500 kVA Saddex Waji oo Qaybinta Qaybinta-4.16/0.6 kV|Kanada 2025

500 kVA Saddex Waji oo Qaybinta Qaybinta-4.16/0.6 kV|Kanada 2025

Dalka: Kanada 2025
Awoodda: 500 kVA
Voltage: 4.16D-0.6Y/0.347kV
Feature: oo leh furaha kirk
U dir sooji

 

 

three phase distribution transformer

Aragga ka maqan, Waligaa Awoodi Maqan – Awooda is haysta ee suufka -Badal-beelayaasha Ku rakiban.

 

 

01 Guud

1.1 Sharaxaada Mashruuca

500 kVA saddex weji suuf ah oo ku rakiban transformer ayaa la geeyey Ameerika sanadka 2025. Awoodda la qiimeeyay ee transformerku waa 500 kVA oo leh ONAN qaboojin. Korantada aasaasiga ah waa 4.16D kV oo leh ± 2 * 2.5% garaacista (NLTC), danab labaad waa 0.6Y / 0.347kV, waxay sameeyeen koox vector ah Dyn1.

Xirmadan 500kVA{1}ku rakiban furaha waxa uu leeyahay qaabayn gaar ah oo loogu talagalay badbaadada la xoojiyey, isku halaynta, iyo adkeysiga baahida jawiga hawlgalka.

Si ka duwan cutubyada caadiga ah, waxa ay ku daraysaa nidaamka isku xidhka Kirk Key si loo dhaqan geliyo hawlgallada badbaadada leh loogana hortago gelitaanka shilalka ee qaybaha tamarta leh, iyada oo hubinaysa u hoggaansanaanta borotokoolka badbaadada adag. Intaa waxaa dheer, waxay ku qalabaysan tahay kuwa xidha suxulka si ay uga ilaaliso koronta xad dhaafka ah, gaar ahaan meelaha u nugul in uu danabku ku dhaco ama khalkhal ku yimaad shabkada. Transformer-ku waxa kale oo ka mid ah bixinta barroosinka seismic, xoojinta xasilloonida qaabdhismeedkeeda si ay ugu adkaysato dhaqdhaqaaqa dhulgariirka, taas oo ka dhigaysa mid ku habboon in la geeyo gobollada halista badan{2}} dhulgariirrada-. Tilmaamahan horumarsan waxay si wadajir ah u wanaajiyaan amniga hawlgalka, yaraynta qalliinka, iyo u adkaysiga musiibada, iyaga oo u adeegaya codsiyada kaabayaasha muhiimka ah sida tas-hiilaadka warshadaha, shabakadaha tamarta, iyo nidaamyada korantada degdegga ah ee aagagga seismically firfircoon.

 

 

 

1.2 Tilmaamaha Farsamada

500 KVA suuf ku rakiban nooca tafatirka beddelka iyo xaashida xogta

loo geeyey
Kanada
Sannadka
2025
Nooca
suuf ku rakiban transformer
Heerka
CSA C227.4:21
Awood lagu qiimeeyay
2500 kVA
Soo noqnoqda
60HZ
Marxaladda
3
Quudinta
Radial
Hore
dhintay
Nooca qaboojinta
ONAN
Korantada aasaasiga ah
4.16D kV
Voltage Secondary
0.6Y/0.347 kV
Qalabka dabaysha
Aluminium
barokaca xagal
Dyn1
Caqabada
3.1%
Taabo Beddelka
NLTC
Riixista Range
±2*2.5%
Wax Xamuul ah ma jiro
0.36 kW
Load Lumista
9 kW

 

 

1.3 Sawirro

500 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.

three phase distribution transformer diagram

three phase distribution transformer drawing

three phase distribution transformer nameplate

 

 

02 Wax-soo-saarka

2.1 Core

CSA- suufka u hogaansan -ku dhejinta transformer-ka waxa uu ku dara - nabarka waxtarka leh ee silikon birta xudunta u ah, loogu talagalay in uu la kulmo hufnaanta tamarta adag iyo heerarka waxqabadka. Dhismaha xudunta nabarku waxa uu hubinayaa isku toosinta qulqulka magnetka ee ugu fiican, si weyn u yaraynaysa - khasaaraha rarka 15 - 25% marka la barbar dhigo koofiyadaha la dahaadhay ee dhaqameed iyada oo la xoojinayo iska caabinta iswaafajinta{101} CSA- waxay shahaado siisay badbaadada iyo isku halaynta.

CSA-compliant

 

2.2 Dabaylaha

transformer winding machine

Transformer-ka gariiradda dabaysha waxa ay adeegsataa tignoolajiyada horumarsan ee gariiradda dabaysha, isku darka hoose -foil foil voltage (aluminium foil) iyo sare{1}}lakabka korantada (siliga naxaasta) si loo helo hufnaan sare iyo isku halaynta. Dhinaca hoose ee - dhinaca korantada waxa ay shaqaaleysiisaa dhowr-lakab caabbinta caabbinta wareega ah, oo bixisa qaab dhismeed is haysta, kulaylka sareeyo, iyo caabbinta wareegga gaaban ee gaaban. Dhinaca sare - dhanka danabku waxa uu leeyahay dabaylaha silig naxaas ah, hubinta dhaqdhaqaaqa wanaagsan iyo xoogga farsamada Iyada oo leh naqshad coaxial ah oo hagaajinaysa cufnaanta awoodda iyo kor u kaca heerkulka.

