5 MVA railway traction transformer

Hal-abuurnimada ku xidh, wad dariiqa mustaqbalka, transformers-ka jiidashada ayaa bixiya awood aan dhammaanayn.

 

 

01 Guud

1.1 Sharaxaada Mashruuca

5 MVA traction transformer waxaa la geeyey Koonfur Afrika 2025. Awoodda lagu qiimeeyey transformerka waa 5 MVA oo leh ONAN qaboojin. Korantada aasaasiga ah waa 132 kV oo leh ± 2*2.5% garaacista kala duwan (NLTC), korantada sare waa 2*1.22+1.22 kV, waxay samaysteen koox-vector Y/d{9}}℃/d-15 degree/d, Yd11.

Transformer-kan waxaa loogu talagalay nidaamyada tareennada casriga ah ee casriga ah, isaga oo isku daraya waxqabad aad u wanaagsan iyo astaamo dhowr ah oo ilaalin ah. Waxay ku qalabaysan tahay bedel{1} shubida tuubada oo leh gacan shaqaynaysa iyo bixinta quful, hubinta hawlgal ku haboon oo badbaado leh. Transformer-ku waxa uu adeegsadaa kulaylka sare{3}}kuleylka-kuleeyahay radiyeeriyeyaasha kulaylka leh-kuleelka galvanizing iyo rinji, kor u qaada iska caabbinta daxalka. Badbaadiyaha saliida leh qallajiye iyo cabirka heerka saliidda waxa uu ogolaanayaa{7}}ilaalinta dhabta ah ee xaalada caafimaad ee saliidda. Gaadhida gaaska sabbaynaysa ee{9}kaliya, ee leh alaarmiga iyo xidhiidhka safarka, ayaa si degdeg ah uga jawaaba xaaladaha khaladka ah. Isku-xidhka kulaylka ee xad-dhaafka ah ayaa bixiya ilaalin xad-dhaaf ah, oo muujisa culays{11}}xidhiidhka heerkulka iyo magdhawga deegaanka, oo leh hawlgelinta safarka heerkul go'an. Qalabka waxaa ku jira waalka siideynta cadaadiska si looga hortago cilladaha cadaadiska, wuxuu qaataa sanduuqyada terminaalka ee IP55 lagu qiimeeyay si ay ugu adkeystaan ​​bay'ada adag, oo ay ku jiraan transformers-ka hadda socda ee kormeerka saxda ah ee hadda jira. Nakhshad kororsigu waxa ay hubisaa isku halaynta iyo badbaadada jidka tareenka iyo codsiyada kale ee jiidista.

 

1.2 Tilmaamaha Farsamada

5 MVA-tareenka jiidashada tareennada nooca iyo xaashida xogta

loo geeyey
Koonfur Afrika
Sannadka
2025
Nooca
Beddelka jiidista
Heerka
IEC60076
Awood lagu qiimeeyay
5000 kVA
Soo noqnoqoshada
50 HZ
Marxaladda
3
Nooca qaboojinta
ONAN
Korantada aasaasiga ah
132 kV
Voltage Secondary
2*1.22+1.22 kV
Qalabka dabaysha
Copper
barokaca xagal
Yd±15 darajo ,Yd11
Caqabada
8.5%
Taabo Beddelka
NLTC
Riixista Range
±2*2.5%
Wax Xamuul ah ma jiro
7.7 kW
Wax Xamuul ah ma jiro
26.5 kW

 

 

1.3 Sawirro

5000 kVA sawir-qaadista jaantuska iyo cabbirka

5000 kVA traction transformer diagram

5 MVA railway traction transformer nameplate

 

 

 

