1000 kVA suuf Buurta Beddelayaasha Iibka-4.16/0.48 kV|USA 2025
Awoodda: 1000 kVA
Voltage: 4.16D-0.48Y/0.277 kV
Feature: oo leh waalka Schrader

Saddex - suufka wejiga - ku rakiban transformer: Hogaaminaya waayaha cusub ee awooda garaadka, iftiiminta gees kasta.
01 Guud
1.1 Dulmar & Shuruudaha Macaamiisha
Sannadkii 2025, waxaanu siinay 1000 kVA saddex{2}}waji -ku rakiban transformer (4.16 kV Delta / 0.48Y/0.277 kV, Dyn1, ONAN, ±2×2.4% NLTC) suuqyada Maraykanka.
Habaynta farsamada waa heer, laakiin caqabadaha ka dambeeya shuruudaha macaamiisha ayaa ka fog kuwa fudud.
Qodobbada Xanuunka Macmiilka ee Muhiimka ah
1. Badbaadada meelaha dadku ku badan yihiin ama kuwa xidhan
suufka -Transformers ee lagu rakibay waxay inta badan fadhiyaan meelo cidhiidhi ah{1}} oo ku xiga wadooyinka lugaynta, meelaha dukaamada, meelaha baabuurta la dhigto, ama deyrarka tamarta yar. Macaamiishu waxay u baahan yihiin unug ilaalinaya iyada oo aan loo eegin cidda ag maraysa ama cidda dayactiraysa. Ma jiro kor u kacay -voltage, lama xidhiidh shil, lama filaan ah.
2. Muddo dheer{{1}Aad u adkaysatid Cimilada iyo Deegaanka
Roobka, qoyaanka, ceeryaamo milix ah, heerkul kedis ah oo isbedbeddela - sanadba sanadka ka dambeeya, xayndaabku wuxuu wajahayaa cadaadis joogto ah. Macaamiishu waxay rabaan transformer-ka aan dumin, daadin, ama hoos u dhigi doonin, oo ilaalinaya qaybaha gudaha muddo tobanaan sano ah.
3. Hawlgalka xasiloon ee ku jira xaaladaha culeyska isku dhafan
Isku-xidhka magaalooyinka iyo ganacsiga si dhif ah ayay u dhaqmaan si saadaaliya. Meelaha ugu sarreeya ee la deggan yahay habeenkii, ganacsiga ugu sarreeya inta lagu jiro maalinta, marmarka qaarkood kor u kaca warshadaha -dhammaan waxay dalbanayaan transformer ah oo dheeli tiran, ka fogaanaya kulaylka, oo keena danab joogto ah oo aan kala go' lahayn.
4. Kharash Nololeed Hoose oo Dayactirka Ugu Yar
Khasaaraha tamarta ayaa urura, dayactirka joogtada ahna ma aha mid raqiis ah. Macaamiishu waxay raadiyaan taransfoorka "si degan ugu socda dhabarka," oo leh khasaare hoose, la socodka fudud, iyo wakhtiga dhimista-iyado si buuxda ugu hoggaansamaya heerarka IEEE/ANSI ee is dhexgalka fudud ee isticmaalka.
1.2 Xalkayaga
Loop - Quudin + Dhintay -Naqshad si buuxda u xidhan oo hore
Mashruucan, badbaadadu ma ahayn kaliya shuruud{0}}waxay ahayd meesha laga bilaabo.
Waxaan dooranay aloop-Nidaamka quudintaleh adhintay - hore, qaab dhismeed si buuxda u xidhan, mid ka mid ah qaabaynta ugu nabdoon ee shabakadaha qaybinta magaalooyinka iyo ganacsiga casriga ah.
Ma jiro terminal qaawan Ma jirto khatar xiriir shil ah. U nuglaanta roobka, boodhka, ama gacmaha xiisaha leh. Interface-ka HV waxa uu ahaanayaa mid ku xidhan qol adag, isaga oo siinaya hawl wadeenada kalsooni xataa marka ay dadku ku badan yihiin ama meel banaan ah{3}} deegaan xaddidan. Iyadoo loop{5}} quudinta dabacsanaanta, qayb ka mid ah shabakada waa la ilaalin karaa iyada oo aan la xidhin nidaamka oo dhan -Deeqsi yar, hawlgalo fudud, iyo rakibid nadiif ah guud ahaan.
Tani waa agabka naqshadaynta ee ay si joogto ah u doortaan marka la isku halaynta iyo badbaadada dadweynuhu ay tahay inay marka hore timaado.
Dabaysha Aluminium + Fool LV + Sare -Waxqabadka Waxqabadka Waxqabadka
Waxaan sidoo kale u wanaajinay waxa muhiimka ah - muddada: kharashka hawlgalka.
Transformer-ka ayaa isticmaaladabaylaha aluminiumdhanka HV iyobuuxa -dhismaha xaashiyahadhinaca LV -fudud, hufnaan, iyo farsamo ahaan ku xoogan marka la eego xaaladaha dhabta ah ee aduunka.
Oo hufnaanta ayaa ka hadlaysa lafteeda.
leh1.3 kW maya - rarka khasaareiyo6.94 kW culayska lumay, cutubku wuxuu keenaa waxqabad sare oo la isku halayn karo oo leh qashinka tamarta oo yaraaday. Biilasha hoose, diiqada kulaylka oo yaraada, iyo nolosha dahaarka oo dheer. Waa nooca wax-ku-oolnimada ee si deggan u bixiya sannad kasta.
Xidhmada Dabagalka & Ilaalinta Dhamaystiran
Hawlgalka badbaadada leh waxa kale oo uu ka dhigan yahay ogaanshaha waxa haanta gudaheeda ka dhacaya.
Cutubkani waxa uu ku qalabaysan yahay xidhmo ilaalin iyo ilaalin dhamaystiran, oo ay ku jiraan:
Qiyaasta heerka saliidda
garaac heerkulbeegga
Cadaadiska -cabirka vacuum
Cadaadiska cadaadiska
Qalabka cadaadiska degdega ah
Dekadda muunadda gaaska
Si wada jir ah, qaybahani waxay u dhaqmaan sidii nidaamka digniinta ugu horayso -fudud, la isku halayn karo, oo u fududahay farsamayaqaannada goobta si ay u tarjumaan. Waxay caawiyaan inay ogaadaan kor u kaca heerkulka, gaasta xanniban, cadaadiska aan caadiga ahayn, ama luminta saliidda ee jaleecada, hagaajinta wakhtiga jawaabta marka shabagga la adkeeyo.
Naqshadeeyay & La tijaabiyay IEEE C57.12.34-2022
Qeexitaan kasta oo muhiim ah - laga bilaabo xoogga makaanikada ilaa kor u kaca heerkulka iyo waxqabadka dielectric{1}} ayaa raacayaIEEE C57.12.34-2022, heerka qeexida Waqooyiga Ameerika -Transformers-ka qaybinta ku rakiban.
Tani waxay hubinaysaa in cutubku uu si aan kala go 'lahayn ula midoobin rajada tamarta ee gobolka oo dhan.
Naqshad la socota shabkada US, oo loo dhisay mid la isku halayn karo, adeeg muddo dheer-
1.3 Tilmaamaha Farsamada
1000 KVA suuf ah oo ku rakiban nooca beddelka iyo xaashida xogta
|
loo geeyey
Ameerika
|
|
Sannadka
2025
|
|
Nooca
suuf ku rakiban transformer
|
|
Heerka
IEEE StdC57.12.34-2022
|
|
Awood lagu qiimeeyay
1000KVA
|
|
Soo noqnoqda
60 HZ
|
|
Marxaladda
3
|
|
Quudinta
Loop
|
|
Hore
dhintay
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
4.16D kV
|
|
Voltage Secondary
0.48Y/0.277 kV
|
|
Qalabka dabaysha
Aluminium
|
|
barokaca xagal
Dyn1
|
|
Caqabada
5.75%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.4%
|
|
Wax Xamuul ah ma jiro
1.3kW
|
|
Load Lumista
6.94 kW
|
|
Agabka
Habaynta caadiga ah
|
1.4 Sawirro
1000 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Sadexda - qaab dhismeedka tiirka waxa uu bixiyaa taageero madax banaan waji kasta, taas oo u ogolaanaysa qaybinta culayska lebbiska ah ee tiir kasta inta lagu jiro hawlgalka. Tani waxay yaraynaysaa faragelinta magnetic iyo khasaaraha tamarta, hubinta soo saarista tamarta deggan. Naqshadeynta xudunta u ah waxay ka kooban tahay wareegga magnetka xiran oo si weyn hoos u dhigaya saturation magnetic iyo khasaaraha, kor u qaadaya guud ahaan waxtarka gudbinta tamarta ee beddelka. Ka faa'iidaysiga xaashida birta silikoon oo leh awood sare leh sida maaddada xudunta u ah kaliya ma wanaajinayso korantada laakiin sidoo kale waxay si wax ku ool ah u yaraynaysaa khasaaraha hadda jira iyo kuleylka, hubinta hawlgalka hufan ee qalabka.

