Macaamiisha Nicaraguan waxay Booqdaan SCOTECH si ay u Aqbalaan Warshada Najaxa ee 20/25MVA Transformer
Aug 14, 2026
Fariin ku dhaaftid

Agoosto 14, 2026 – SCOTECH waxay ku soo dhawaysay saddex macaamiil oo ka yimid Nicaragua imtixaankii aqbalida warshada ee korontada hore ee SFZ-20000/25000-138, oo ay weheliso socdaal ay ku tagtay qolka bandhiga ee shirkadda iyo xarumaha wax soo saarka. Maamulaha guud ee SCOTECH oo ay weheliyaan kooxaha farsamada, wax soo saarka, iyo tayada, ayaa marti galiyay booqashada oo si diiran ugu soo dhaweeyay martida.
Ka Marag kaca Tijaabooyin Adag - Dhammaan Xogta Waxqabadku way ka gudubtay qeexitaannada
Transformer-ka hoos imanaya waxa uu leeyahay awood lagu qiimeeyay 20 MVA (ONAN) / 25 MVA (ONAF), oo leh dhinaca korantada sare ee 138 kV iyo dhinaca korantada hoose ee 34.5 kV, kooxda vector YNyn0+d, iyo cabbir taabasho ah ±10×1.25%. Waxaa loo qaabeeyey oo loo soo saaray si buuxda oo waafaqsan heerarka taxanaha IEC 60076. Hoolka tijaabada korantada sare ee SCOTECH, macaamiishu waxay arkeen imtixaanada caadiga ah oo dhamaystiran, oo ay ku jiraan:
- Tijaabada Dareenka Hillaaca (LI): Korontada ugu sarreysa ee 650kV ayaa lagu dabaqay dhinaca HV. Halbeegyada mawjadadu waxay ahaayeen T 1=1.35 μs iyo T2≈47 μs dhammaan saddexda weji, dhammaantood waxay ku gudbeen isku daygii ugu horreeyay iyada oo aan wax burbur ah ama toosin. Tijaabada mawjada la jarjaray ayaa sidoo kale u samaysay si aan cillad lahayn.
- Tijaabada Korantada ee La dabaqay (AV): Dhinaca LV waxaa lagu sakhiray 95 kV dhulka, iyo HV dhexdhexaad ah ilaa 140 kV dhulka, labadaba 60 ilbiriqsi, oo leh dareere deggan hadda iyo dahaar la isku halayn karo.
- Tijaabada Voltage-ka ee la Keenay Cabbirka Bixinta Qaybeed (IVPD): Markay tahay 1.58Ur/√3 mudo 5 daqiiqo ah, heerka dheecaanka qaybeed wuxuu ka hoos maray 80 pC ilaa inta, aad uga sarraysa xadka caadiga ah, taas oo muujinaysa nidaam dahaadh nadiif ah oo la isku halayn karo.
- Cabbirka Heerka CodkaHeerka dhawaaqa la qiyaasay wuxuu ahaa 57 dB ee hoos yimaada ONAN iyo 69 dB ee hoos yimaada ONAF, labaduba waxay aad uga fiicnaayeen qiimaha dammaanadda ah ee Wax ka yar ama la mid ah 80 dB. Macmiilku shakhsi ahaan waxay ku xaqiijiyeen akhrinta mitir heerka dhawaaqa gacanta ee goobta.
- Khasaar la'aan: Lagu qiyaasay 18.262 kW (dammaanad 22 kW),16.9% ka wanaagsan shuruudaha qandaraaska.
- Load Loss (ONAN): Lagu cabbiray 69.071 kW (loo dammaanad qaaday 72 kW),4.1% ka wanaagsan qiimaha la dammaanad qaaday.
- Waxyeelo-gaaban: Waxaa lagu qiyaasaa 10.5%, oo si sax ah u dhigma qiimaha naqshadeynta.
- Iska caabbinta dabaylaha DC, weecasho saamiga, is-hortaagga eber-xiga, iyo Falanqaynta Jawaabta Soo noqnoqda (FRA) isku xidhka isku xidhkadhamaantood waxay la kulmeen ama dhaafeen tilmaamihii farsamada. Gaar ahaan, qaloocyada FRA waxay muujiyeen joogtnaansho saddex-waji ah oo aad u wanaagsan, taas oo muujinaysa in aan qalloocin.
Macaamiishu waxay si taxadar leh u eegeen dhammaan xogta cayriinka ah iyo oscillograms ee imtixaan kasta waxayna muujiyeen mahadnaq sare oo ku saabsan saxnaanta qalabka imtixaanka SCOTECH iyo xirfadda shaqaalaha hawlgalka. Dhammaadka habka aqbalaadda, macaamiishu waxay ku saxiixeen shahaadada aqbalaadda warshadda goobta.




