100 kVA Pad Mount Transformer-24/0.24 kV|Jamaica 2024
Awoodda: 100kVA
Voltage: 24/0.24kV
Feature: oo leh xire qalliin

Naqshad is haysta, deegaan {{0}saaxiibtinimo, siinta xalal la isku halayn karo oo loogu talagalay nidaamyada awood qaybinta casriga ah.
01 Guud
1.1 Asalkii Mashruuca
100 kVAhal weji suuf ku rakiban transformerwaxaa la geeyey Jamaica 2024. Awoodda la qiimeeyay ee transformerku waa 100 kVA oo leh qaboojinta ONAN. Korantada aasaasiga ah waa 24GrdY / 13.8kV oo leh ± 2 * 2.5% garaacista (NLTC), korantada labaad waa 0.24 / 0.12kV, waxay sameeyeen koox vector ah Ii0, waana quudin loop ah iyo 100 kva hore oo dhintay.suuf Buur transformer. 100 kva pad mount transformer si fiican ayaa loo qaabeeyey nidaamka dahaarka ayaa la hagaajiyay si uu si wax ku ool ah uga hortago shoogga hillaaca. Qaybinta qulqulka magnetic waa lebis, khasaaraha dheeraadka ah waa hooseeyaa, kulaylka deegaanka ayaa laga fogaadaa. Xooga elektromagnetic-ga waxa lagu xakameeyaa tiro yar, gariirka iyo sawaxankana si weyn ayaa loo dhimay. Qaybinta heerkulka isku midka ah waxay hubisaa saameynta qaboojinta wanaagsan; Sifooyinka magnetization-ku waxay muujinayaan toosan heer sare ah iyo isku-xirnaan sare oo toosan, taas oo hubinaysa hawlgalka hufan oo xasilloon ee qalabka. suufka ku rakiban Transformer wuxuu ku haboon yahay culeyska guud ee culus warshadaha iyo shirkadaha macdanta, dekedaha iyo meelaha la dego iyo meelaha kale, waxay ka dhigi kartaa koronto koronto oo sareysa oo la gaarsiiyo xarunta xamuulka, waxay yareyn kartaa heerka hoose-radius koronto koronto, yareyn kartaa khasaaraha. Muddada dhismaha goobta waa gaaban yahay, maalgelin yar.
1.2 Tilmaamaha Farsamada
100 kva suuf ah oo ku dheji nooca beddelka nooca iyo xaashida xogta
|
loo geeyey
Jamaica
|
|
Sannadka
2024
|
|
Nooca
suuf ku rakiban transformer
|
|
Heerka
IEEE
|
|
Quudinta
Loop
|
|
Hore
dhintay
|
|
Awood lagu qiimeeyay
100kVA
|
|
Soo noqnoqoshada
50HZ
|
|
Marxaladda
1
|
|
Nooca qaboojinta
ONAN
|
|
Polarity
Kala goyn
|
|
Korantada aasaasiga ah
24GrdY/13.8kV
|
|
Voltage Secondary
0.24/0.12 kV
|
|
Qalabka dabaysha
Copper
|
|
barokaca xagal
Ii0
|
|
Caqabada
4%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Dulqaad
±7.5%
|
|
Wax Xamuul ah ma jiro
0.205KW ( 10%)
|
|
Load Lumista
0.801KW ( 6%)
|
|
Agabka
Habaynta caadiga ah
|
1.3 Sawirro
100 kVA suuf buurta beddelka jaantus sawir iyo cabbir.
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Xudunta birta nabarka waxay ka samaysan tahay xaashi bir silikoon leh oo awood sare leh iyadoo loo marayo habka dabaysha. Inta lagu jiro habka dabaysha, lakabka dahaadhka ah ayaa badanaa lagu daraa si loo yareeyo vortexka iyo khasaaraha asaasiga ah. Dahaarka u dhexeeya lakabyada waxaa lagu xoojiyay habka wax soo saarka si loo hagaajiyo waxqabadka xudunta. Qaab dhismeedka xudunta birta nabarka ayaa si wax ku ool ah u uruurin karta una gudbisa qulqulka magnetic, si ay ugu adkeysato cufnaanta qulqulka magnetic sare ee mugga isku midka ah, iyo hagaajinta cufnaanta awoodda iyo waxqabadka qalabka. Iyada oo leh- xaashiyaha birta silikoon ee tayada sare leh iyo habka dabaysha saxda ah, khasaaraha asaasiga ah iyo khasaaraha dheeraadka ah si weyn ayaa loo dhimi karaa, si loo wanaajiyo waxtarka guud ee qalabka. Sababtoo ah habka dabayshu wuxuu yareeyaa farqiga hawada iyo xidhiidhka liita ee xudunta, xudunta birta boogta waxay caadi ahaan leedahay gariir hoose iyo heerarka qaylada, iyo habka dabayshu wuxuu ka dhigayaa xuddunta mid la mid ah, taas oo yaraynaysa dhibaatada gariirka farsamada. Raaxada hawlgalka qalabka waa la hagaajiyay. Qaab dhismeedka dabaysha ee xudunta birta boogta waxay yaraynaysaa khasaaraha hadda jira sababtoo ah dariiqa gaaban ee xudunta inta lagu jiro habka dabaysha. Qaab dhismeedka dabaysha ayaa sida caadiga ah ka dhigaya naqshadda udub-dhexaadka ah ee beddelka mid cufan oo ku habboon codsiyada u baahan cufnaanta awoodda sare. Marka la barbar dhigo koofiyadaha la dahaadhay, feeraha birta nabarrada waxay caadi ahaan leeyihiin mug iyo miisaan ka yar, taas oo gacan ka geysanaysa yaraynta miisaanka guud ee beddelka.

