167 KVA Hal Waji oo Tiir Ku Rakiban Tamashlaha-2.4/0.347 KV|Kanada 2025
Awoodda: 167 kVA
Voltage: 2.4/0.347 kV
Sifada: leh IFD iyo daba-galka- lidka ku ah

Loo dhisay Walxaha, Lagu Kalsoonyahay Waxqabadka: Tiirka Keliya ee Tiirka Ku rakiban.
01 Guud
1.1 Sharaxaada Mashruuca
167 kVA hal waji oo tiir ku rakiban transformer ayaa la geeyey Kanada sanadka 2025. Awoodda lagu qiimeeyay taransfooriyaha waa 167 kVA oo leh ONAN qaboojin. Korontada sare waa 2.4 kV, danab hooseeya waa 0.347 kV, waxay sameeyeen koox vector ah II6.
Midka casriga ah ee - tiirka wejiga -Transformer-ka rakiban, ee isku daraya Baadhista Cilada Gudaha (IFD) iyo Ka-hortagga dahaarka, waxa loogu habeeyey isku halaynta sare ee codsiyada muhiimka ah sida qaybinta awooda deegaanka, korantada miyiga, iyo khadadka quudiyaha warshadaha. IFD waxay si firfircoon ula socotaa khaladaadka gudaha si ay awood ugu siiso dayactirka saadaalinta iyo ka hortagga guul-darrooyinka, halka Ka-hortagga{4}}Nidaamka dabagalku uu si adag uga hortagayo raadraaca dusha sare ee ay keento ceeryaamaha milixda xeebta, wasakhowga warshadaha, ama jawiga qoyan. Is-waafajintan ogaanshaha iyo cimri dhererka waxay hubisaa badbaadada la xoojiyay waxayna yaraynaysaa carqaladaynta adeegga macaamiisha tamarta.
1.2 Tilmaamaha Farsamada
167 kVA tiirka ku rakiban qalabka beddelka nooca iyo xaashida xogta
|
loo geeyey
Kanada
|
|
Sannadka
2025
|
|
Nooca
Transformer ku rakiban tiirarka
|
|
Heerka
CSA C2.2-06
|
|
Awood lagu qiimeeyay
167 kVA
|
|
Soo noqnoqoshada
60HZ
|
|
Marxaladda
1
|
|
Polarity
Wax lagu daro
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
2.4 kV
|
|
Voltage Secondary
0.347 kV
|
|
Qalabka dabaysha
aluminium
|
|
Kooxda Vector
II6
|
|
Caqabada
2.3%(±10%)
|
|
Taabo Beddelka
N/A
|
|
Wax Xamuul ah ma jiro
0.096 kW
|
|
Load Lumista
1.85 kW
|
1.3 Sawirro
167 kVA tiirka ku rakiban jaantuska beddelka sawirka iyo cabbirka.
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core

Xuddunta waxa lagu dhisay iyadoo la isticmaalayo nashqad boog joogto ah oo ka timid bir silikoon heerkeedu sareeyo-. Qaab dhismeedkan hal-abuurka leh waxa uu abuuraa waddo birlabeed ah oo aan fiicneyn oo leh nusqaamo yar, taasoo u horseedaysa hufnaan tamar sare iyo aamusnaan, hawlgal la isku halayn karo.
2.2 Dabaylaha
Waxay shaqaaleysiisaa foil aluminium -naqshad naqshadeeynta hoose -dhinaca korantada si ay u bixiso tabar gaaban oo gaaban{2}}xoog wareeg ah iyo silig aluminium lakabaysan -Nashqada dhaawaca sare -dhinaca korantada ee qaybinta ugu fiican. Habka dabaysha isku-dhafan, iyadoo la isticmaalayo aluminium, waxay gaadhaysaa isku dheelitirnaanta ugu wanaagsan ee isku halaynta, qiimaha - hufnaanta, iyo waxqabadka kulaylka.

