500 KVA Radial Feed Transformer-12.47*4.16/0.6 KV|Kanada 2024

500 KVA Radial Feed Transformer-12.47*4.16/0.6 KV|Kanada 2024

Dalka la geeyey: Kanada 2024
Awoodda: 500kVA
Voltage: 12.47Grdy/7.2 X 4.16Grdy/2.4-0.6y/0.347 kV
Muuqaalka: Iyadoo IFD
U dir sooji

 

500 kVA Radial Feed Transformer

Waxtarka sare - 500 kVA Radial Feed Transformer ee la isku halayn karo iyo qaybinta korantada

 

 

01 Guud

1.1 Sharaxaada Mashruuca

2024, macmiil Canadian ah ayaa helay 500 kVA saddex{2}}waji suuf{3}} ku rakiban Scotech. Transformer-ka waxa loo nashqadeeyay oo loo sameeyay si waafaqsan CSA Standard C227.4:21. Cutubka waxaa loogu talagalay in lagu rakibo bannaanka suufka shubka ah. Waxay siisaa xal kooban oo badbaado leh oo loogu talagalay qaybinta awoodda deegaanka iyo ganacsiga.

Tani waa 500 kVATransformer feed radial waxay ONAN u isticmaashaa qaboojinta iyo saliida macdanta si ay u ilaaliso. Dabaylaha aluminiumku wuxuu bixiyaa dheelitirnaan wanaagsan oo waxtarka, miisaanka, iyo qiimaha. Waxaa lagu qiimeeyay 500 kVA, 60 Hz, oo leh danab hoose oo ah 12.47/4.16 kV iyo danab labaad oo ah 0.6 kV, oo loo habeeyey koox Véctor YNyn0 ah.

Cutubka waxaa loogu talagalay shabakadaha quudinta radial, kuwaas oo awood ku bixiya hal waddo oo ka timaada substation-ka macaamiisha. Nidaamyada shucaaca waa sahlan yihiin, kharash{1} wax ku ool ah, oo ku haboon meelaha la isku halayn karo lagu maareeyo furayaasha kala qaybiya

Si loo oggolaado nidaaminta danab dabacsan, taransfooriyuhu waxa uu ku qalabaysan yahay maya -load tap changer (NLTC), oo bixinaya ±2×2.5% taabasho. Waxay gaadhaa 99.05% hufnaan, iyada oo aan lahayn - khasaare rarka Wax ka yar ama le'eg 1090 W iyo khasaaraha culayska In ka yar ama la mid ah 5800 W. Waxaa loo dhisay adkeysiga, waxa ay la timaadaa heerka CSA{9} qalabyada u hogaansan waxayna u taagan tahay xal la isku halayn karo ee shabakadaha qaybinta Kanadiyaanka.

 

 

 

1.2 Tilmaamaha Farsamada

500 kVA radial feed transformer tilmaanta iyo xaashida xogta

loo geeyey
Kanada
Sannadka
2024
Nooca
Saddex weji suuf Buur Transformer
Heerka
CSA C227.4:21
Awood lagu qiimeeyay
500KVA
Soo noqnoqoshada
60HZ
Quudinta
Radial
Hore
dhintay
Marxaladda
saddex
Nooca qaboojinta
ONAN
Insulant dareere ah
Saliidda Macdanta
Korantada aasaasiga ah
12.47 (4.16) kV
Voltage Secondary
0.6 kV
Kooxda Vector
YNyn0
Qalabka dabaysha
Aluminium
Caqabada
5 %
Waxtarka
99.05%
Taabo Beddelka
NLTC
Riixista Range
±2*2.5%
Wax Xamuul ah ma jiro
In ka yar ama la mid ah 1090 W
Load Lumista
In ka yar ama la mid ah 5800 W
Agabka
Habaynta caadiga ah

 

1.3 Sawirro

500 kVA radial feed transformer sawir iyo saxan magaceed

500 kVA Radial Feed Transformer drawing 500 kVA Radial Feed Transformer nameplate

 

 

02 Wax-soo-saarka

2.1 Core

Xudunta xudunta shanta{{0} addintu waxay ilaalisaa qulqulka magnetic dhammaan saddexda weji. Naqshadani waxay yaraynaysaa qulqulka iyo luminta. Xuddunta waxay isticmaashaa 0.30-0.35 mm xaashiyo bir silikoon ah oo leh xoog bir ah oo sarreeya iyo iska caabin hoose. Natiijadu waxay tahay waxtarka wanaagsan iyo qaylada hoose inta lagu jiro hawlgalka.

 

2.2 Dabaylaha

Transformer-kani waxa uu leeyahay dabaylaha aluminium. Gariiradda ayaa ku dhaawacantay bireed loogu talagalay danab yar iyo silig loogu talagalay danab sare. Naqshadani waxay hubisaa qaybinta isku midka ah ee hadda jira, caabbinta wareegga wareegga ah ee gaaban, iyo qaboojinta waxtarka leh. Iyada oo leh 5% impedance iyo 99.05% hufnaan, transformer-kani waxa uu keenaa waxqabad xasiloon oo hufan oo hoos yimaada xaalado culeysyo kala duwan.

 

2.3 Haanta

500 kVA Radial Feed Transformer oil tank

Taangiga khafiifka ah ee la shaabadeeyey ee - oo leh dabool daboolan ayaa loo isticmaalaa 500 kVA radial feed transformer. Waxay u adkeysan kartaa 50 kPa cadaadis gudaha ah oo aan lahayn qulqulo ama qallooc ka badan 0.25% cabbirka dhinaca. Golaha wasiirada waxaa loo dhisay si loogu isticmaalo dibadda, faragalin{6}}iska adkeysi iyo cimilo-, waxaana lagu ilaaliyay boolal maxaabiis ah oo pentahead ah sida ku cad CSA C227.4.

