150 kVA Dareeraha Buuxsan Beddelka-13.2/0.48 kV|Kanada 2024
Awoodda: 150kVA
Voltage: 13.2/0.48kV
Muuqaalka: oo leh OCTC

Si dadaal la'aan ah u maaraynta dalabaadka tamarta adag - Saddex-Safafka Wajiga{1}Ku rakibida Bawlaha waxay hubisaa in kilowatt kastaa uu yahay mid la isku halayn karo oo hufan!
01 Guud
1.1 Asalkii Mashruuca
SCOTECH waxay dhawaan dhoofisay sare -{1}}- xariiqda 150kVA ee saddexda waji ee ku rakiban taransfooraha Kanada. Korantada aasaasiga ah ee Transformer-ku waa 13.2Y/7.62kV, halka tamarta labaadna ay tahay 0.48Y/0.277kV oo leh laba danab oo dhinaca LV ah, taas oo ah sida saxda ah u gaarka ah transformerkan.
Transformer-ka suufka lagu rakibay waa qalab dhamaystiran oo ah qalab koronto oo isku daraya Transformer-ka, is-beddelka rarka iyo qalabka fiyuuska difaaca ee qaybta tamarta sare ee hadda jirta, furaha rarka iyo qalabka fiyuuska difaaca ee qaybta hadda jirta, iyo cabbirka iyo beddelka qaybta qaybinta tamarta hoose. Jirka wax ka beddelka,{1} sare ee culeyska korantada, fiyuuska iyo qaybaha kale ayaa lagu wada meeleeyaa haanta transformer-ka, sababtoo ah ku shubidda saliidda, mugga ka kooban si weyn ayaa loo dhimay, qaabdhismeedku waa mid cufan, fudud in la rakibo oo dabacsan. Si buuxda u dahaaran, qaab dhismeedka si buuxda u xidhan, badbaado leh oo la isku halayn karo, fududahay in lagu shaqeeyo, dayactirka{3}} bilaash ah. Si weyn looga isticmaalo aagagga la deggan yahay, xarumaha warshadaha sare, warshadaha iyo shirkadaha macdanta, garoomada diyaaradaha, saldhigyada, dugsiyada iyo meelo kale.
Qaybta korantada sare waxay si buuxda u dahaaran tahay galitaanka korantada sare ee korantada iyo meelaha laga baxo iyo qalabka fiilada, si aanay u jirin qayb toos ah oo bannaan oo ku dhex jirta muddada tamarta sare, oo leh astaamo hawlgal oo ammaan ah oo la isku halayn karo; Ilaalinta fiyuuska cadaadiska labanlaabka ah, fiyuuska - fiyuuska ku jiraa wuxuu leeyahay sifooyinka heerkulka iyo ilaalinta xasaasiga ah ee labanlaabka ah, fiyuuska kaydka ah si loo ilaaliyo cilladda beddelka; Isla mar ahaantaana, waxay leedahay qalabyada kormeerka hawlgalka oo dhamaystiran, sida cabbirada cadaadiska, valves cadaadiska, cabbirada heerka saliidda, cabbirada heerkulka saliidda, iwm.
Qaybta korantada hoose waxay ku qalabaysan tahay tijaabiye cabbir dhammaystiran si loo cabbiro tamarta, hadda, awoodda firfircoon, tamarta falcelinta, heerkulka iyo cabbirrada kale ee meel go'an. Qalabka mitirka akhriska ee otomaatiga ah ee isticmaala, ayaa si otomaatig ah u koobi kara isticmaalka awoodda dhammaan - isticmaaleyaasha korantada ee qalabkan iyada oo loo marayo side ama qaab fiilsan; Hooseeya{2}}Qaybinta korantada korantada waxa ay ku qalabaysan tahay ilaalinta wejiga luminta, taas oo ogaan karta luminta wejiga oo ku dhiirigelisa isticmaale kasta in uu ka hortago waxyeelada ay keento -full- hawlgalka wejiga; Golaha cadaadiska hooseeya waxaa lagu qalabeeyaa marawaxad, kaas oo si toos ah u tuuraya oo soo saaraya kulaylka iyadoo loo eegayo heerkulka, laga bilaabo 45 digrii oo ku soo noqda 40 digrii.
1.2 Tilmaamaha Farsamada
150 KVA suuf ah oo ku rakiban tafatirka tafatirka iyo xaashida xogta
|
loo geeyey
Kanada
|
|
Sannadka
2024
|
|
Qaabka
150KVA-13.2Y(7.62)/0.48Y(0.277)KV
|
|
Nooca
suuf ku rakiban transformer
|
|
Heerka
IEEE C57.12.34
|
|
Awood lagu qiimeeyay
150KVA
|
|
Soo noqnoqoshada
60HZ
|
|
Marxaladda
3
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
13.2Y (7.62) KV
|
|
Voltage Secondary
0.48Y (0.277) KV
|
|
Qalabka dabaysha
Aluminium
|
|
barokaca xagal
YNyn0
|
|
Polarity
Wax lagu daro
|
|
Caqabada
5±7.5%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
0.29KW
|
|
Load Lumista
1.52KW
|
|
Agabka
Habaynta caadiga ah
|
1.3 Sawirro
150 KVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Walaxda xudunta u ah waxay ka samaysan tahay {{0}qabow tayo sare leh{1}} hadhuudh duuban - xaashi bir silikoon ku jihaysan. Birta Silikoon lafteedu waa walax birlabeed leh oo awood birlabeed xooggan leh. Gariiradda tamarta leh, waxay soo saari kartaa xoojinta kicinta magnetic weyn, taas oo yareyn karta mugga beddelka. Waxaan ognahay in transformer-ka dhabta ahi uu had iyo jeer ku jiro gobolka AC, iyo khasaaraha korantadu ma aha oo kaliya caabbinta gariiradda, laakiin sidoo kale xudunta u ah magnetization-ka beddelka ah ee hadda jira. Sida caadiga ah khasaaraha korontada ee xudunta birta waxaa loo yaqaannaa birta khasaaro, khasaaraha birta waxaa sababa laba sababood, mid waa Magnetic khasaaro, mid waa eddy current loss. Luminta birta waa luminta birta ee ay keento ifafaalaha birlabeedka ee habka magnetization ee xudunta, iyo xajmiga khasaarahani wuxuu la mid yahay cabbirka aagga ay ku hareeraysan yihiin wareegga magnetka ee walxaha. Wareegga magnetic ee birta silikoon waa cidhiidhi, iyo luminta magnetic ee xudunta udubdhexaadiyaha iyada ayaa yar, taas oo aad u yareyn karta heerka kuleylka.

