1000 kVA Dhintay Beddelka Hore-24/0.48 kV|USA 2024

1000 kVA Dhintay Beddelka Hore-24/0.48 kV|USA 2024

Dalka la geynayo: USA 2024
Awoodda: 1000kVA
Voltage: 24000 D-480Y/277 V
Feature: oo leh feedthru insert
U dir sooji

 

 

1000 kva dead front transformer-front-door-open

1000 kVA dhintay{1} suufka hore -Transformer ku rakiban - badbaado leh, hufan, oo loo dhisay awood qaybin la isku halayn karo goob kasta.

 

 

01 Guud

1.1 Sharaxaada Mashruuca

Waxaa loo geeyey USA 2024, kan 1000 kVAsaddex{0}} suufka wejiga{1} ku rakibanu hoggaansama IEEE Std C57.12.34{11}}2022 oo buuxiya DOE 2016 heerarka hufnaanta tamarta. Waxay ku shaqeysaa 60 Hz oo leh danab hoose oo ah 24 kV iyo koronto labaad oo ah 480GrdY/277 V, oo ay ku jiraan koox kooxeed Dyn1. Transformer-ku wuxuu isticmaalaa dabaylaha naxaasta ah iyo qaboojinta KNAN, waxaana ka buuxsamay FR3 saliid ester dabiici ah si kor loogu qaado badbaadada dabka iyo sii jirista deegaanka. Ku qalabaysan shaqaynta quudinta loop, dhintay- gelida hore, iyo maya{16}loader tuubada oo bixisa ±2 × 2.5% kala duwan ee nidaaminta danab, unuggu waxa uu leeyahay 5.75% impedance, maya{18}} lumitaanka 1.020 kW, iyo - 10 kW oo ku xidhan qaybinta korantada dhexdhexaadka ah.

Transformer-ka hore ee 1000 kVA ee dhintay wuxuu yareeyaa khatarta fallaadhka fallaadhka inta lagu jiro hawlgalka ama dayactirka. Dhismaheeda hore ee dhintay waxaa ka mid ah kaymaha caagga ah ee si buuxda u dahaaran, oo leh joojinta lagu sameeyay xusullada jabinta, hubinta badbaadada iyo fududaynta isku xidhka.

1000 kVA dhintay suufka hore ee buurta beddelka wuxuu u adeegaa sidii xal awoodeed oo kooban oo hufan oo loogu talagalay isticmaalka, ganacsiga, iyo codsiyada warshadaha. Waxaa loogu talagalay adkeysiga, waxaa lagu rakibi karaa gudaha iyo dibaddaba, iyadoo la siinayo nidaam tamar la isku halayn karo oo badbaado leh oo ku baahsan deegaanno kala duwan.

 

 

 

1.2 Tilmaamaha Farsamada

1000kVA saddex weji oo dhintay tafatirka hore iyo xaashida xogta

loo geeyey
USA
Sannadka
2024
Nooca
Saddex weji suuf Buur Transformer
Heerka
IEEE Std C57.12.34-2022
Awood lagu qiimeeyay
1000 kVA
Soo noqnoqoshada
60HZ
Quudinta
Loop
Hore
dhintay
Marxaladda
Saddex
Nooca qaboojinta
KNAN
Insulant dareere ah
FR3 Saliid
Korantada aasaasiga ah
24 kV
Voltage Secondary
0.48 kV
Kooxda Vector
Dyn1
Qalabka dabaysha
Copper
Caqabada
5.75%
Heerka Waxtarka iyo Khasaaraha
DOE 2016
Taabo Beddelka
NLTC
Riixista Range
±2*2.5%
Wax Xamuul ah ma jiro
1.020 kW
Load Lumista
8.170 kW
Agabka
Habaynta caadiga ah

 

 

1.3 Sawirro

1000kVA saddex waji oo dhintay sawir beddelka hore iyo saxanka magaca

1000 kva dead front transformer-outline-drawing 1000 kva dead front transformer-nameplate

 

 

02 Wax-soo-saarka

2.1 Core

Koofiyadaha SCOTECH waxaa lagu soo saaray kontorool tayo adag, iyadoo la hubinayo isugeynta saxda ah, cadaadiska lebbiska lebbiska ah, iyo toosinta birlabeedka joogtada ah. Nidaamkani wuxuu si wax ku ool ah u yareeyaa farqiga hawada iyo cadaadiska farsamada ee xudunta u ah, hagaajinta sharafta qaab dhismeedka iyo yaraynta khatarta dhibcaha kulul.

