250 kVA Qalalan Qalalan Resin Transformers-10/0.4 kV|Georgia 2025
Awoodda: 250kVA
Voltage: 10/0.4kV
Muuqaalka: oo leh CT

Eco{0}horjooge saaxiibtinimo, tayo gaar ah, beddelka beddelka resinka oo awood u siinaya mustaqbalka!
01 Guud
1.1 Sharaxaada Mashruuca
250 kVA resin kabka transformer nooca qalalan waxaa la geeyey Georgia sanadka 2025. Awooda lagu qiimeeyay ee Transformer waa 250 kVA oo leh qaboojinta ONAN. Korantada aasaasiga ah waa 10 kV oo leh ± 2 * 2.5% garaacida kala duwan (NLTC) adoo garaacaya isku xirka, tamarta labaad waa 0.4 kV, waxay sameeyeen koox vector ah Dyn11.
Xabagtaan{0}}ee qallalan ee la duubay{1}}nooca transformer-ku waxa uu leeyahay nakhshad horumarsan oo looga dan leeyahay in lagu gaadho gudbinta awood hufan oo degan. Nidaamkeeda xakamaynta heerkulku waxa uu ka kooban yahay Shiinaha -lagu sameeyay E{4}} nooca heerkulka xakamaynta iyo afar PT100 heerkul ah oo madax banaan. Saddex PT100 ayaa si gaar ah loogu talagalay la socodka heerkulka dabaysha, halka hal baaro loo isticmaalo la socodka heerkulka xudunta ah. Qaabayntan dabacsani waxay hubisaa maareynta heerkulka saxda ah ee xaaladaha kala duwan ee hawlgalka, si wax ku ool ah uga hortagga khataraha kulaylka iyo kordhinta cimriga qalabka.
Intaa waxaa dheer, transformerku waxa uu ku qalabaysan yahay transformer-ka hadda (CT) ee lagu ogaanayo cilada dhulka ee xaga hoose -dhinaca korantada, awood u siinaya aqoonsiga cilada degdega ah si weyna kor ugu qaadaysa badbaadada iyo isku halaynta nidaamka. Iyada oo leh waxqabadkeeda gaarka ah, naqshadeynta joogtada ah, iyo sifooyin badbaado oo heer sare ah, transformer-kani waxa uu noqday qayb muhiim ah oo ka mid ah nidaamyada tamarta casriga ah, oo siinaya dammaanad xasilloon oo lagu kalsoonaan karo codsiyada kala duwan.
1.2 Tilmaamaha Farsamada
250 kVA resin tuurista nooca qalalan qeexitaanka iyo xaashida xogta
|
loo geeyey
Jamaica
|
|
Sannadka
2025
|
|
Nooca
Transformer nooc qalalan oo shub ah
|
|
Qalabka muhiimka ah
xaashi bir silikoon ku jihaysan hadhuudhka
|
|
Heerka
IEC60076
|
|
Awood lagu qiimeeyay
250kVA
|
|
Soo noqnoqoshada
50HZ
|
|
Kooxda Vector
Dyn11
|
|
Marxaladda
3
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
10 kV
|
|
Voltage Secondary
0.4 kV
|
|
Qalabka dabaysha
Aluminium
|
|
Caqabada
6%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
± 2*2.5%
|
|
Wax Xamuul ah ma jiro
0.52 kW
|
|
Load Lumista
3.8 kW
|
|
Heerka dahaarka
F
|
1.3 Sawirro
250 kVA resin tuuray jaantuska jaantuska qalalan nooca qalalan.

02 Wax-soo-saarka
2.1 Core
Xudunta resinka{0}kabka qalalan-nooca transformerka waa qayb muhiim ah, oo laga sameeyay taarikada birta bir ah ee daalacashada sare leh waxaana loo qaabeeyey qaabdhismeed dahaadhan si loo yareeyo khasaaraha hadda jira oo kor loogu qaado waxtarka. Dahaarka dahaadhka ah ayaa lagu dabaqaa inta u dhaxaysa xayndaabyada si looga hortago wareegyada gaaban, kor loogu qaado wareegga magnetic, loona hubiyo gudbinta hadda jirta. Naqshadeyntani waxay ilaalisaa waxqabadka deggan - heerkulka iyo jawiga qoyan, iyadoo sidoo kale bixisa awoodaha kulaylka wanaagsan si loo sii daayo kulaylka dhasha inta lagu jiro hawlgalka, ka hortagga kulaylka. Qaab dhismeedka is haysta ee xudunta udub dhexaadka u ah waxa uu ogolaadaa in taransfooriyaha lagu rakibo oo si caadi ah loogu shaqeeyo meel banaan ah - bay'ada xaddidan, taaso kor u qaadaysa waxtarka iyo badbaadada guud, iyada oo kordhinaysa cimriga