2.3 Haanta

Haanta waxaa laga dhisay bir sare -, taasoo bixisa iska caabin daxalka ah oo meesha ka saaraysa baahida rinjiyeynta. Naqshadeeda hermetically shaabadaysan, oo ay weheliso baalasha jiingado, waxay hubisaa ilaalinta adag ee ka dhanka ah bay'ada adag iyo waxtarka, dayactirka - daadinta kulaylka bilaashka ah inta lagu jiro nolosha adeega dheer.
2.4 Kulanka ugu dambeeya
Isu imaatinka kama dambaysta ahi wuxuu matalaa is-dhexgalka saxda ah ee dhammaan qaybaha waaweyn. Xudunta -Ururka dabaysha waxa lagu shaabadeeyey daxalka{2}} haanta birta aan adkaysiga lahayn, kaas oo faaruq ah{3}}ka buuxa dareere dielectric si loo dammaanad qaado awood sare oo koronto iyo qaboojin. Ku-xidhka sare-Bushings voltage, accessories, and hard test exam final, taasoo keentay in la joogteeyo oo la dayactiro{6}Transformer hufan oo loo habeeyay qaybinta sare.

03 Tijaabinta
Midka -Tiirka Wajiga -Transformer-ka ku rakiban (qaabka: 167kVA-2.4/0.347kV) ee SCOTECH waxa uu u hogaansamay CSA C2.2-06(R2022) iyo CSA C802.1-02(R2) standards Tijaabooyinka caadiga ah waxaa ka mid ah cabbiraadda iska caabbinta dabaysha (HV: 0.09067Ω, LV: 1.919mΩ at 32℃iyo 60% qoyaan qaraabo ah), tijaabada saamiga ( weecasho: 0.04% In ka yar ama la mid ah 0.5%, kooxda vector: Ii6), tijaabada polarity (Ku dar, buuxinta shuruudaha) 9% gudahood:{1} dulqaadka, hadda: 0.36%), imtixaanka load (lumin at 85 darajo: 1165W, khasaaraha guud: 1261W, impedance gaaban gaaban: 2.17% gudahood ± 10% dulqaadasho, hufnaan: 99.57% Greater ka badan ama la mid ah 98.63% V: 0.63 korontadu hoos u dhacay, korontadu waa 0.0%, 0,000 V, 0.0% koronto imtixaanka u adkeysiga danab (0.694kV, 150Hz ee 48s, koronto la'aan burburtay), cabbirka caabbinta dahaarka (LV-HV dhulka: 29.1GΩ), 20kPa tijaabada daadinta cadaadiska (24h, ma daadsanaan ama dhaawac), iyo baaritaanka saliid (xoog-dielectric: 58.4kV, content qoyaan: 9.5mg).
|
Maya |
Shayga Tijaabada |
Unug |
Ogolaanshaha Qiimaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
/ |
/ |
/ |
Gudub |
|
2 |
Imtixaanada saamiga |
/ |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: II6 |
0.04 |
Gudub |
|
3 |
Tijaabada polarity |
/ |
Wax lagu daro |
Wax lagu daro |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% |
I0 :: bixiyaan qiime la qiyaasay |
0.36 |
Gudub |
|
kW |
P0: bixi qiimaha la qiyaasay |
0.095 |
|||
|
/ |
Dulqaadka wax qabad la'aan waa +15% |
/ |
|||
|
5 |
Load khasaaraha , danab impedance, khasaaraha guud iyo hufnaan |
/ |
t:85 darajo dulqaadka impedance waa ± 10% dulqaadka wadarta rarka luminta waa +8% |
/ |
Gudub |
|
% |
Z%: qiimaha la qiyaasay |
2.17 |
|||
|
kW |
Pk: qiimaha la qiyaasay |
1.165 |
|||
|
kW |
Pt: qiimaha la qiyaasay |
1.261 |
|||
|
% |
Waxtarka aan ka yarayn 98.63% |
99.57 |
|||
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV):0.694 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
Muddada:48 |
|||||
|
Inta jeer (HZ): 150 |
|||||
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
LV-HV ilaa Ground |
29.1 |
Gudub |
|
9 |
Tijaabada daadinta |
/ |
Cadaadiska la dabaqay: 20kPA |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
Muddada: 12h |
|||||
|
10 |
Tijaabada Saliida |
kV |
Xoogga Dielectric |
58.4 |
Gudub |
|
mg/kg |
Nuxurka qoyaanka |
9.5 |
|||
|
% |
Qodobka Burburinta |
0.00194 |
|||
|
mg/kg |
Falanqaynta Furan |
0.03 |
|||
|
/ |
Falanqaynta Chromatography ee Gaaska |
/ |


