500 kVA Dhintay suufka hore ee ku rakiban beddelka-24.94/0.48 kV|Kanada 2024

500 kVA Dhintay suufka hore ee ku rakiban beddelka-24.94/0.48 kV|Kanada 2024

Dalka: Kanada 2024
Awoodda: 500kVA
Voltage: 24.94/0.48kV
Tilmaam: oo leh beddelka tuubada
U dir sooji

 

 

dead front pad mounted transformer

Tayada wanaagsan, qaybinta garaadka - Saddex-Waji suuf -Transformer, jaangooyada cusub ee maaraynta tamarta!

 

01 Guud

1.1 Asalkii Mashruuca

500 kVA suuf ku rakiban transformer ayaa la geeyey Kanada sanadka 2022. Awooda lagu qiimeeyay taransfooriyaha waa 500 kVA oo leh ONAN qaboojin. Korontada aasaasiga ah ee Transformer waa 24.94GrdY/14.4kV, halka korantada labaadna ay tahay 0.48y/0.277kV oo leh laba danab oo dhanka LV ah, taas oo ah sida saxda ah u gaarka ah transformerkan. waxay samaysteen koox fallaago ah YNyn0.

Transformer-ka ku rakiban suufka, sidoo kale loo yaqaano substation-ka la isku daray, waa qalab dhamaystiran oo ah transformer-ka iyo qaybinta oo isku daraysa transformer-ka la isku daray,{0}}sare ee culayska korantada iyo qalabka fiyuuska difaaca, hoose{1}}qayb qaybinta korantada, iwm Lagu dabaqi karo warshadaha, macdanta, goobaha shidaalka, dekedaha, garoomada diyaaradaha, dhismayaasha dadweynaha ee magaalooyinka, meelaha la deggan yahay, waddooyinka waaweyn, tas-hiilaadka dhulka hoostiisa ah iyo meelaha kale. Waxay leedahay faa'iidooyinka beddelka fudud ee habka korontada, hawlgal ammaan ah oo la isku halleyn karo, cabbir yar, rakibid degdeg ah, isticmaalka ammaan ah, hawl fudud, muuqaal qurux badan iyo dayactir fudud. Dhaqaale ahaan, waxay leedahay faa'iidooyinka raad yar, muddada dhismaha gaaban iyo qashinka yar.

 

 

1.2 Tilmaamaha Farsamada

500 kVA suuf ku rakiban tilmaanta beddelka iyo xaashida xogta

loo geeyey
Kanada
Sannadka
2024
Qaabka
500kVA-24.94GrdY/14.4-0.480y(0.277)kV
Nooca
suuf ku rakiban transformer
Heerka
IEEE C57.12.34
Awood lagu qiimeeyay
500kVA
Soo noqnoqda
60HZ
Marxaladda
3
Nooca qaboojinta
ONAN
Korantada aasaasiga ah
24.94GrdY/14.4 kV
Voltage Secondary
0.480y/0.277 kV
Qalabka dabaysha
Aluminium
barokaca xagal
YNyn0
Caqabada
5.75%
Taabo Beddelka
NLTC
Riixista Range
(+0,-4)*2.5%
Wax Xamuul ah ma jiro
0.765KW
Load Lumista
3.870KW
Agabka
Habaynta caadiga ah

 

1.3 Sawirro

150 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.

dead front pad mounted transformer diagram dead front pad mounted transformer nameplate

 

 

