Tilmaanta beddelayaasha Radial iyo Loop Feed Transformers

Mar 09, 2026

Fariin ku dhaaftid

Radial and Loop Feed Transformers

Qaybinta awoodda korantada, ereyada "loop feed" iyo "radial feed" waxay qeexayaan sida korontadu uga soo qulqulayso isha ilaa transformers-ka hoos u dhigaya tamarta isticmaalayaasha dhamaadka. In kasta oo erayadani ay ka soo jeedaan qaabaynta nidaamka qaybinta ballaaran, waxaa inta badan loo isticmaalaa in lagu qeexo -Voltajka (HV) ee isku xidhka baadiyaha suufka - ku rakiban transformers.

Doorashada dhexda radial ama loop feed transformer waxay saamaynaysaaisku halaynta, dabacsanaanta, iyo qiimahaee shabakadaada korontada. Hagahan ayaa sharaxaya sida nidaamyadani u shaqeeyaan, kala duwanaanshahooda jireed, iyo sida loo doorto qaabaynta saxda ah ee mashruucaaga.

 

 

 

I. Fahamka Nidaamyada Qaybinta Radial iyo Loop

 

Ka hor inta aan la baadhin transformers-ka laftooda, waxaa lagama maarmaan ah in la fahmo labada nooc ee hababka qaybinta ee ay u adeegaan.

 

Nidaamka Quudinta shucaaca

Nidaamka quudinta shucaaca ayaa ah qaabka ugu fudud uguna badan ee awood qaybsiga. Nashqadan, korontadu waxay ka socotaa hal il (sida substation) dibadda iyada oo raacaysa hal waddo oo loo maro rarka, si la mid ah afhayeennada giraangiraha. Transformer kastaa wuxuu awood ka helaa hal dhibic oo keliya.

  • Faa'iidooyinka:Way fududahay in la naqshadeeyo, lagu shaqeeyo, oo la ilaaliyo. Qiimaha bilowga ahi wuu hooseeyaa sababtoo ah waxay u baahan tahay qalab yar.
  • Khasaaro:Waxay bixisaashaqo dhimis la'aan. Haddii isha keliya ay fashilanto ama cilad ka dhacdo khadka, dhammaan transformers-ka hoose iyo macaamiishu waxay luminayaan awoodda ilaa dayactirka la sameeyo.
Radial distribution system
Nidaamka qaybinta shucaaca
Radial feed diagram of pad mounted transformer
Jaantuska quudinta shucaaca ee suufka ku rakiban transformer

Nidaamka Quudinta Loop

Nidaamka quudinta loop waxaa loogu talagalay isku halaynta sare. Qaabayntan, xariiqda qaybinta waxay samaysaa loop, transformers-yadu waxay awood u leeyihiin inay awood ka helaanlaba ama ka badan jiho ama ilo.

  • Faa'iidooyinka:Waxay bixisaashaqo ka dhimis. Haddii ciladu ka dhacdo dhinac ka mid ah loop-ka ama hal il ay fashilanto, awoodda ayaa laga rogi karaa jihada kale, iyada oo la ilaalinayo nidaamka tamarta. Tani waxay ka dhigaysaa mid ku habboon tas-hiilaadka muhiimka ah.
  • Khasaaro:Waxay u baahan tahay qorshayaal ilaalin oo kakan iyo maalgashi hore oo sarreeya sababtoo ah fiilooyinka iyo furayaasha dheeraadka ah.

 

Loop feed distribution system
Habka qaybinta quudinta loop
Loop feed diagram of pad mounted transformer
Jaantuska quudinta loop ee beddelka suufka ku rakiban

 

 

 

 

 

II. Habaynta Bushing: Farqiga Jirka

 

 

Farqiga ugu cad cad ee u dhexeeya labadan nooc ee transformers waxay ku jirtaa -qaybtooda korantada ee sare. Nashqadan jireed waxa ay tilmaamaysaa sida taransfooriyuhu ugu xidhmo shabkada

 

Habaynta Buushka Radial Feed

Transformer feed radial waxa loo nashqadeeyay hal -dhibcood koronto Qaybteeda sare -qayb koronto ayaa ka koobansaddex bushings aasaasiga ah(sida caadiga ah waxaa lagu calaamadiyay H1, H2, H3) -mid ka mid ah weji kasta oo soo gala Naqshaddan fudud waxay ku badan tahay xaafadaha la deggan yahay, meelaha ganacsiga yaryar, ama sida unugga ugu dambeeya ee xargaha beddelka ee xariiqdu ka baxdo.

