50 kVA Hal Waji oo Waji ah oo Ku rakiban Badaha-24/0.24 kV|Jamaica 2024
Awoodda: 50kVA
Voltage: 24GrdY/13.8-0.24/0.12 kV
Muuqaal: Qabta qalliin

Bixinta awood xasiloon bulshooyinka leh wajiyo kasta oo ku rakiban transformer
01 Guud
1.1 Sharaxaada Mashruuca
2024,scotechla keenay 10 unug oo 50kVA ahhal - suufka wejiga - ku rakiban transformersmacaamiisha Jamaica. Transformer kasta waxaa loo qaabeeyey loona dhisay si uu ula kulmo heerarka IEEE. Waxay bixiyaan waxqabad lagu kalsoonaan karo iyo nolol adeeg oo dheer.
Waxay u adeegaan sidii dhexdhexaad -Transformers qaybinta korantada gudaha nidaamka qaybinta awooda dhulka hoostiisa. Ku qalabaysan korantada dabaysha aasaasiga ah ee 24GrdY/13.8 kV iyo koronto dabaysha sare ee 0.24/0.12 kV, taasoo bixisa 50 kVA oo ah awood wax soo saar.
Dhintay{0}Transformers-ka hore waxa ay wataan isku xirka korantada oo si buuxda u xidhan iyo qaybo ka mid ah, oo aan lahayn qaybo toos ah ama terminal marka albaabka hore la furo. Naqshadaynta quudinta- waxay wanaajisaa badbaadada, isku halaynta, iyo dabacsanaanta shabakadaha qaybinta.
50 kVA hal weji suuf ah oo ku rakiban transformer-ka waxaa lagu dhisay dabeylo naxaas ah oo loogu talagalay waxqabadka koronto ee xooggan. Transformer-ku waxa uu ku qalabaysan yahay nidaam qaboojin wax ku ool ah oo ONAN ah, oo ay kaabayaan -saliid macdan oo tayo sare leh iyo heerka PCB oo hooseeya, sidaas darteed hubinta hawlgal badbaado leh oo deegaan ahaan u wanaagsan. Intaa waxaa dheer, qiimaha luminta - wuxuu ku hadhayaa 0.35 kW, iyo maya -qiimaha lumitaanka kama badna 0.13 kW.
Ku saabsan nidaamka ilaalinta, transformers-yadani waxay leeyihiin fiyuuska bayooleed, fiyuuska xaddidaya hadda (CLF), iyo aaladda cadaadiska cadaadiska. Qaybahani waxay ka ilaalinayaan qulqulka xad-dhaafka ah waxayna hoos u dhigaan halista dhaawaca ka imanaya wareegyada gaaban ama cilladaha kale.
1.2 Tilmaamaha Farsamada
50 kVA hal weji suuf ah oo ku rakiban tafatirka beddelka iyo xaashida xogta
|
loo geeyey
Jamaica
|
|
Sannadka
2024
|
|
Nooca
Hal weji suuf ku dheji transformer
|
|
Heerka
IEEE Std
|
|
Awood lagu qiimeeyay
50kVA
|
|
Soo noqnoqoshada
50HZ
|
|
Quudinta
Loop
|
|
Hore
dhintay
|
|
Nooca qaboojinta
ONAN
|
|
Insulant dareere ah
Saliidda Macdanta
|
|
Korantada aasaasiga ah
24GrdY/13.8
|
|
Voltage Secondary
0.24/0.12 KV
|
|
Kooxda Vector
Ii0
|
|
Polarity
Kala goyn
|
|
Qalabka dabaysha
Copper
|
|
Caqabada
4%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
0.13 KW
|
|
Load Lumista
0.35 KW
|
|
Agabka
IFD, Qalliin Qabta
|
1.3 Sawirro
50 kVA hal weji suuf ah oo ku rakiban sawir beddele iyo warqad magaceed
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Xudunta waa in la isku dhejiyaa oo la isku dhejiyaa si ay uga hortagaan qallooca ay sababaan culeyska wareegga gaaban ama maaraynta gaadiidka iyo si looga hortago beddelka saqafka asaasiga ah.
Koofiyadaha waa in laga dhisaa gade sare -, ku jihaysan hadhuudhka, daahyada birta silikoon duuban qabow, oo leh awood birlabeed sare leh. Dhismaha muhiimka ah waa in lagu daraa qodobbo yareynaya khasaaraha asaasiga ah, xamaasadda hadda iyo heerarka qaylada.