1000 kva dead front transformer-iron-core

 

2.2 Dabaylaha

1000 kva dead front transformer-windings-dyn1

Loo dhisay isticmaalka ganacsiga iyo warshadaha, 1000 kVA Dyn1 transformer-ka waxa uu qaataa xaashida-nabarka gariiradaha LV iyo warqad{3}} gariiradaha HV ee silig naxaas ah Qaab dhismeedka la hagaajiyay wuxuu xaqiijinayaa dahaarka la isku halayn karo, buuq yar, iyo adkaysiga la xoojiyay ee hoos yimaada 24 kV iyo xaaladaha culeyska ee kala duwan.

 

2.3 Haanta

Taangiga beddelka wuxuu ka ilaaliyaa qaybaha gudaha ee shooga farsamada, gariirka, iyo xoogga dibadda. Qaab dhismeedka birta ee la xoojiyey waxay hubisaa in inta lagu jiro gaadiidka iyo rakibidda, qaybaha muhiimka ah ay yihiin kuwo si fiican loo ilaaliyo oo si ammaan ah loo dhigo.

1000 kva dead front transformer-transformer-oil-tank

 

2.4 Kulanka ugu dambeeya

1000 kva dead front transformer-inside-view

Scotech waxay ku qalabaysaa transformer kasta oo leh Bay gudaha -O-Fiyuusyada saafiga ah oo taxane ah oo wata fiyuusyada hadda xadidaya-, si sax ah loogu cabiray ilaalinta ugu fiican. Waxaan bixinaa suxulka MOV{4}}nooca xirayaasha qalliinka ee buuxiya IEEE 386, anagoo hubinayna waxqabad badbaado leh oo hoos yimaada xaaladaha qalliinka.

 

 

03 Tijaabinta

Imtixaanka Joogtada ah iyo Heerka Imtixaanka

1. Cabbiraadaha iska caabinta sida waafaqsan IEEE C57.12.90-2021 faqrada 5

2. Wajiga{1}}Tijaabada xidhiidhka sida uu dhigayo IEEE C57.12.90-2021 Farqada 6

3. Tijaabooyinka saamiga sida uu qabo IEEE C57.12.90-2021 Farqada 7

4. Wax khasaare ah oo rar ah iyo wax rar ah ma jiro sida ku cad IEEE C57.12.90-2021 faqrada 8

6

6. Tijaabada adkaysiga korantada ee la kiciyay si waafaqsan IEEE C57.12.90-2021 faqradda 10.5.1

7. Tijaabada Voltage ee la dabaqay sida uu qabo IEEE C57.12.90-2021 faqradda 10.6

8. Tijaabada Diidida oo leh Cadaadis loogu talagalay Beddeleyaasha Dareeraha Immersed - Tijaabada daadinta ee 15 kPa waa in la qabtaa 12 saacadood iyada oo aan wax dareerin ah. Ma jiro qallooc joogto ah.