02 Wax-soo-saarka

2.1 Core

Xudunta birta waa qaybta ugu muhiimsan ee korontadu, qaabdhismeedkeedu waxa uu leeyahay laba nooc oo aasaasi ah oo xudunta u ah iyo qolofka, waxaanu soo saara noocaan oo kale ah oo ku rakiban transformer si aanu u qaadano qaab dhismeedka xudunta u ah qaab ka samaysan bir is dulsaaran. Xudunta birta la dahaadhay ayaa mid mid looga sameeyaa xaashida birta silikoon ee koronto oo dahaaran, iyo walxaha xudunta u ah waa qabow - hadhuudh duuban - xaashi bir silikoon ku jihaysan. Xudunta ayaa si toosan loo dhigay, waxayna inta badan ka kooban tahay laaminta xudunta u ah, xajin, cag, suun jiid, saxan jiid iyo saxan taageero. Qaybta dabaysha ee ka baxsan xudunta birta waxaa loo yaqaannaa tiirka xudunta u ah, qaybta aan dabaylaha lahayn waxaa loo yaqaan harqoodka birta, harqoodka birta waxa loo qaybiyaa harqoodka birta sare iyo harqoodka birta hoose, saddexda weji shan tiir nooca birta ah ee labada dhinac, dabaysha aan galka lahayn waxaa loo yaqaan harqoodka dhinaca.

image007

 

2.2 Dabaylaha

automatic transformer winding machine

Siliga dabaysha ee dabaylaha ma aha mid ka samaysan silig naxaas ah oo wareegsan iyo silig naxaas ah oo fidsan, laakiin waxa uu ku dhaawacmay bireed naxaas ah ama bireed aluminium ah, lakab kastaa waxa uu dhaawacan yahay hal mar, lakab kasta oo naxaas ahina waxa lagu kala saaraa walxo dahaarka ah. Walaxda dahaadhka ah waxay ka samaysan tahay warqad Nomax ah oo ay soo saartay Shirkadda DuPont ee Maraykanka. Warqadan dahaarka ah ayaa u adkaysata heerkulka sare, ololka iyo dahaadhka wanaagsan. Naxaasta xaashida ah iyo xaashida dahaadhka ah ayaa la is dulsaaray oo la wada dhaawacay, ballaca xaashida dahaadhka ahi waxa uu ka weyn yahay ballaca xaashida naxaasta ah, qaybta ballaadhan ee labada dhinacna waxa lagu dahaadhay fiilooyinka dahaarka oo la mid ah dhumucda naxaasta oo ay isku mar ka wada qayb qaataan si ay u sameeyaan dahaarka dhamaadka, iyo xariijimaha taageerada waxa la dhex dhigayaa laba ama saddex lakab mid kasta si ay u neefsato iyo kulaylka. Ka dib marka ay nabarka iyo xaashida dahaadhka ahi ay dhaawacmaan si waafaqsan tirada lakabyada, xaashida dahaadhku waxa ay dhaawacmaan dhawr lakab ka dibna cajaladda aan{4}}aan ahayn alkali waxay ku dhaawacmi doontaa warqadda dahaadhka. Ka dib markii dabaysha la qooyay oo la qalajiyo, waa la dejin karaa. Dabaylaha dabaysha ayaa guud ahaan ku haboon - dabaylaha korantada ee transformerka.

 

2.3 Haanta

1. Qaybta sare ee sanduuqa si dabiici ah ayaa loo daadin karaa, iyo xagasha u janjeerta ee daboolka sare waa mid aan ka yarayn 3 digrii.

2. Waxqabadka wanaagsan ee ka-hortagga muraayadda qorraxda, oo aan fududayn in la kululeeyo, si looga fogaado heerkulka xad-dhaafka ah ee uu keeno heerkulka dibadda ee xad-dhaafka ah, lakabka dahaarka

3. Qoyaanka wanaagsan -waxqabadka caddaynta, ma fududa in la soo saaro uumi

4. Ka-hortagga -daxalka, ololka celisa, qaboojinta{2}

5. Qalabka farsamada ee wanaagsan, iska caabinta cadaadiska, iska caabinta saameynta

6. Isku-dubbaridka deegaanka

moisture-proof oil tank

 

2.4 Kulanka ugu dambeeya

no load tap changer

Ka dib marka qaybaha asaasiga ah iyo dabaylaha la sameeyo, waa in la isku dhejiyaa. Ka dib marka qaybaha asaasiga ah iyo dabaylaha la sameeyo, waa in la isku dhejiyaa. Marka hore, ka saar xajinta sare, ka saar harqoodka birta sare, geli dahaarka dhamaadka hoose ee hoose, geli kartoonka insulating xudunta u dhigno dabaylaha hoose iyo dabaysha danab sare. Tuubada - beddelku waa in la beddelo saamiga leexashada beddelka iyadoo la beddelayo booska tuubada si loo hubiyo soosaarka tamarta deggan.