2.2 Dabaylaha

Gariiradda xabagta {{0}kabka qalalan-nooca Transformer waa qayb muhiim ah oo ka masuul ah beddelka iyo gudbinta tamarta korantada, si wayn u saamaynaysa waxqabadka iyo hufnaanta. Waxa laga sameeyay agabka dahaadhka sare{3}}, waxa ay bixisa dahaar aad u fiican iyo - iska caabin heerkul sare ah si looga hortago daadinta hadda. Gariiradda ayaa leh farsamooyin dabaylo sax ah oo loogu talagalay habaynta siligga dhagan iyo qaybinta lebbiska ah, kor u qaadida waxqabadka korantada iyo yaraynta khasaaraha firfircoonida.
Naqshadeynta kulaylka waxtarka leh inta lagu jiro hawlgalka, waxay ka hortagtaa waxyeelada kulaylka. Gariiradu waxa ay martaa shubista resin si ay u adkeyso, taas oo xoojisa cufnaanta iyo xasiloonida, hubinta waxqabadka joogtada ah ee xaaladaha kala duwan.
Intaa waxaa dheer, maaddada resin waxay bixisaa iska caabin daxalka, taas oo u oggolaanaysa inay si kalsooni leh ugu shaqeyso qoyaanka ama jawiga wasakhaysan, kor u qaadista cimriga.
1. Hagaajinta gariiradda:Si sugan ugu rakib gariirada hore{0}ku shubay xudunta iyadoo loo eegayo shuruudaha naqshadaynta, hubinta in jihada, hababka xidhiidhka, iyo kala dheeraynta gariiradu ay u hogaansamaan qeexida naqshadaynta si loo dammaanad qaado waxqabadka korantada ee caadiga ah.
2. Isku xirka Korontada:Ku xidh xadhkaha sare -voltage and low-xadhkaha korantada,iyaga oo hubinaya in dhamaan xidhidhyadu ay amaan yihiin oo ay la kulmayaan heerarka
3. Rakibaadda Agabka:Ku rakib qalabyo kala duwan sida giraangiraha, dahaarka, kantaroolayaasha heerkulka, PT100 heerkulka, iyo CT-yada (transformers hadda) si loo hubiyo in ay si sax ah u shaqeeyaan qalabka caawiye.

03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
|
1 |
Cabbirka caabbinta dabaysha |
/ |
Qiyaasta dheelitir la'aanta iska caabbinta ugu badan Iska caabinta khadka: In ka yar ama la mid ah 2% |
HV (khadka) |
LV (khadka) |
Gudub |
|
0.41% |
0.61% |
|||||
|
2 |
Cabbirka saamiga korantada iyo hubinta barakaca wejiga |
/ |
Dulqaadka saamiga korantada ee taabashada maamulaha: ± 1/10 Astaanta isku xirka: Dyn11 |
0.03% ~ 0.13% Dyn11 |
Gudub |
|
|
3 |
Cabbirka Gaaban -Caaqadaha Wareega iyo Luminta Culayska |
/ kW kW |
t: 120 digrii Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay |
6.14% 2.458 3.455 |
Gudub |
|
|
4 |
Cabbirka maya{0}} lumitaanka rarka iyo hadda 90% iyo 110% ee danab la qiimeeyay |
/ kW |
I0 :: bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay |
90% Uur |
0.50 0.437 |
Gudub |
|
100% Uur |
0.56 0.486 |
|||||
|
110% Uur |
0.616 0.534 |
|||||
|
5 |
Tijaabada Korantada ee La dabaqay |
/ |
HV: 28kV 60s LV: 3kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
|
6 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV): 2 Uur Danab la kiciyay (KV): 0.8 Muddada:40 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
|
7 |
Tijaabada Bixinta Qaybeed |
pC |
Heerka ugu badan ee sii daynta qayb ahaan waa in ay ahaataa 10 pc |
<10 |
Gudub |
|


04 Baakaynta iyo dhoofinta


05 Goobta iyo Kooban
Gebagebadii, transformer-ka nooca qallalan ee kabka resin-ka waxa uu u taagan yahay marag madoonta hal-abuurnimada injineerinka korantada, isaga oo siinaya badbaado la xoojiyay, isku halaynta, iyo adkeysiga deegaanka marka la barbar dhigo transformers-dhaqameedka. Naqshadeeda adag iyo guryaha dahaarka sare waxay xaqiijinayaan waxqabadka ugu wanaagsan ee codsiyada kala duwan, taas oo ka dhigaysa doorasho ku habboon nidaamyada qaybinta awoodda casriga ah. Maaddaama warshaduhu ay si isa soo taraysa u kala mudnaan siinayaan waaritaanka iyo hufnaanta tamarta, resin cast transformer nooca engegan ayaa loo dejiyay inuu door muhiim ah ka ciyaaro qaabaynta mustaqbalka gudbinta tamarta. Awooddeeda ay kaga shaqeyso degaano kala duwan, oo ay weheliso shuruudaha dayactirka ee la yareeyey, waxay ka dhigaysaa hanti fure u ah buuxinta baahida sii kordheysa ee la isku halayn karo iyo xalalka tamarta deegaanka{3} saaxiibtinimo. Sida aan ku sii wadno horumarka tignoolajiyada iyo baahiyaha tamarta, resin cast transformer nooca qalalan ayaa shaki la'aan ahaan doona safka hore ee horumarinta kaabayaasha korantada.

Hot Tags: Transformers xabagta qalalan, soo saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
630 kVA Saddexda Waji Kala beddelka Nooca Qalalan-10...
630 kVA Cast Coil Transformer-6.6/0.55 kV|Koonfur Af...
400 kVA Qalalan Nooca Koronto-0.55 / 0.46 kV|Salvado...
160 kVA Guddaha Nooca Qalalan ee Gudaha-10/0.4 kV|Ge...
1.25 MVA Cast Resin Type Transformer-0.415/3.3*6.6 k...
3 MVA Qalalan Nooca Qalalan-13.8 / 0.48 kV|Jamaica 2025
U dir sooji