04 Baakaynta iyo dhoofinta
4.1 Xirxirida

Baakadaha, tiirka kaliya ee - wejiga - ku rakiban transformer-ka waxa si amaan ah loogu hayaa sanduuq alwaax ah oo waara. Ka hor inta aan la gelin sanduuqa, transformer-ka waxaa lagu daboolaa lakabka filim caag ah si looga ilaaliyo qoyaanka iyo wasakhowga. Sanduuqa alwaaxdu wuxuu ku qalabaysan yahay xoojinta cidhifka birta si ay u sii waarto, iyo tilmaamaha maaraynta muhiimka ah iyo calaamadaha digniinta ayaa si cad loogu daabacay dusha sare. Intaa waxaa dheer, waxaa lagu rakibay sariirta, fududaynta hawlgallada saadka iyo hubinta in beddelka uu ku sii jiro xaalad wanaagsan inta lagu jiro dhoofinta iyo kaydinta.
4.2 dhoofinta
Marka loo eego shuruudaha CIF Montreal, hal - tiirka wejiga - ee ku rakiban transformers waxaa lagu qaadaa xamuulka badda. Iibiyuhu wuxuu habeeyaa oo dabooshaa kharashka gaadiidka badda ee Dekedda Montreal, wuxuu soo iibiyaa caymiska xamuulka badda si uu uga ilaaliyo khataraha ku-meel-gaarka ah ee iman kara, wuxuuna xaqiijiyaa in transformers-yada si habboon loo maamulo oo lagu raro markabka si badbaado leh loogu geeyo dekedda uu ku socdo.

05 Goobta iyo Kooban
Laga soo bilaabo dhismaheeda birta ah ee adag ilaa xudunta dhaawaca aadka u hufan iyo dabaylaha, dhinac kasta oo ka mid ah - tiirka wejiga -ku rakiban transformer waxa loogu talagalay hal ujeedo: isku halaynta garoonka dhexdiisa. Waa doorashada caqliga leh, waara ee loogu talagalay yutiilitida kuwaas oo doonaya in ay wanaajiyaan adkeysiga xadhkaha, yareeyaan kharashaadka hawlgalka, oo ay siiyaan adeeg gaar ah macaamiishooda. Diyaar ma u tahay inaad awoodda mustaqbalka si kalsooni leh? Nala soo xidhiidh maanta si aad u ogaato sida transformer-kan loogu dari karo shabakadaada.

Hot Tags: hal weji tiir ku rakiban transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
37.5 kVA Transformers on Tiirka Telefoonka-34.5/0.12...
167 kVA Korontada Cirifka -13.8 / 0.347 kV|Kanada 2025
50 kVA Khadka Korontada Transformer-13.8/0.12*0.24 k...
75 kVA Tiirka Ku Rakiban Beddelka-7.97/0.12/0.24 kV|...
75 kVA Utility Transformer-24.94/0.12 kV|Kanada 2025
25 kVA Transformer tiir Ku rakiban-14.4/0.12 kV|Kana...
U dir sooji