh - si loo hubiyo in haanta ay leedahay xoog makaanik oo wanaagsan iyo iska caabin daxalka Marka loo eego sawirka naqshadeynta, xargaha waxaa loo isticmaalaa in lagu gooyo saxanka birta ee cabbirka iyo qaabka la rabo. Ku shaabadeynta ama foorarsiga habka, saxanka birta ee la gooyey ayaa laga sameeyaa qaybo kala duwan oo taangiga ah (sida saxanka hoose, saxanka dhinaca, saxanka sare, iwm.). Qaybaha waxa lagu ururiyaa haanta iyadoo la isticmaalayo alxanka gaaska ka ilaaliya (MIG alxanka) ama alxanka arc. Markaad alxanayso, hubi cidhiidhiga iyo xoogga alxanka. Alxanka ayaa la dhalaaliyaa alxanka ka dib si loo baabi'iyo burooyinka iyo sinnaanta.

2.4 Kulanka ugu dambeeya


03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug |
Ogolaanshaha Qiimaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
/ |
/ |
/ |
Gudub |
|
2 |
Imtixaanada saamiga |
/ |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: Ii0 |
-0.03 |
Gudub |
|
3 |
Tijaabada polarity |
/ |
Kala goyn |
Kala goyn |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% kW |
I0 : bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay Dulqaadka wax qabad la'aan waa +10% |
1.44 0.084 |
Gudub |
|
5 |
Khasaaraha load, danab impedance, khasaaraha guud iyo hufnaan |
/ kW kW |
t: 85 darajo Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay dulqaadka impedance waa ± 10% dulqaadka wadarta rarka luminta waa +6% |
2.41 0.296 0.380 98.80 |
Gudub |
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
HV: 34KV 60s LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV): 2 Ur Muddada: 48 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV -LV ilaa Ground LV-HV ilaa Ground HV&LV ilaa Ground |
79.6 78.3 78.1 |
/ |
|
9 |
Tijaabada daadinta |
/ |
Cadaadiska la dabaqay: 20kPA Muddada: 12h |
Wax daadasho ah oo aan waxyeello lahayn |
Gudub |
|
10 |
Tijaabada Dielectric Oil |
kV |
Ka weyn ama la mid ah 45 |
52.18 |
Gudub |


04 Baakaynta iyo dhoofinta
![]() |
![]() |
05 Goobta iyo Kooban
Waad ku mahadsan tahay xiisahaaga iyo taageeradaada hal - tiirka wejiga{1}}ku rakiban transformerka! Iyada oo leh waxqabadkeeda gaarka ah, hawlgalkeeda xasiloon, iyo tamar - astaamo hufnaan leh, alaabtani waxay buuxisaa baahiyaha tamarta ee codsiyada kala duwan, iyagoo siinaya taageero la isku halayn karo ee nidaamyada korantada. Waxaan sii wadi doonaa halabuurnimada oo ay naga go'an tahay in aan keeno{4}}alaabooyin iyo adeegyo tayo sare leh. Waxaan rajeyneynaa inaan kula shaqeyno si aan u abuurno mustaqbal ifaya warshadaha korontada si wadajir ah!