2.2 Dabaylaha

Sare -Dabaysha siliga korantada: Sarre{1}}Dabaysha korantada inta badan waxa ay isticmaashaa silig naxaas ah oo leh dahaadhid aad u wanaagsan,waxana lagu dahaadhay rinjiga dahaadhka ah ama lakabka dahaadhka ah ee duuban si looga hortago wareegga gaaban ee korontada oo loo hubiyo badbaadada. Waxyaabaha ay ka midka yihiin heerka dahaarka, iska caabinta korantada iyo maaraynta kulaylka waa in lagu tixgaliyaa naqshad ahaan. Tirada wareegyada, dhexroorka iyo dabaylaha dabayshu waxay saamaynaysaa waxqabadka iyo waxtarka beddelka.
Hoose - dabaylaha bireed ee korantada: dabaylaha foilku waxa uu ku salaysan yahay naxaas ama cajalad bireed aluminium dhumucdiisuna kala duwan tahay kaari ahaan, oo leh walxo dahaadh ballaadhan sida dahaarka interlayer, walxaha cidhiidhi cidhiidhi ah sida dahaarka dhamaadka, in mishiinka bireed wareeg ah si ay u dhamaystirto dabaylaha, samaynta gariiradda, iyo dhamaystirto alxanka ee gudaha iyo dibadda ee dharka. Sababtoo ah hadda gariiradda hoose - sida badan gariiradda danabku waa weyn tahay, haddii siliggu is barbar yaalo, haddii habka dabaysha lakabka la isticmaalo marka dabayshu soo saari doonto xagal weyn oo wareeg ah, marka transformer gaab - wareegtu waxay soo saari doontaa xoog weyn oo makaanik jihada toosan ee gariiradda, taasoo keenta dhaawac gariiradda. Dhamaadka xaashida naxaasta ah waa fidsan, sidaa awgeed xoogga axial ee wareegga gaaban waa qayb ka mid ah qaab dhismeedka boogta siliga, waxayna leedahay caabbinta wareegga gaaban-
2.3 Haanta
Qaab dhismeedka asalka ah ee shaabadeynta dhaqameed, gaar ahaan meesha daadinta saliidda ay fududahay in la sameeyo, ka bilow koontaroolka wax iibsiga si loo hubiyo in birta aysan miridhku, garaacin, xoqin, dubbe, farsamaynta gaarka ah ee qaybta xidhitaanka taangiga saliidda, iyo rinjiyeynta guud ee sanduuqa, ka saar burrs gees fiiqan iyo alxanka alxanka ee ka soo baxa habka sanduuqa, oo xoojiya dhejinta rinjiga. Weld saxanadda birta ee la gooyey, oo hubi isku-duubnaanta iyo xoogga alxanka inta lagu jiro habka alxanka. Guud ahaan, alxanka gaashaanka gaaska (MIG ama MAG) ama alxanka arc gacanta ayaa la isticmaalaa.

2.4 Kulanka ugu dambeeya


03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug
|
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
/ |
/ |
/ |
Gudub |
|
2 |
Imtixaanada saamiga |
/ |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: Ii0 |
A: -0.05 B: -0.05 |
Gudub |
|
3 |
Tijaabada polarity |
/ |
Kala goyn |
Kala goyn |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% kW |
I0 : bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay Dulqaadka wax qabad la'aan waa +10% |
0.23 0.187 |
Gudub |
|
5 |
Khasaaraha rarka iyo danab-celinta |
/ kW kW |
t: 85 darajo Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay dulqaadka impedance waa ± 10% dulqaadka wadarta rarka luminta waa +6% |
3.71 0.732 0.919 99.30 |
Gudub |
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (kV): 2 Ur Muddada: 40 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
LV-HV ilaa Ground |
34.4 |
/ |
|
9 |
Tijaabada daadinta |
/ |
Cadaadiska la dabaqay: 20kPA Muddada: 12h |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
10 |
Tijaabada Dielectric Oil |
kV |
Ka weyn ama la mid ah 45 |
56.81 |
Gudub |


04 Baakaynta iyo dhoofinta


05 Goobta iyo Kooban
Halbeegga{0}wajiga{1}ku rakiban transformer-ka, oo leh nashqaddiisa is haysta, wax qabadkiisa gaarka ah, iyo laqabsiga sare, ayaa ah doorashada ugu fiican ee nidaamyada qaybinta awooda casriga ah. Hadday tahay bulshooyinka la deggan yahay, tas-hiilaadka korantada, ama mashaariicda ganacsiga, waxay keentaa koronto deggan oo la isku halayn karo si loo daboolo baahiyaha kala duwan. Iyada oo leh adeeggeeda dheer iyo kharashkeeda dayactirka hooseeya, waxay ku siinaysaa hufnaan iyo kharash badan{4}} xal awood wax ku ool ah, iyada oo hubinaysa xasilloonida maskaxda iyo ku habboonaantaadabaahida korontada!