02 Wax-soo-saarka

2.1 Core

Xuddunta waxa laga sameeyay go'yaal silikoon tayo sare leh oo -, kuwaas oo leh awood birlabeed aad u wanaagsan iyo khasaaro hooseeya, hubinaya hufnaan sare iyo xasilooni. Naqshadeynta qaab dhismeedka dahaaran waxay yaraynaysaa khasaaraha hadda jira waxayna sii kordhisaa waxqabadka dahaarka iyo waxtarka ka faa'iidaysiga tamarta iyada oo la adeegsanayo walxaha dahaarka ee u dhexeeya lakabyada. Xuddunta waxa loo qaabeeyey qaab xidhan- si loo sameeyo wareegtamaha birneedka xidhan oo kor loogu qaado ka faa'iidaysiga goobta magnetic iyadoo la tixgelinayo waxqabadka kulaylka si loo ilaaliyo heerkulka ku habboon ee ku shaqaynta ee culaysyada sareeyo, si loo sii dheereeyo nolosha adeegga. Intaa waxaa dheer, xudunta waxaa loogu talagalay in lagu yareeyo faragelinta elektromagnetic, hubinta xasilloonida iyada oo aan saameyn ku yeelan qalabka ku hareeraysan. Nidaamkeeda isu-ururinta si sax ah ayaa loo farsameeyay si loo hubiyo is-dhexgalka adag ee qaybaha, yaraynta gariirada farsamada iyo buuqa, iyo hagaajinta xoogga qaabdhismeedka iyo xasilloonida.

high-quality silicon steel sheets iron core

 

2.2 Dabaylaha

continuous disc windings

Ku xidhidh: Yd ± 15 darajo

Dhammaan dabaylaha ayaa si buuxda u dahaaran.

Sare - dabaylaha korantada: Xidhiidhka xidigta

Hooseeya-Dabaysha koowaad ee korantada: xidhiidhka Delta

Hooseeya -Dabaysha sare ee korantada: Dabaylaha hoose{1}}waa in lagu xidhaa delta dhexdeeda, iyada oo qaabaynta ka kooban laba dabaylo delta ah oo madax banaan, waji{2}}oo lagu wareejiyay 15 darajo . Waxaa jira wadar ahaan lix weji oo dabaysha labaad ah, mid walbana waxa uu leeyahay danab wax soo saar ah oo ku dhow 1220 volts. Dabaysha sare waa in loo qaabeeyaa in ay la jaanqaado laba iyo toban{7} unug hagaajinta garaaca wadnaha.
Hooseeya-Korantada dabaysha saddexaad: xidhiidhka Delta. Transformer-ku waxa uu bixiyaa saddex{2}} wejiga saddexaad ee dabaysha oo ah dhinaca labaad si uu koronto u siiyo taransfooriyaha kaaliyaha ah. Dabaysha saddexaad waxaa si toos ah looga taaban karaa dabaysha labaad ama waxaa laga dhigi karaa dabaylo saddexaad oo gooni ah. Dabaysha saddexaad waa in ay lahaataa duurka u goonida ah si ay koronta ugu shubto transformer-ka caawiyaha, kaas oo leh awood 100 kVA ah.

Dabaylaha sare -Voltajka waa in uu isticmaalo dabaylo saxan ah oo joogto ah,halka dabaylaha hoose -waa in uu isticmaalo dabaylo helical ah. Transformer-ka ayaa loo baahan yahay in lagu isticmaalo meelaha ay ka jirto danab daran. Xirayaasha hillaaca waa in lagu rakibaa inta u dhaxaysa-baska korantada ee sare iyo goynta saldhiga. Meesha dhexdhexaadka ah ee dabaysha xiddigta ugu weyn uma baahna in la soo saaro. Dabaylaha is beddelka ahi waa inuu lahaadaa awood farsamo oo ku filan oo uu iskaga celin karo qulqulka cilladaha.

 

2.3 Haanta

Haanta shidaalka waxa ay ka samaysan tahay taargooyin bir ah oo dhumucdiisu ka weyn tahay ama le’eg tahay 6mm, daboolka sare ee haanta shidaalkana waxa lagu xidhaa boolal. Haanta saliidda beddelka waa cawl, barkin saliiddu waa caddaan, dhumucdiisuna waa ugu yaraan 125 microns. Taangiga saliidda ee ugu weyn, waxaa ku yaal hal tuubo oo leh tuubo dhinaca ku dhow barkin saliidda iyo mid ka soo horjeeda, taas oo loo isticmaalo in lagu xiro filtarka saliidda. Dhererku wuxuu ku habboon yahay hawlgalka dhulka, oo leh hal dhinac oo sarreeya iyo kan kale oo hooseeya (haddii loo baahdo, dhinacan waxaa lagu dari karaa iyada oo la raacayo tuubada saliidda). Tubadu waxay leedahay dun gudaha ah oo ah 50mm.