2.2 Dabaylaha

Dabaylaha foil danab yar
● Qaybinta hadda jirta ee axial ayaa si xor ah u habaysa
● Waxay yaraysaa xoogaga xiiraya
● Dabaysha ka dib, Prepreg wuxuu ku dul dheggan yahay xaashida kirishbooyada si uu u sameeyo tuubo is haysta iyadoo la raacayo habsocod dabci ah.
Dabaysha danab sare
● Si buuxda iyo badh{0}mashiinada dabaysha oo toos ah
● dhaldhalaalka - silig dahaaran oo leh dabaylo joogto ah oo jiid jiid dhululubo sidaha, ama si toos ah dabaylaha LV
● Lakabka dahaadhka waraaqda fiilada tayada sare leh ee {{0}
● Daboosha faashad ka samaysan xaashi yaraynaysaa dabaysha is haysta oo leh {{0}jawaab wareeg ah oo wanaagsan iyo qaybinta tamarta ugu wanaagsan
2.3 Haanta
Shirkadeena waxay u isticmaashaa birta aan tayada lahayn - oo ah alaabta ceeriin ee soo saarista haamaha shidaalka, waxayna isticmaashaa mishiinada haydarooliga ama qalabka kale ee samaynta si ay u laaloosho, u jarto oo ugu cadaadiso saxanka birta qaabka la rabo ee haanta shidaalka. Dabada qaybaha oo samee alxanka gaashaanka gaaska ama hababka alxanka kale si loo hubiyo cidhiidhiga iyo xoogga qaabdhismeedka taangiga. Dhammaan shaabadihii waxa lagu xidhay xadka ugu dambeeya; Qaybaha birta ah ee gudaha iyo dibadda santuuqa ayaa lagu soo koobay si ay timaha uga saaraan, iyo tolitaanka alxanka iyo shaabadda ayaa la tijaabiyaa saddex jeer (fluorescence, cadaadis togan, tijaabada daadinta cadaadiska xun); Rinjiga waxaa loo sameeyay si waafaqsan heerka caadiga ah ee ka-hortagga{3} shuruudaha miridhku.