9. Cabbirka iska caabbinta dahaarka

10. Tijaabada Dielectric Oil

 

1000 kva dead front transformer-electrical-test
1000 kva dead front transformer-factory-test

 

Natiijooyinka Imtixaanka

Maya

Shayga Tijaabada

Unug

Qiimaha Ogolaanshaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbiraadaha iska caabinta

%

Qiyaasta dheelitir la'aanta iska caabbinta ugu badan

0.356

Gudub

2

Imtixaanada saamiga

%

Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5%

Astaanta isku xirka: Dyn1

-0.02%

Gudub

3

wajiga- imtixaanada xidhiidhka

/

Dyn1

Dyn1

Gudub

4

Maya- khasaarooyinka rarida iyo xamaasadda hadda

%

kW

I0 :: bixiyaan qiime la qiyaasay

P0: bixi qiimaha la qiyaasay

Dulqaadka wax qabad la'aan waa +0%

0.18%

0.985

Gudub

5

Load khasaaraha danab impedance iyo hufnaan

%

kW

kW

t:85 darajo

Z%: qiimaha la qiyaasay

Pk: qiimaha la qiyaasay

Pt: qiimaha la qiyaasay

dulqaadka impedance waa ± 7.5%

dulqaadka wadarta rarka luminta waa +0%

Waxtarka aan ka yarayn 99.43%

5.61%

7.740

8.725

99.46%

Gudub

6

Tijaabada Korantada ee La dabaqay

kV

HV: 40kV 60s

LV: 10kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada adkaysiga korantada ee keentay

kV

Danab la dabaqay (KV):

0.960

Muddada:40

Inta jeer (HZ): 180

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

8

Tijaabada daadinta

kPa

Cadaadiska la dabaqay: 15kPA

Muddada: 12h

Wax daadsan iyo maya

Waxyeello

Gudub

9

Cabbirka iska caabinta dahaarka

GΩ

HV -LV ilaa Dhulka:

LV-HV ilaa Dhulka:

HV&LV ilaa Dhulka:

2.51

2.60

3.88

/

10

Tijaabada Dielectric Oil

kV

Ka weyn ama la mid ah 40

52.0

Gudub

 

 

04 Baakaynta iyo dhoofinta

1000 kva dead front transformer-packaging-sealed tin foil bag 1000 kva dead front transformer-export-packing
 
 
 
 

05 Goobta iyo Kooban

Scotech's 1000 kVA beddelka hore ee dhintaywaxaa loogu talagalay dhexdhexaad la isku halayn karo oo hufan{0}}qaybinta korantada korantada ee tamarta, ganacsiga, iyo goobaha warshadaha. Naqshadeynta si ay ula kulanto IEEE Std C57.12.34-2022 iyo DOE 2016 heerarka tamarta, transformerkan ayaa leh dabaylaha naxaasta ah, qaboojinta KNAN, iyo FR3 saliid ester dabiici ah oo loogu talagalay badbaadada iyo daryeelka deegaanka ee la xoojiyey. Naqshadeeda hore ee dhimatay oo leh buushyo si buuxda u daboolan iyo xusullada rarka ayaa si weyn u yareynaya khatarta fallaadhaha inta lagu jiro hawlgalka iyo dayactirka.

Lagu dhisay si sax ah -Koofiyado is dulsaaran iyo bireed la hagaajiyay{1}nabar LV iyo warqad{2}} gariiradaha HV ee dahaaran, waxa ay hubisaa dahaarka waara iyo qaylada hoose ee culaab kala duwan. Taangiga birta ah ee adag wuxuu ka ilaaliyaa qaybaha muhiimka ah shoogga iyo gariirka inta lagu jiro gaadiidka iyo rakibidda. Lagu qalabeeyay Bay-O{{6}net and current-Fiyuusyada xaddidaya iyo IEEE 386-u hoggaansanaanta MOV xirayaasha, beddelka hore ee dhintay wuxuu bixiyaa ilaalin adag iyo waxqabad la isku halayn karo.

Scotech, waxaan diirada saareynaa bixinta transformers hore oo dhab ah, badbaado leh, oo waara oo ku haboon bey'ad kala duwan{0}}gudaha guddaha ama dibada{1}}Anagoo ku xoojinayna hawlahaaga kalsooni iyo xasilooni maskaxeed.

1000 kva dead front transformer-right-45-degree-view

 

Hot Tags: Transformer hore oo dhintay, soo saaraha, alaab-qeybiyaha, qiimaha, qiimaha