steel plates oil tank of traction transformer

 

2.4 Kulanka ugu dambeeya

traction transformer final assembly

1. Rakibaadda dabaysha:

Ku rakib dabaylaha sare{0}voltage-ga xudunta, adoo fiiro gaar ah u leh lakabyada dabaylaha, tirada leexashada iyo habka isku xidhka (sida xidhiidhka xidigta ama xagasha).

Ka dib, rakib dabaylaha hoose{0}voltage hore iyo dabaylaha sare, hubinta in wejiga iyo habka isku xidhka dabayshu ay sax yihiin.

Ugu dambayntii, ku rakib dabaylaha saddexaad ee hooseeya{{0}voltage si aad u hubiso inay buuxisay shuruudaha sahayda korontada

2. Kor-u-qaadista iyo saliidaynta qaybta nool:

Kor u qaad qaybaha nool (dabaylaha iyo xudunta) beddelka boosaska loo qoondeeyay oo hubi in toosan sax ah.

Ku rakib qalabyada sida kuwa xidha hillaaca, relays, sanaadiiqda terminalka, iwm

Ka dib markii kor u qaadida la dhammeeyo, saliid waa in lagu duraa si loo hubiyo in transformer-ka uu si buuxda uga buuxo saliid gudaha ah si loo dammaanad qaado dahaarka iyo qaboojinta.

 

 

03 Tijaabinta

1. Tijaabada joogtada ah - Tijaabada Diidmada Cadaadiska Dareeraha -Tightness Testing

2. Tijaabada joogtada ah -Cabirka gaaska kala diri ee dareeraha dielectric ee qayb kasta oo saliid gaar ah marka laga reebo weeciye

3. Imtixaanka caadiga ah{1}

4. Tijaabada joogtada ah -Cabirka saamiga korantada iyo hubinta barakaca wajiga

5. Tijaabada joogtada ah -Cabirka caabbinta dabaysha

6. Tijaabada joogtada ah - Hubinta saamiga iyo kala duwanaanta la dhisay{2}}

7. Tijaabada joogtada ah - Cabbirka iska caabinta dahaadhka DC ee u dhexeeya dabayl kasta oo dhulka ku socota iyo inta u dhaxaysa dabaylaha

8. Tijaabada joogtada ah -Cabirka qodobka kala daadsanaanta (tanθ) ee awoodda habka dahaarka

9. Tijaabada joogtada ah-Go'aaminta awooda dabaylaha dhulka iyo inta u dhaxaysa dabaylaha

10. Tijaabada joogtada ah -Cabirka Maya{2}}luminta iyo hadda

11. Tijaabada joogtada ah -Cabirka maya{2}} lumitaanka rarka iyo hadda 90 % iyo 110 % danab la qiimeeyay

12. Tijaabada joogtada ah -Cabirka Gaaban -kahortagga wareegga wareegga iyo luminta rarka

13. Tijaabada joogtada ah - Tijaabada mawjadda buuxa ee laydhka ee terminaalka .(LI)

14. Nooca tijaabada -Go'aaminta heerka dhawaaqa (IEC 60076-10) ee hab kasta oo qaboojinta kaas oo loo cayimay heerka dhawaaqa dammaanad qaaday

15. Tijaabada gaarka ah-Cabirka jawaabta soo noqnoqda (Falanqaynta Jawaabta Soo noqnoqda ama FRA)

16. Tijaabada joogtada ah -Tijaabada Voltage ee la dabaqay (AV)

17. Tijaabada joogtada ah -Tijaabada adkaysiga korantada ee keentay cabirka PD (IVPD)

18. Tijaabada joogtada ah - Tijaabada Dahaarka Kaaliyaha.(AuxW)

19. Tijaabada joogtada ah -Cabirka gaaska kala diri ee dareeraha dielectric ee qayb kasta oo saliid gaar ah marka laga reebo qaybta beddelka weeciye.(imtixaam kadib)