Radial Feed Bushing Configuration

 

Qaabaynta Dhirta Quudinta Loop

Beddelka quudinta loop waxaa loogu talagalay dabacsanaan iyo dib u soo celin. Waxay ka kooban tahaylix sare -bushing voltaji-laba qaybood oo buuxa oo saddex ah (sida caadiga ah waxay ku calaamadsan yihiin H1A, H2A, H3A dhanka "A" iyo H1B, H2B, H3B dhanka "B"). Tani waxay u ogolaaneysaa laba quudin aasaasiga ah:

  • Isku-dubbaridaha Isku-dhafka:Fiilooyinka isha ka soo baxa waxay galaan baadiyaha "A" cutubka koowaad, ka dibna ka baxa baadiyaha "B" si ay u quudiyaan duurka "A" ee transformerka xiga. Dais-gan -waxa ay isku xidhan yihiin unugyo badan
  • Quudinta Labada Isha:Hal unug ayaa lagu xidhi karaa laba ilo koronto oo kala duwan. Dareemaha xulashada gudaha ayaa u oggolaanaya hawlwadeenada inay doortaan isha quudinaysa culeyska.

Loop Feed Bushing Configuration

Fadlan ogow: "loop of transformers" wuu ka duwan yahay "nidaamka loop." Waa suurtogal in lagu xidho taxanayaal taransfoorayaal ah oo loop ah, laakiin haddii ay dhamaantood ku tiirsan yihiin hal il koronto, ka dib guuldarada ishaas waxay sababi doontaa in dhammaan unugyadu ay lumiyaan tamarta{1}} taasoo la macno ah qaabayntu inay ahaanayso radial.

a loop of transformers is different from a loop system

Muuqaal

Beddelka Quudinta shucaaca

Loop Feed Transformer

Sare - Buushka Voltage

Saddex (H1, H2, H3)

Lix (H1A, H2A, H3A, H1B, H2B, H3B)

Kakanaanta Naqshadeynta

Fudud

Kakan badan

Isha Korontada

Hal dhibic kaliya

Hal il ama laba ilood

Ku-noqoshada

Midna- hal dhibic oo guul darro ah

Quudin heer sare ah- waa la heli karaa

Qiimaha caadiga ah

Hoose

Sareeye

 

 

 

III. Badbaadinta, Ilaalinta, iyo Beddelka

 

Marka laga soo tago tirada baadiyaha, loop feed transformers waxay bixiyaan sifooyin horumarsan oo kor u qaadaya isku halaynta xadhkaha iyo joogteynta.

 

Dib-u-celinta iyo Go'doominta Ciladda

In nidaamka loop leh transformers badan, gudahabayonet fiyuusbixiyaan ilaalin muhiim ah. Haddii ciladu ka dhacdo dhinaca labaad ee hal transformer, fiyuuska aasaasiga ah ayaa afuufaya. Taniwaxay go'doomiyaan transformer-ka khaldanlaga bilaabo wareegga, taas oo u oggolaanaysa awoodda inay sii socoto iyada oo u gudubta qalabka kale ee wareegga. Tani waxay yaraynaysaa wakhtiga dhimista waxayna ku koobtaa maqnaanshaha hal rar.

bayonet fuse

 

Habaynta Bedelka Xulashada

Transformers loop feed waxaa lagu qalabayn karaa saliid{0}}qalabka dooraha la quusiyay si loo maareeyo socodka awooda Furayaashani waxay bixiyaan awooda ay ku jiheeyaan hadda ama go'doomiyaan transformerka iyada oo aan - tamar siin wareegga oo dhan. Habaynta caadiga ah waxaa ka mid ah:

  • Saddex Labo -Meesha Raashiyaha Booska:Mid ka mid ah beddelka ayaa maamula transformer-ka laftiisa, midna wuxuu maamulaa quudinta "A" ee soo socota, midna wuxuu maamulaa quudinta "B". Tani waxay bixisa isku-bedelka ugu sarreeya, taasoo u oggolaanaysa hawl-wadeenka inuu go'doomiyo transformerka isagoo ilaalinaya wareegga tamar.
2-Position Load Break Switch
2-Bedelka booska
Two-Position Load Break Switches
Labo -Meesha Bedelka