2.2 Dabaylaha

Hooseeyo-Dabaylaha Faylka Voltage
Qaab dhismeedka: Birta birta waxay kordhisaa awoodda hadda jirta waxayna yaraynaysaa khasaaraha.
DahaarkaWaxay xoojisaa xasiloonida isticmaalka korantada yar -
Kulaylka Kala DiriddaWaxay caawisaa qaybinta kulaylka hufan.
EMI: Waxay yaraynaysaa faragelinta korantada.
Sare -Wireyga Voltage Dabaysha
DhismahaWaxay u isticmaashaa silig aluminium ah gudbinta korantada ee hufan-
Dahaarka: Waxay ka ilaalisaa wareegyada gaaban.
Dabacsanaanta rarka: La qabsada culeysyada kala duwan.
Iska caabinta gariirka: Waxay xaqiijisaa isku halaynta walaaca.
2.3 Haanta
Mashiinka saxda ah ee birta iyadoo la isticmaalayo goynta laser ama tignoolajiyada goynta balaasmaha. Saxanka birta ah waa la xoojiyey oo la sameeyay, saxnaanta foorarsigana waxaa lagu hubiyaa qalab toos ah. Qaado habka alxanka heerka sare ah, sida alxanka tooska ah ama alxanka argon-ga gacanta, si loo hubiyo xoogga iyo adkaanta alxanka. Taangiga oo dhan waa la ciide si looga saaro lakabka oksaydhka ka dibna lagu buufiyaa furaha iyo jaakad sare si kor loogu qaado caabbinta daxalka. Deegaannada gaarka ah, kulaylka-kuleelka galvanizing ama dahaarka kale ee horumarsan ayaa sidoo kale la isticmaali karaa.