Ka dib markii jidhka la ururiyo, geli qolka vacuum qalajinta si ay u qalalaan, taangiga la rakibo karaa ka dib markii jidhka qalalan, taangiga ee Transformer waa in la ilaaliyo qolof ka mid ah transformer jirka iyo weelka saliidda, iyo sidoo kale waa qalfoof ka mid ah shirka qaybaha qaab dhismeedka dibadda ee transformer ah, oo ciyaari kara doorka convection iyo shucaaca u dhexeeya saliidda Transformer iyo hawada, iyo wareejinta tamarta.

 

 

03 Tijaabinta

Tijaabada dahaarka: oo ay ku jiraan tijaabada xoogga dielectric iyo tijaabinta caabbinta dahaadhka si loo hubiyo in tayada dabaylaha iyo alaabada dahaadhka ay buuxiyaan shuruudaha.

Load luminta iyo maya-Tijaabada luminta rarka: Waxa loo isticmaalaa in lagu cabbiro luminta tamarta culayska la qiimeeyay iyo danab la qiimeeyay si loo xaqiijiyo waxqabadkeeda.

Tijaabada impedance gaaban oo gaaban: Cidhiidhiga gaabnaanta wareegga wareegga wareegga (transformer) waa la cabbiraa si loo qiimeeyo jawaabta taransfooriyaha ee qulqulka wareegga gaaban -.

Tijaabada korantada degdega ah: Waxaa loo isticmaalaa in lagu tijaabiyo awoodda nidaamka dahaadhka si uu ugu adkaysto koronta degdega ah.

Tijaabada qaybta isku xigxiga eber: Hubi dabaylaha transformerka si uu u gaabiyo.

Taabo-Tijaabada beddelka: Waxaa loo isticmaalaa in lagu tijaabiyo ficilka, xasiloonida iyo waxqabadka tubbada{1}} beddelka

Tijaabada kor u kaca heerkulka: Go'aami kor u kaca heerkulka is-beddelka ee culayska la qiimeeyay oo hubi in aanu dhaafin xadka la ogol yahay.

Kormeerka muuqaalka: Hubi in muuqaalka, calamadaha iyo rakibaadda transformerku ay buuxiyeen shuruudaha.

 

Impulse voltage test
Load loss and no-load loss test

 

 

04 Baakaynta iyo dhoofinta

500kva transformer packaging
dead front pad mounted transformer shipping
 
 

05 Goobta iyo Kooban

Waad ku mahadsan tahay xiisahaaga saddexdayada{{0}wajiga{1}} Sida qayb muhiim ah oo ku saabsan gudbinta iyo qaybinta awoodda, alaabtayadu waxay u taagan tahay waxtarkeeda, xasilloonida, iyo badbaadada, buuxinta baahiyaha kala duwan ee codsiga. Hadday tahay jardiinooyinka warshadaha ama tas-hiilaadka ganacsiga, waxay ku siinaysaa xalal awoodeed oo la isku halayn karo oo aad ku tiirsanaan karto. Fahmida baahida adag ee tayada iyo adeegga ee nidaamyada korantada, waxaa naga go'an inaan bixinno tignoolajiyada cusub iyo taageerada feejigan. Waxaan rajeyneynaa inaan bixinno xalal xirfadeed oo awood ah mashaariicdaada oo aan ka wada shaqeyno si loo helo mustaqbal hufan oo waara! Fadlan xor u noqo inaad nala soo xiriirto wixii su'aalo ah.

power transmission

 