 

2.3 Haanta

Taangiga Transformer-kan waxa laga dhisay Bir khafiif ah, oo bixisa xoog farsamo oo adag iyo cimri dheer- Taangiga waa la lingaxay waxaana lagu daaweeyaa dahaarka lidka ku ah - (tusaale, rinjiyeynta ama galvanization) si ay ugu adkaysato xaaladaha adag ee dibadda. Naqshadeeda shaabadaysan oo kuleyl leh ayaa waxaa ka mid ah feeraha xoojinta si ay u xoojiso iska caabinta cadaadiska, ka hortagga qallafsanaanta balaarinta saliidda ama{6}} ciidamada wareegyada gaaban. Astaamaha caadiga ah sida dekedaha buuxinta saliidda, tilmaamayaasha heerka, iyo aaladaha cadaadiska cadaadiska ayaa xaqiijinaya dayactirka badbaadada iyo fududaynta. Qiimaha fudud ee birta - wax ku oolnimada iyo isku halaynta ayaa ka dhigaya agab la door biday dhexdhexaadin -

welded transformer tank

 

2.4 Kirk Key

20251203092939882177

KIRK Nooca F interlock waa furaha isdhexgalka farsamaysan ee ku habboon xakamaynta qalabka korontada. Cutubka caadiga ah wuxuu la socdaa bir aan lahayn 5/8" dhexroor quful quful ah oo leh tuur ama safar ah 3/4". Xirmada qufulka waxaa loo isticmaalaa in lagu xakameeyo wareegtada ama dhaqdhaqaaqa gacan-qabashada ama beddelka qalabka korontada. Alaab-qeybiyeyaal badan oo qalabka wax lagu beddelo ayaa leh qalab kor u kaca oo diyaar u ah xirmooyinka KIRK. Qufulka waxaa lagu soo saaray naxaas ama bir aan daahin.

 

 

03 Tijaabinta

 

dga test
dga oil test

 

 

04 kale

4.1 Qodobbada barroosinka seismic

Qodobbada barroosinka seismic ee suufka lagu dhejiyay{0}Transformers-ku-xidhan waxay tixraacaan hababka xidhitaanka ee la farsameeyay iyo qeexida rakibida ee loogu talagalay in lagu sugo unugga aasaaskeeda la taaban karo inta lagu jiro dhacdooyinka seismic. waxay sifaysan tahay sida -oo hore loo qoday-daloolada barroosinka xooga leh ee salka iyo isticmaalka xidhmooyinka seismic ee shahaadaysan iyo boolalka barroosinka. Shaqadooda aasaasiga ah waa inay ka hortagaan transformer-ku inuu beddelo, rogo, ama simbiriirixdo, si markaas loo hubiyo qaabdhismeedkiisa, ilaalinta isku xirka korantada, iyo ka hortagga khataraha labaad (sida dabka ama daadinta saliidda) marka ay la kulmaan xoogag dardargelin ah oo dhulka ah. Tani waa badbaado halis ah oo loo baahan yahay tafaftirayaasha lagu rakibay dhulgariirka- gobolada u nugul

20251203092940883177

 

4.2 dhoofinta

marine insurance

Marka loo eego shuruudaha CIF, iibiyuhu waxa uu dabooshaa kharashka, caymiska badda, iyo xamuulka dekedda uu ku socdo (sida caadiga ah Vancouver) ee Pad {{0}Mounted Transformers oo loo soo raro Winnipeg, Canada, iyada oo ay la socoto khatarta u wareejinta iibsadaha ee dekedda rarka. Transformers waa in lagu soo buuxiyaa qoyaan -sanduuqyo/qariifyo bir ah oo aan lahayn calaamado wax qaadis ah iyo calamadaha caarada, oo ay la socdaan qaansheego ganacsi, B/L, iyo shahaado CSA. Ka dib xamuulka badweynta ee Vancouver, iibsaduhu wuxuu gacanta ku hayaa fasaxa kastamka iyo gaadiidka gudaha ee tareenka (5-7 maalmood) ama xamuulka Winnipeg, isagoo xusaya dib u dhacyada jiilaalka. Iibiyuhu waxa uu caymiyaa 110% qiimaha xamuulka, halka iibsaduhu uu bixiyo cashuuraha iyo kharashka gaadiidka gudaha.

 

 

05 Goobta iyo Kooban

Sida qayb muhiim ah oo ka mid ah nidaamyada awood qaybinta, suufka {{0}Mounted Transformer wuxuu keenaa xalal awoodeed la isku halayn karo, hufan, iyo deegaan saaxiibtinimo u leh warshadaha, ganacsiga, iyo kaabayaasha dadweynaha. Isku darka tignoolajiyada cusub iyo heerarka tayada adag, waxaanu hubinaynaa in transformer kastaa bixiyo -waxqabad waara ee deegaan baahida iyadoo la wanaajinayo hufnaanta tamarta lana yareynayo kharashyada dayactirka.

Haddi aad u baahan tahay nashqado la habeeyey ama hufnaanta tamarta sare, kooxdayada khubarada ah waxay bixiyaan dhamaadka{0}ilaa{1}} dhamaadka taageerada. Noo door qaybinta awood la isku halayn karo oo caqli badan{3}} dhisida mustaqbal tamar waara

Maanta nala soo xidhiidh si aad u hesho xal ku habboon!

high energy efficiency

 

Hot Tags: saddex waji qaybinta transformer, saaraha, alaab-qeybiyaha, qiimaha, kharashka