2.3 Kulanka ugu dambeeya

Rakibaadda Cutubka Muhiimka ahKor u qaad transformer-ka, ku xidh khadadka tamarta sare iyo kuwa hoose, oo hubi in dhulka la dhigay.
Isku xirka Xadhkaha: Ku xidh terminal danab sare iyo mid hooseeya oo xaqiiji jaantuska xargaha.
Agabka iyo qaboojinta: Ku rakib nidaamka qaboojinta iyo qalabka lagama maarmaanka ah.
Bilawga iyo DejintaSamee hubin dhamaystiran, shid tijaabada, iyo dib u habeynta diiwaan gelinta.
2.4 Qaybaha






03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
% |
Qiyaasta dheelitir la'aanta iska caabbinta ugu badan |
2.93 |
Gudub |
|
2 |
Imtixaanada saamiga |
% |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% |
-0.13 |
Gudub |
|
3 |
Wajiga{0}}imtixaamaadka xidhiidhka |
/ |
Dyn1 |
Dyn1 |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% |
I0 : bixiyaan qiime la qiyaasay |
0.43 |
Gudub |
|
kW |
P0: Bixi qiimaha la qiyaasay (85 darajo) |
1.289 |
|||
|
/ |
Dulqaadka wax qabad la'aan waa ± 10% |
/ |
|||
|
5 |
Khasaaraha load , danab impedance, khasaaraha guud iyo hufnaan |
/ |
t: 85 darajo dulqaadka impedance waa ± 7.5% Dulqaadka wadarta rarka luminta waa ± 6% |
/ |
Gudub |
|
% |
Z%: qiimaha la qiyaasay |
5.42 |
|||
|
kW |
Pk: qiimaha la qiyaasay |
7.223 |
|||
|
kW |
Pt: qiimaha la qiyaasay |
8.451 |
|||
|
% |
Waxtarka aan ka yarayn 99.43% |
99.43 |
|||
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
HV: 19kV 60s LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV): 0.96 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
Muddada: 48 |
|||||
|
Inta jeer (HZ): 150 |
|||||
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV -LV ilaa Dhulka: |
20.8 |
/ |
|
LV-HV ilaa Dhulka: |
31.0 |
||||
|
HV&LV ilaa Dhulka: |
19.4 |
||||
|
9 |
Tijaabada daadinta |
/ |
Cadaadiska la dabaqay: 20kPA |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
Muddada: 12h |
|||||
|
10 |
Tijaabada Saliida |
kV |
Xoogga Dielectric |
54.9 |
Gudub |
|
mg/kg |
Nuxurka qoyaanka |
9.7 |
|||
|
% |
Qodobka Burburinta |
0.00227 |
|||
|
mg/kg |
Falanqaynta Furan |
/ |
|||
|
/ |
Falanqaynta Chromatography ee Gaaska |
/ |


04 Baakaynta iyo dhoofinta


05 Goobta iyo Kooban
Isku soo wada duuboo, sadexdayada{0}xajisyada- ee ku rakiban taransfoorayaasha ayaa bixiya hawlqabad adag iyo xalal awood qaybsi la isku halayn karo oo codsiyo kala duwan ah. Naqshadeeda is haysta, rakibaadda fudud, iyo astaamaha badbaadada sare, waa doorasho ku habboon nidaamyada korantada ee casriga ah ee u baahan waxtarka iyo cimri dhererka. Waxaa naga go'an inaan bixino{4}}alaab tayo sare leh oo buuxiya baahiyaha kobcaya ee macaamiisheena, anagoo hubinayna waxqabadka ugu wanaagsan iyo qanacsanaanta. U dooro transformers-keena baahida tamarta oo khibrad kala duwanaanshaha tayada iyo adeegga.

Hot Tags: Transformers-yada suufka ah ee iibka ah, soo saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
75 kVA Pad Mount Transformer-22.86 / 0.208 kV|USA 2024
1500 kVA suuf Ku rakiban Beddelka-34.5/0.48 kV|USA 2024
2500 kVA Pad Mount Transformer-12.47 / 0.48 kV|USA 2025
112.5 kVA Dhintay Transformers hore-22.86/0.208 kV|U...
2000 kVA suuf Ku rakiban Beddelka-24/0.48 kV|USA 2024
1000 kVA Dhintay Beddelka Hore-24/0.48 kV|USA 2024
U dir sooji