20. Nooca tijaabada{1}} Heerkulka{2}}Tijaabada nooca kor u kaca

21. Tijaabada joogtada ah -Cabirka gaaska kala diri ee dareeraha dielectric ee qayb kasta oo saliid gaar ah marka laga reebo qaybta beddelka weeciye.(Tijaabada ka dib)

 

traction transformer testing

5 MVA railway traction transformer fat

 

 

04 Baakaynta iyo dhoofinta

4.1 Xirxirida

1. Ku duub galka saliidda ee jirka weyn wax la mid ah sida filimada oo ku dheji hoosta si aad uga hortagto in laga furo dekedaha gudaha iyo dibadda.

2. Tallaabooyinka ilaalinta waxaa loo qaataa sanduuqyada terminaalka, sanduuqyada dheeriga ah iyo qalabyada kale si looga hortago waxyeellada saameynta inta lagu jiro gaadiidka badda.

3. Dukumeenti warshadeed: Warbixinta tijaabada ee shirkadeena, buug-gacmeedka isbeddelka ee shirkadeena, iyo buug-gacmeedka dheeriga ah.

4. Baakadaha ka dib, xaqiiji cabbirka ugu dambeeya oo samee liiska baakadaha. 5. Laba koobi oo calaamad kasta oo raritaan ah waa in la daabacaa oo lagu dhejiyaa geeska bidix ee sare ee dhinacyada ku xiga xirmada.

5 MVA railway traction transformer packing

 

4.2 dhoofinta

11

U rarida transformerka 5MVA ee dekeda Durban ee hoos timaada CIF (Qiimaha, Caymiska, iyo Xamuulka) waxay ku lug leedahay dhowr tillaabo. Marka hore, baakooyinka transformer-ku waa in ay u hoggaansamaan heerarka badda, waana in la diyaariyaa dukumeentiyada khuseeya sida liiska baakadka, qaansheegta ganacsiga, iyo biilka rarida. Marka xigta, shirkad maraakiib ah oo ku habboon ayaa la doortaa, waxaana loo habeeyaa si badbaado leh loogu raro transformer-ka weelka maraakiibta. Inta lagu jiro habka gaadiidka badda, sideyaasha ayaa mas'uul ka ah oo bixiya caymiska khataraha gaadiidka. Marka la yimaado Durban, waa in la dhamaystiraa nidaamka banaynta kastamka, iyo qalab gaar ah oo loo isticmaalo in lagu dejiyo transformerka. Ugu dambeyntiina, waxaa la baarayaa muuqaalka transformer-ka iyo sida uu u shaqeeyo, si loo hubiyo in aysan jirin wax khasaare ah oo soo gaaray inta lagu guda jiro gaadiidka. Marka la eego shuruudaha CIF, iibiyuhu wuxuu qaadanayaa dhammaan kharashyada iyo khatarta la xiriirta gaadiidka ilaa uu koronto-bixiye si badbaado leh u gaaro dekedda uu ku socdo.

 

 

05 Goobta iyo Kooban

Gebagebadii, Transformers-keena waxaa loo farsameeyay si ay u daboolaan baahiyaha baahida hababka gaadiidka casriga ah, iyagoo bixinaya waxqabad la isku halayn karo iyo hufnaan gaar ah. Tignoolajiyada horumarsan iyo dhismo adag, transformers-yadani waxay xaqiijinayaan maamulka tamarta ugu fiican iyo kor u qaadida badbaadada hawlgalka ee codsiyada tareenada iyo metro. Sida lamaane lagu kalsoon yahay ee warshadaha, waxaa naga go'an inaan keeno{2}}alaab tayo sare leh oo aan kaliya buuxin balse dhaafsan filashada macaamiisheena. U dooro Transformers-kayaga si aad u hesho xal waara oo hufan kaasoo awood u siinaya mustaqbalka gaadiidka.

5 MVA railway traction transformer south africa

 