2.2 Dabaylaha
Xirmadayada 50kVA ee hal weji ee ku rakiban dabaylaha beddelka ayaa adeegsada{1} nadiif ah oo namaray silig wareeg ah oo naxaas ah, oo muujinaya firfircooni koronto oo heersare ah iyo dahaar is haysta. Ku dheggan dhaldhalaalka xooggan waxay wanaajisaa adkeysiga waxayna xirataa caabbinta.
Silig noocaan ah ayaa si weyn loogu isticmaalaa yar iyo dhexe{0}xajmi is beddeleyaal iyo qalab elektaroonig ah sababtuna waa dabacsanaantiisa, fudaydka dabaysha, iyo qiimaha - hufnaantiisa.

2.3 Haanta

Dhammaan xayndaabyadu waxay ka samaysan yihiin bir khafiif ah waxayna leeyihiin budo{0}}dhamays dahaaran si ay u bixiso dusha adkeysi badan, tamper{1} Saxaarad go'an, oo loogu talagalay in lagu hayo 100ml oo dareere ah oo dahaadh ah oo looga hortago in dareeruhu ka da'ayo gidaarka taangiga ama qalabyada, waa in lagu rakibaa meel ka hoosaysa goobta fiyuus kasta oo la bixi karo. Scotechsuufka -ku rakiban transformersu adkeyso wax-ka-qabashada iyo cimilada adag labadaba, taasoo ka dhigaysa inay badbaado u tahay in lagu rakibo goobaha caamka ah.
2.4 Kulanka ugu dambeeya
Transformer-kan waa in lagu ilaaliyaa laba -nidaamka ilaalinta fiyuuska oo ka kooban saliid bayooleed -Fuyuus la rusheeyey, fiyuuska eryida oo taxane ah oo saliid -la miiray, qayb ah{{3}kala duwan, hadda- fiyuuska xaddidaya. Xidhiidhiyayaasha fiyuuska Bayoneetku waa inay dareemaan qulqulka sare iyo heerkulka saliidda oo sarreeya si ay u bixiyaan ilaalinta kulaylka beddelka.
Isku-dubbarid ilaalinta beddelka fiyuuska eryida ee nadiifinta hooseeya-ciladaha hadda jira iyo hadda{1} xadaynta fiyuuska nadiifinta sare{2}}ciladaha hadda jira ee dhaafsiisan qiimaynta kala goysa ee fiyuuska eryida. Si loo baabi'iyo ama loo yareeyo qulqulka saliida, isku dhafka bayonet-ka waa in uu ku jiraa galka saliida haynta gudaha guriga kaas oo xidha marka fiyuuska la saaro, iyo gaashaan dibadeed dibadeed. Habaynta guud ee jabinta rarka iyo qalabka ilaalinta waa in ay u ogolaato quudinta loop-ka taransfooriyaha oo ay ka hortagto xidhitaanka u beddelka khaladaadka gudaha.

03 Tijaabinta
Imtixaanka joogtada ah
1. Cabbiraadaha iska caabinta
2. Imtixaanada saamiga
3. Tijaabada Polarity
4. Wax Khasaare ah oo Xamuul ah oo Hadda socda ma jiro
5. Load Khasaaraha iyo Korantada Waxyeelada
6. Tijaabada Voltage ee la dabaqay
7. Tijaabada adkaysiga korantada ee keentay
8. Cabbirka iska caabbinta dahaarka
9. Tijaabada Diidida oo leh Cadaadis loogu talagalay Beddeleyaasha Dareeraha Immersed
10. Tijaabada Dielectric Oil


