50 kVA Khadka Korontada Transformer-13.8/0.12*0.24 kV|Guyana 2024
Awoodda: 50kVA
Voltage: 13.8 / 0.12 * 0.24 kVA

SCOTECH Hal Waji oo Tiir Ku rakiban Beddelayaasha: Awood la isku halayn karo laga bilaabo 10kVA ilaa 500kVA baahi kasta
01 Guud
1.1 Sharaxaada Mashruuca
Dalabka ka yimid macaamiisheena Guyana 2024, shirkadda adeegyada injineernimada korontada, waxaa ku jira transformers oo awood u leh 25kVA, 50kVA, 75kVA, 100kVA, iyo 167kVA. 50kVA Ideal ee dhexdhexaad ah{7}} meelaha la dego ama ganacsiyada yaryar.
Transformerku wuxuu si fiican u waafaqsan yahay IEEE & ANSI C57.12.00 heerarka. Wuxuu ku shaqeeyaa korantada aasaasiga ah ee 13,800V, isagoo hoos ugu soo dhacaya 120/240V dhanka labaad, oo leh inta jeer ee 60Hz iyo dabaylaha naxaasta ah. Cidhiidhigu waa 2%, taas oo yaraynaysa hoos u dhaca korantada ee culeyska.
Ku qalabaysan nidaamka qaboojinta ee ONAN iyo NLTC (No Load Tap Changer), waxay bixisaa 10% kala duwan oo taabasho ah (± 2.5% tuubadaba), xasilinta korantada sare xitaa iyadoo leh isbeddellada aasaasiga ah. Khasaaruhu - maya waa 160W, iyo - lumitaanka rarka waa 512W, wanajinta isticmaalka tamarta. Transformer-ku waxa uu ka kooban yahay polarity kala-goyn iyo koox fayow oo Ii0 ah, oo qeexaysa xidhiidhka wejiga.
Sida soo saaraha hormuudka ah ee transformers, waxaan bixinaa kaamil ahxalalka transformerbaahida qaybinta korontada.
1.2 Tilmaamaha Farsamada
50kVA tiir hal waji ah oo ku rakiban qeexida beddelka iyo xaashida xogta
|
loo geeyey
Guyana
|
|
Sannadka
2024
|
|
Nooca
Tiir hal waji ah oo ku rakiban transformer
|
|
Heerka
IEEE & ANSI C57.12.00
|
|
Awood lagu qiimeeyay
50 kVA
|
|
Soo noqnoqda
60HZ
|
|
Polarity
Kala goyn
|
|
Kooxda Vector
Ii0
|
|
Korantada aasaasiga ah
13800 V
|
|
Voltage Secondary
120/240 V
|
|
Qalabka dabaysha
NAxaas
|
|
Caqabada
2%
|
|
Habka qaboojinta
ONAN
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
± 2X2.5% (Guud ahaan tirada =10%)
|
|
Wax Xamuul ah ma jiro
160 W
|
|
Load Lumista
512 W
|
|
Agabka
Habaynta caadiga ah
|
1.3 Sawirro
50kVA Hal weji tiir ku rakiban cabbirka beddelka iyo faahfaahinta miisaanka
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Faa'iidada qaabdhismeedka ee xudunta dhaawaca ayaa ah in ay u ogolaato walxaha ferromagnetic in ay si buuxda u isticmaalaan sifooyinkeeda sare ee korantada, yaraynta isku-dhafka khasaaraha asaasiga ah. Lugta xudunta ah iyo iskutallaabta harqoodka -Qaybta halbawlaha -wajiga dhaawaca xudunta ah labaduba waa leydi waxayna si joogto ah u dhaawacmaan xariijimaha birta birta birta ah, si weyn u yaraynaysa wax - lumitaanka rarka, maya-load hadda, iyo buuqa beddelka.

2.2 Dabaylaha

Dabaylaha transformer-kayadu waxa ay adeegsadaan{0}nadiif sare oo naxaas ah oo lagu naas-nuujiyay silig naxaas ah, oo leh firfircooni koronto oo heersare ah iyo dahaar adag. Dahaarka dhaldhalaalka wuxuu bixiyaa dahaarka isku midka ah iyo xoogga dielectric la isku halayn karo. Samee qaab dhismeedka gariiradda la hagaajiyay ee dabaylaha bireedku hooseeya - gariiradaha korantada iyo dabaysha siliga sare - gariiradaha korantada, hubinta xasilloonida hawleed ee wanaagsan, isku halaynta, iyo waxqabadka kulaylka.
2.3 Haanta
Taangiga birta khafiifka ah ee leh lugaha wax qaadda ee alxanka leh iyo xadhkaha dhejiska ee tooska ah{0}}ilaa{1} Qiimaynta KVA ee darbiga haanta. Dahaarka ilaalinta ayaa lagu dabaqaa taangiyada si loo yareeyo daxalka. Si loo hubiyo in ay si badbaado leh u shaqeeyaan transformers-ka korantada in kasta oo ay la kulmaan xaaladaha cimilada adag iyo meelaha fog fog, isku halaynta ayaa lagu dhisay tilmaamahooda.