 

2.4 Kulanka ugu dambeeya

Waxaan leenahay koox si xirfadaysan loo tababaray oo si adag loo qiimeeyay, kuwaas oo si joogto ah ugu gudbiya waayo-aragnimo wax ku ool ah oo qiimo leh iyada oo loo marayo sayid{0}}nidaamka tababarka. Goobta wax soo saarka, waxaan hirgelineynaa kantaroolka habka jilicsan, iyadoo la hubinayo in habka isu-ururinta transformer kasta uu gacanta ku hayokormeer tayo leh oo dhamaystiraniyo duubista xogta muhiimka ah. Isku dhafka dabiiciga ah ee fulinta kooxda xirfadlayaasha ah iyo ilaalinta kontoroolka caatada ah waxay hubisaa tayada gaarka ah.

 

 

03 Tijaabinta

Imtixaanka Heerka iyo Imtixaanka Joogtada ah

CSA C227.4-21

Saddex - waji,suufka - ku rakiban transformers qaybinta Xidhiidhiyayaasha korantada ee sare-

CSA{0}C802.1-13 (R2022)

Qiimaha Hufnaanta Ugu Yar ee Dareere -Beddelayaasha Qaybinta Buuxa

 

1. Cabbiraadaha iska caabinta
2. Imtixaanada saamiga
3. Imtixaanka Xiriirka Wajiga
4. Wax Khasaare ah oo Xamuul ah oo Hadda socda ma jiro
5. Load Khasaaraha Korontada iyo Waxtarka
6. Tijaabada Voltage ee la dabaqay
7. Tijaabada adkaysiga korantada ee keentay
8. Tijaabada Diidida oo leh Cadaadis loogu talagalay beddelayaasha Dareeraha Immersed
9. Cabbirka iska caabbinta dahaarka
10. Tijaabada Dielectric Oil
 

500 kVA Radial Feed Transformer testing
500 kVA Radial Feed Transformer Test

Natiijooyinka Imtixaanka

Maya

Shayga Tijaabada

Unug

Ogolaanshaha

Qiimaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbiraadaha iska caabinta

%

Qiyaasta dheelitir la'aanta iska caabbinta ugu badan

1.17

Gudub

2

Imtixaanada saamiga

%

Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5%

-0.03-0.10

Gudub

3

wajiga- imtixaanada xidhiidhka

/

YNyn0

YNyn0

Gudub

4

Maya- khasaarooyinka rarida iyo xamaasadda hadda

/

I0 :: bixiyaan qiime la qiyaasay

0.39%

Gudub

P0: bixi qiimaha la qiyaasay

0.7455kW

Dulqaadka wax qabad la'aan waa +10%

/

5

Load khasaaraha danab impedance iyo hufnaan

/

t:85 darajo

dulqaadka impedance waa ± 7.5%

dulqaadka wadarta rarka luminta waa +6%

/

Gudub

Z%: qiimaha la qiyaasay

5.36%

Pk: qiimaha la qiyaasay

4.534kW

Pt: qiimaha la qiyaasay

5.312kW

Waxtarka aan ka yarayn 99.05%

99.28%

6

Tijaabada Korantada ee La dabaqay

kV

LV: 10kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada adkaysiga korantada ee keentay

kV

Danab la dabaqay (KV):

2 Uur

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

Muddada:30

Inta jeer (HZ): 240

8

Tijaabada daadinta

kPa

Cadaadiska la dabaqay: 20kPA

Muddada: 12h

Wax daadsan iyo maya

Waxyeello

Gudub

9

Cabbirka iska caabinta dahaarka

GΩ

LV-HV ilaa Ground

6.3

/

HV&LV ilaa Ground

9.5

10

Tijaabada Saliida

/

Xoogga Dielectric;

56.2 kv

Gudub

Nuxurka qoyaanka

11.9 mg/kg

Qodobka Burburinta

0.00342%

Falanqaynta Furan

In ka yar ama la mid ah 0.1

Falanqaynta Chromatography ee Gaaska

/

 

 

04 Baakaynta iyo dhoofinta

500 kVA Radial Feed Transformer packing
500 kva radial feed transformer-export-packing
500 kVA Radial Feed Transformer shipping

 

05 Goobta iyo Kooban

500 kva radial feed transformer-back-view

Sadexdan 500 kVA ee - wajiga suufka ah -ku rakiban Transformer waxa loo dhisay Kanada. Waxay raacdaa CSA C227.4:21 waxaana loo sameeyay badbaado, wax ku ool ah qaybinta tamarta dibadda. Waxa ay leedahay suuf is haysta-naqshad ku rakiban oo si fiican uga shaqaysaa shabakadaha deegaanka iyo ganacsiga labadaba. Nashqada xudunta u ah shanta - addintu waxa ay ilaalisaa dheeli tirnaanta waxayna yaraynaysaa qaylada. Haanta birta xidhani waa mid xoog badan, cimiladu ma ilaaliso Transformer kasta waxaa sameeya shaqaale xirfad leh oo si adag loo ilaalinayo. Waxay ku shaqeysaa 99.05% hufnaan, khasaaro yar, iyo danab deggan. Waa doorasho waarta oo la aamini karo ee nidaamyada korantada Kanada.

 