 

  • Afar - Booska Culayska Bedelka:Dareemadan kelida ah (oo inta badan loo yaqaan "loop feed switch") ayaa isku daraa hawlaha, taas oo u oggolaanaysa hawl-wadeennada inay doortaan Quudinta A, Quudinta B, ama go'doomiso cutubka, in kasta oo koontaroolku wax yar ka yar yahay saddexda -.
4-Position Load Break Switch
4-Bedelka booska
Four-Position Load Break Switch
Afar - Bedelka booska

 

 

 

IV. Sida loo doorto Transformer sax ah

 

 

Xulashada u dhaxaysa radial iyo loop feed transformer waxay ku xidhan tahay shuruudaha gaarka ah ee mashruuca ee isku halaynta, miisaaniyada, iyo koritaanka mustaqbalka.

Goorta la dooranayo quudinta shucaaca

Transformers feed shucaaca ayaa ugu fiican codsiyada halka qiimuhu yahay welwelka koowaad iyo maqnaanshaha kooban ee loo dulqaadan karo.

Qaybaha deegaankaiyo miyiga.

Goobaha ganacsiga fududoo leh culays la saadaalin karo.

U adeegaya sidabarta joojintadhamaadka loop{0}} khadka quudinta

Mashaariic lehcaqabado miisaaniyadeed oo adag.

 

Goorta la dooranayo Quudinta Loop

Transformers loop feed ayaa ah doorashada la door bidayo ee hamiga{0}}arjiyada muhiimka ah halkaas oo wakhtigu muhiim yahay

Isbitaalada, garoomada diyaaradaha, iyo xarumaha xogtahalkaasoo awood joogto ah ay muhiim tahay.

Xarumaha jaamacadaha iyo xarumaha waaweyn ee warshadahaoo u baahan kalsooni sare.

Nidaamyada u baahandabacsanaanta dayactirka, u oggolaanaya in transformer-ka la hagaajiyo iyada oo aan la xidhin shabakada oo dhan.

Rakibaadaha halka mustaqbalkakorriinka rarkawaxa laga yaabaa inay u baahato in lagu daro transformers badan oo loop ah.

Radial Feed pad mounted transformer
Radial Feed pad ku rakiban transformer
Loop Feed pad mounted transformer
Loop Feed suuf ku rakiban transformer

Qoraal ku saabsan Wax-ka-bedelka

Waa suurtagal in la isticmaalo aloop feed transformer in hab radial ah. Xaaladahan oo kale, qaybta labaad ee baadiyaha (B{1}}dhinac) si fudud ayaa loo daboolay ama lagu rakibay kuwa xidhaya qalliinka. Si kastaba ha ahaatee, waa dhif in la isticmaalo aRadial feed transformer ee habka loop, maadaama saddexdeeda-naqshadeeda baadiyaha aysan qaadi karin quudin labaad iyada oo aan la helin wax ka beddel dibadeed oo adag.

elbow arresters
xusul duubayaasha
pad mounted transformer with surge arresters
suuf ku rakiban transformer-ka oo leh xirayaal qallafsan

V. Gabagabo

Doorashada u dhaxaysa radial iyo loop feed transformers ayaa ugu dambeyntii qeexaysa isku halaynta iyo kakanaanta shabakadaada qaybinta tamarta.Transformers radial feedU soo bandhig fudud, kharash{0}xal wax ku ool ah codsiyada caadiga ah ee leh saddex bushings iyo hal il koronto.Loop quudinta transformers, oo wata lixdooda- nashqadeynta duurka iyo beddelka ikhtiyaariga ah ee gudaha, waxay bixiyaan dib-u-celinta iyo dabacsanaanta looga baahan yahay kaabayaasha muhiimka ah. Markaad qiimeyso baahidaada wakhtiga ku-meel-gaadhka ah ee miisaaniyadaada, waxaad dooran kartaa qaabaynta hubinaysa badbaadada, hufan, iyo gaarsiinta awooda la isku halayn karo.

 

U dir sooji