2.4 Kulanka ugu dambeeya

1. Golaha dabaysha:U jiid dabaylaha HV/LV oo dul saar xudunta dahaarka leh, adoo hubinaya toosinta saxda ah iyo hufnaanta dahaarka.
2. Isku xirka Korontada:Isku-xidhka dabaysha waxay u horseedaa beddelka tuubada, baadiyaha, iyo qaybaha kale, ka dibna ilaali oo dahaadh kala-goysyada.
3. Xudunta - Qalajinta gariiradda:Geli qaybta firfircoon ee la soo ururiyey (core + windings) foornada qallajisa si loogu kululeeyo faakuumka si looga saaro qoyaanka.
4. Rakibaadda Haamaha:Ku rid qaybta firfircoon ee engegan taangiga, u dhig si ammaan ah, oo hubi in dahaarka saxda ah ee gidaarada haanta.
5. Kordhinta Agabka:Ku rakib bushings, valve gargaarka cadaadiska iyo qalabyada kale, ka dibna iska hubi inay jiraan.
6. Buuxinta & Dejinta Saliidda:Vacuum-ku buuxi saliid dahaarka, degsooyinka, oo oggolow degitaanka ka hor intaadan hubin heerarka saliidda iyo xoogga tamarta.
03 Tijaabinta
Imtixaanka joogtada ah
1. Cabbiraadaha iska caabinta
2. Imtixaanada saamiga
3. Tijaabada Polarity
4. Wax Khasaare ah oo Xamuul ah oo Hadda socda ma jiro
5. Load khasaaraha iyo Voltage impedance
6. Tijaabada Voltage ee la dabaqay
7. Tijaabada adkaysiga korantada ee keentay
8. Cabbirka iska caabbinta dahaarka
9. Tijaabada Diidida oo leh Cadaadis loogu talagalay beddelayaasha Dareeraha Immersed
10. Tijaabada Dielectric Oil

Natiijooyinka Imtixaanka
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
/ |
/ |
/ |
Gudub |
|
2 |
Imtixaanada saamiga |
/ |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: Ii0 |
-0.04 |
Gudub |
|
3 |
Tijaabada polarity |
/ |
Kala goyn |
Kala goyn |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% kW |
I0 :: bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay Dulqaadka wax qabad la'aan waa +10% |
0.95 0.130 |
Gudub |
|
5 |
Load khasaaraha , danab impedance, khasaaraha guud iyo hufnaan |
/ kW kW |
t:85 darajo Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay dulqaadka impedance waa ± 10% dulqaadka wadarta rarka luminta waa +6% |
2.08 0.518 0.648 99.02 |
Gudub |
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
HV: 34KV 60s LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV): 2 Uur Muddada: 48 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV -LV ilaa Ground LV-HV ilaa Ground HV&LV ilaa Ground |
83.6 76.9 75.3 |
/ |
|
9 |
Tijaabada daadinta |
/ |
Cadaadiska la dabaqay: 20kPA Muddada: 12h |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
10 |
Tijaabada Dielectric Oil |
kV |
Ka weyn ama la mid ah 45 |
51.41 |
Gudub |
04 Baakaynta iyo dhoofinta
![]() |
![]() |
05 Goobta iyo Kooban
Our50kVA hal -tirka wejiga{2}}ku rakibanGuyana waxay xaqiijisaa qaybinta tamarta hufan, degan, iyo badbaadada.
Lagu farsameeyay - dabaylo naxaas ah oo tayadiisu sareyso, - xudunta dhaawaca luminaysa, iyo taangiga dibadeed waara-taangiga diyaarsan, waxa ay keentaa{3}} isku halaynta muddada dheer xataa marka loo eego deegaan baahida loo qabo.

Hot Tags: khadka koronto ee transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
50 kVA Beddeleyaasha Cirifka Utility-34.5/0.12*0.24 ...
75 kVA Nooca Cirifka -34.5 / 0.12 * 0.24 kV|Kanada 2024
75 kVA Transformer ee Xadhkaha Korontada-12.4*24.94/...
167 kVA Badelaha Qaybinta Cirifka-14.4/0.6 kV|Kanada...
50 kVA Transformer Dusha Korontada-7.97/0.12/0.24 kV...
50 kVA Transformer Utility Tiirka-13.8/0.24 kV|Guyan...
U dir sooji