Qolka-muuska-qoto-dheer iyo Safarka Warshada - La-kulanka Wax-soo-saarka Sare ee SCOTECH
Intii lagu guda jiray socdaalka qolka bandhiga, macaamiishu waxay heleen faham faahfaahsan oo ku saabsan taariikhda SCOTECH ee soo saaraha isbeddelka caalamiga ah, shatiyada tignoolajiyada asaasiga ah, iyo faylalka mashruuca adduunka oo dhan. Kiisaska mashruuca caadiga ah ee la soo bandhigay ayaa daboolay Waqooyiga Ameerika, Yurub, Aasiya, Koonfurta Ameerika, Afrika, iyo Oceania, taasoo siinaysa booqdayaasha sawir cad joogitaanka caalamiga ah ee SCOTECH.


Macaamiishu waxay markaas dhex mareen aqoon-is-weydaarsiga wax-soo-saarka, iyagoo si isdaba-joog ah u soo booqdaydukaanka rarista xudunta u ah(goynta birta silikoon ee hadhuudhka ku jihaysan ee saraysa, is dulsaar toos ah, iyo xidhidh),dukaanka dabaylaha(nooca diskooga qaybta dabaysha, riixida, iyo qalajinta),qaybaha dahaarka xarunta machining(goynta iyo samaynta kartoonada saxda ah),kulanka kama dambaysta ah iyo aagga buuxinta saliidda faakuumka(isku xidhka xudunta u ah, alxanka rasaasta, qalajinta faakuumka, iyo buuxinta saliidda), iyoxarunta tijaabada alaabta dhammaatay. Macaamiishu waxay si gaar ah u fiirsadeen tayada alxanka haanta, qaab dhismeedka xidhidhiyaha, iyo qiimaynta ilaalinta marawaxadaha qaboojinta. Maareeyaha wax soo saarka ee SCOTECH wuxuu si faahfaahsan u soo bandhigay xirmadaha birta aan-ka-soo-baxa lahayn, gaskets NBR, nidaamka rinjiyeynta adkeysiga sare ee C5M (la dammaanad qaaday in ka badan 15 sano), iyo ilaaliye leh barkin saliid iyo qalajiye. Aqoon-is-weydaarsiga nadiifka ah oo si wanaagsan loo agaasimay, qalabka habaynta otomaatiga ah, iyo diiwaannada kormeerka hab-socodka adag - oo wata kaararka tayada madaxbannaan ee tallaabo kasta - waxay raad xooggan ku reebeen macaamiisha.






Ammaanta Macmiilka iyo Iskaashiga Ballanqaadka ah
Wakiilka macmiilka ayaa faallo ka bixiyay: "Laga soo bilaabo cabbirada naqshadeynta habka wax soo saarka, laga bilaabo xogta tijaabada ilaa maareynta goobta, SCOTECH waxay soo bandhigtay heerar heer caalami ah. Waxqabadka transformer-ka ayaa xitaa dhaaftay filashadayada, gaar ahaan khasaaraha iyo tirada qaylada, taas oo aan aad ugu qanacsanahay. Waxaan kalsooni buuxda ku qabnaa iskaashiga muddada dheer ee mustaqbalka."
Isaga oo ka jawaabaya, Maareeyaha Guud ee SCOTECH wuxuu yiri: "Aqbalaada guusha leh ee cutubka ugu horreeya ee macmiilkayaga Nicaraguan waa barta bilawga ah ee kalsoonida labada dhinac. SCOTECH waxay sii wadi doontaa bixinta alaabooyin lagu kalsoonaan karo iyo adeegyo xirfad leh si ay u taageeraan horumarinta shabakadaha macmiilka iyo si wadajir ah kor loogu qaado kala-guurka tamarta nadiifka ah. "
Aqbalaada iyo socdaalkii dhirtu waxay ku soo gebagebowday si guul leh, iyadoo sii xoojinaysa sumcadda summada SCOTECH ee suuqa Bartamaha Ameerika. SCOTECH waxay weli u heellan tahay mabaadi'da "wax ku oolnimada, joogtaynta, iyo mas'uuliyadda deegaanka," bixinta xalal awood sare leh macaamiisha adduunka oo dhan.


U dir sooji