2.4 Kulanka ugu dambeeya

Qaab dhismeedka sanduuqa Maraykanka -nooca transformer-ka isku dhafka ah waxa loo qaybiyaa laba qaybood, horena waa golaha xadhkaha, golaha xadhkaha waxa ka mid ah terminal danab sare iyo mid hooseba leh, xidhidh sare oo danab ah, fiyuus - ku jira fiyuuska, cadaadiska sare ee beddelka tuubada hawlgalka, mitirka dhadhanka saliidda, mitirka heerkulka saliidda, iwm.; Gadaalku waa sanduuqa saliida iyo weelka kulaylka, transformer-ka dabaysha, xudunta birta, furka culayska sareeyo, fiyuuska{3}}ku jira ayaa ku jira jidhka haanta. Furayaasha, fiyuusyada, iyo Transformers-ka ayaa lagu dhex shubaa saliidda beddelka.
Ku rakib terminalka guriga, ku rid xudunta birta ee la ururiyey haanta saliidda, hagaajin furayaasha ka dib marka xudunta birta la geliyo, oo rakib fiyuuska tamarta sare leh. Ka dib marka dhammaan tallaabooyinka kor ku xusan la dhammeeyo, buuxi haanta saliidda.
03 Tijaabinta
Tijaabada suufka ku rakiban waxay badiyaa u qaybsantaa isku xirka soo socda: kormeerka muuqaalka, tijaabada shaqada korantada, tijaabada caabbinta dabaysha, tijaabada luminta culeyska, tijaabada heerkulka sare u kaca iyo tijaabada hawlgalka.
1. Kormeerka muuqaalka: Kormeerka muuqaalka ee sanduuqa Ameerika waxaa loo sameeyaa si loo hubiyo in sanduuqa, dabaylaha, alaabta dahaarka, iwm, ay yihiin kuwo sugan.
2. Tijaabada shaqada korantada: Isticmaal qalabka tijaabinta korantada si aad u tijaabiso oo aad u hubiso waxqabadka korantada ee transformerka santuuqa Ameerika, oo ay ku jiraan fiilooyinka, caabbinta dahaarka, caabbinta dabaysha, tijaabada danab, dacas hadda iyo jeegag kale.
3. Tijaabada iska caabbinta dabaysha: Isticmaal qalabka tijaabinta dahaadhka si aad u tijaabiso una hubiso caabbinta dabaysha ee sanduuqa Maraykanka.
4. Tijaabada luminta culayska: Sawir qadar yar oo hadda ah iyadoo loo eegayo culayska la qiimeeyay ee beddelka santuuqa Ameerikaanka si aad u hubiso in luminta iyo hufnaanta sanduuqa ay buuxinayaan shuruudaha naqshadaynta.
5. Tijaabada kor u kaca heerkulka: hagaajin tamarta gelinta iyo culayska santuuqa Ameerika, u fiirso xaalada sanduuqa, tijaabi heerkulka dabaylaha, kor u kaca heerkulka jidhka, heerkulka saliidda, iwm.
6. Tijaabada Hawlgalka: Transformer-ka Ameerikaanka muddo dheer oo tijaabo ah, si joogto ah u hagaajiya korantada gelinta, cabbirka culeyska, iwm, si loo hubiyo waxqabadka iyo xasilloonida qalabka beddelka.


04 Baakaynta iyo dhoofinta
![]() |
![]() |
05 Goobta iyo Kooban
Waad ku mahadsan tahay xiisahaaga saddexdayada{{0}wajiga{1}} Iyada oo ay si heer sare ah u shaqeyneyso oo la isku halleyn karo, naqshad kooban oo qurux badan, iyo sifooyin badbaado oo gaar ah, badeecadani waxay noqotay doorasho ku habboon warshadaha, ganacsiga, iyo nidaamyada awood qaybinta dadweynaha. Waxaa naga go'an inaan bixino xalal koronto oo dhameystiran iyo adeegyo qaali ah si aan u daboolno baahida suuqa. Wax dhib ah maleh baahida mashruucaaga, waxaan halkaan u joognaa inaan ku taageerno guushaada si karti iyo hufnaan leh. Waxa aanu rajaynaynaa in aanu idinla samayno iskaashi wakhti dheer- iyo horumarinta hufnaanta iyo joogtaynta warshadaha tamarta si wada jir ah! Wixii macluumaad dheeraad ah, fadlan xor u noqo inaad nala soo xidhiidho wakhti kasta!

Hot Tags: dareere buuxiyey transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
150 kVA suuf Ku rakiban Beddelka-34.5/0.208 kV|USA 2024
300 kVA suuf - ku rakiban Transformer-34.5/0.208 kV|...
300 kVA Saliid Buuxiyey Beddelka-13.2 / 0.48 kV|Guya...
1500 kVA suuf Ku rakiban Beddelka-34.5/0.48 kV|USA 2024
500 kVA Saddex Waji oo Qaybinta Qaybinta-4.16/0.6 kV...
2000 kVA suuf Ku rakiban Beddelka-24/0.48 kV|USA 2024
U dir sooji