Natiijooyinka Imtixaanka
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
/ |
/ |
/ |
Gudub |
|
2 |
Imtixaanada saamiga |
/ |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: Ii0 |
A: -0.05 B: -0.05 |
Gudub |
|
3 |
Tijaabada polarity |
/ |
Kala goyn |
Kala goyn |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% kW |
I0 :: bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay Dulqaadka wax qabad la'aan waa +10% |
0.24 0.099 |
Gudub |
|
5 |
Khasaaraha rarka iyo danab-celinta |
/ kW kW |
t:85 darajo Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay dulqaadka impedance waa ± 7.5% dulqaadka wadarta rarka luminta waa +6% |
3.71 0.330 0.429 99.31 |
Gudub |
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV): 2 Uur Muddada:40 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
LV-HV ilaa Ground |
33.9 |
/ |
|
9 |
Tijaabada daadinta |
/ |
Cadaadiska la dabaqay: 20kPA Muddada: 12h |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
10 |
Tijaabada Dielectric Oil |
kV |
Ka weyn ama la mid ah 45 |
60.4 |
Gudub |
04 Baakaynta iyo dhoofinta
4.1 Baakad
1. Baakadaha alwaaxyada: Transformers waxaa sida caadiga ah lagu xiraa sanduuqyo alwaax ah oo adag, kuwaas oo si wax ku ool ah uga ilaaliya cadaadiska dibadda inta lagu jiro gaadiidka. Gudaha sanduuqyada waxaa badanaa lagu dhejiyaa xumbo ama isbuunyo si loo nuugo saameynta.
2. Agabka biyuhu: Baakadaha biyuhu waxay si gaar ah muhiim u yihiin inta lagu jiro gaadiidka badda. Transformers inta badan waxaa lagu daboolaa filim aan biyuhu lahayn ama qoyaan - walxaha aan biyaha lahayn si looga hortago qoyaanka iyo xagashada inta lagu jiro safarka.
3. Qalabka Xoojinta: Transformers badan oo jilicsan ayaa lagu xoojiyay birta ama birta si looga hortago burburka isku dhaca iyo burburka inta lagu jiro gaadiidka.
4. Calaamadeynta iyo Calaamadeynta: Baakadaha waxaa lagu calaamadeyn doonaa calaamado dhoofin oo caan ah, sida "Jilicsan," "culus," ama "Toosnaanta," si loo xasuusiyo gaadiidleyda inay si taxadar leh ula qabsadaan.

4.2 dhoofinta

1. Soo dejinta iyo dejinta: Qalabka kor u qaadista waxaa loo isticmaalaa habka rarista iyo dejinta si loo hubiyo in aysan jirin culeys dheeri ah oo farsamo inta lagu jiro gaadiidka transformerka.
2. Go'an: Inta lagu jiro gaadiidka, Transformer-ku wuxuu u baahan yahay in si sax ah loo hagaajiyo si looga hortago leexinta ama isku dhaca, taasoo keenta burbur farsamo.
3. Ilaalinta: Waxa loo baahan yahay in la qaado tallaabooyin lagu ilaalinayo qaybta dahaaran ee Transformer-ka iyo qaab-dhismeedka dibadda si looga hortago wasakh ama dhaawac.
05 Goobta iyo Kooban
Qalabkan 50kVA ee hal waji ah ee ku rakiban transformer-ka waxa lagu sameeyay dabaylo naxaas ah iyo haan bir ah oo xooggan. Xuddunta waxay isticmaashaa bir silikoon oo heerkeedu sareeyo -, kaas oo hoos u dhigaya khasaaraha iyo qaylada. Nidaamka qaboojinta ee ONAN iyo saliidda macdanta ayaa ka caawiya unugga inuu si badbaado leh u shaqeeyo oo uu dheereeyo.
Waxay leedahay bakhti -hore, loop{1}}naqshad quudin. Cutubku waxa uu leeyahay fiyuusyo, aalad cadaadis cadaadis, waxaana ku jiri kara qaybo dheeraad ah sida kuwa qalliinka lagu xidho iyo cillad-sheegayaasha. Kuwani waxay si fiican uga ilaalinayaan khaladaadka waxayna ka dhigaan cutubka mid la isku halleyn karo.
Transformerkani waa badbaado, xoog badan, oo hufan. Waxay siisaa awood joogto ah guryaha iyo ganacsiyada gudaha Jamaica. Waa doorasho wanaagsan isticmaalka tamarta muddada dheer-

Hot Tags: hal weji suuf ku rakiban transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
50 kVA suuf Ku rakiban Beddelka-24.94/0.24*0.12 kV|S...
100 kVA Pad Mount Transformer-24/0.24 kV|Jamaica 2024
167 kVA Pad Mount Transformer-24*12/0.24 kV|Jamaica ...
75 kVA Qalabka Korontada-13.8/0.24 kV|Guyana 2025
50 kVA Waji Keliya ah oo Ku Rakiban Badal Qaybinta Q...
25 kVA suuf Ku rakiban Beddelka-24*12/0.24 kV|Jamaic...
U dir sooji