Dry Type Transformer Installation

1. Hordhac

Hagahan waxa uu bixiyaa tilmaamo dhammaystiran oo ku saabsan rakibaadda, hawlgalka, iyo dayactirka qalalan{0}}nooca beddelka korontadu. Waa lagu dabaqi karaa kuwa aan -qalalan ee kicinta -nooca Transformers power and on -regulation resin epoxy resin -nooca transformers koronta oo leh awood ilaa 6300 kVA ah iyo qiimaynta danab ilaa 35kV. Tilmaamaha halkan ku jira waxay daboolayaan gaadiidka, kaydinta, rakibaadda, ka hor{9}} kormeerka adeega, tijaabinta, hawlgalka, iyo dayactirka.

Heerarka lagu dabaqi karo:Nooca qalalan{0}Transformers ee lagu daboolay hagahan waxa loo qaabeeyey oo loo soo saaray si waafaqsan heerarkan soo socda: GB 6450-86Qalalan -nooca Awood beddelayaasha, GB 10228-1997Hababka Farsamada iyo Shuruudaha Qalalan{0}}nooca Transformers Power, iyo GB 1094.1-1996Beddeleyaasha Awoodda{0}Qaybta 1: Guud. Codsiyada caalamiga ah, waxaa sidoo kale loo tixraaci karaa IEC 726 iyo GB/T 1094.11 -2022 *Power Transformers-Qaybta 11: Transformers nooca qalalan*.

Qalalan{0}nooca taransfoorayaasha ayaa si gaar ah u wanaagsan{1}}ku haboon codsiyada halka ay badbaadada dabku tahay walaaca koowaad, oo ay ku jiraan- dhismayaal sare u kaca, xarumaha ganacsiga, goobaha ciyaaraha, tas-hiilaadka batroolka, nidaamyada tareenada dhulka hoostiisa mara, garoomada diyaaradaha, iyo meelaha kale ee leh shuruudaha ilaalinta dabka ee adag.

 


 

 

 

 

2. Xaaladaha Shaqada

 

 

 

2.1 Shuruudaha Adeegga Caadiga ah

Nooca qalalan{0}Transformers waxaa loogu talagalay in lagu shaqeeyo xaaladahan caadiga ah:

Halbeegga

Heerka caadiga ah

Heerkulka deegaanka

Ka hooseeya 40 digrii

Dhererka

Ka hooseeya 1000 m oo ka sarreeya celceliska heerka badda

Qoyaanka Qaraabada

Ka hooseeya 93% (wax uumi ah malaha dusha gariiradda)

Goobta Rakibaadda

Gudaha, si wanaagsan{0} hawo u leh, oo ka nadiif ah kiimikooyinka iyo walxaha sunta ah

Marka heerkulka deegaanku uu dhaafo 40 digrii ama joogga uu ka sarreeyo 1000 m, waa in la hagaajiyo qiimaynta beddelka iyadoo la raacayo shuruudaha GB 6450.

 

2.2 Fasalada Ilaalinta

Nooc qallalan{0}Transformers ayaa diyaar ah oo wata saddex fasal ilaalinta caadiga ah:

IP00:Ma jiro ilaalin meel-xiran; ku habboon in lagu rakibo qolal koronto oo go'an ama shirar-bedeleedka.

IP20:Waxay ka hortagtaa walxaha adag ee qalaad ee ka weyn dhexroorka 12 mm. Tani waa xayndaabka ugu badan ee la isticmaalo gudaha gudaha, iyadoo si wax ku ool ah uga hortagaysa xidhiidhka shilalka ah ee qaybaha nool iyo ka hortagga xayawaanka yaryar (jiirka, masaska, bisadaha, shimbiraha, iwm.) inay galaan oo ay keenaan wareegyo gaaban.

IP23:Marka lagu daro ilaalinta IP20, xirmooyinka IP23 waxay ka hortagayaan soo galitaanka biyaha dhibcaha dhibcaha ku dhacaya xagal ilaa 60 digrii oo toosan. Tani waxay ka dhigaysaa inay ku habboon yihiin rakibaadda dibadda ama bay'adaha leh soo-gaadhista buufinta biyaha fudud. Si kastaba ha noqotee, ogow in xirmooyinka IP23 ay yareeyaan awoodda qaboojinta beddelka, oo u baahan tixgelinno.

dry type transformer enclosure installation
xirid rakibidda
IP20 enclosure
xiritaanka IP20

 

2.3 Hababka qaboojinta

Laba hab oo qaboojinta ayaa diyaar u ah qalalan{0}nooca transformers:

AN (Hawada Dabiiciga ah):Qaboojinta convection dabiiciga ah iyada oo aan qasab ahayn socodka hawada.

AF (Awoodda Hawada):Qaboojinta hawada qasabka ah iyadoo la isticmaalayo marawaxadaha. Markaad ka shaqaynayso meelo xaddidan ama meelaha hawo liidato, qalabka AF waa in lagu daraa. Mugga hawada dheeriga ah ee loo baahan yahay waa 4 m³/daqiiqadii 1 kW ee wadarta khasaaraha (P₀ + Pₖ).

AN cooling
AN
AF cooling
AF

 

 

 


 

 

 

 

3. Xulashada Transformer iyo Cabbirka

 

 

 

Xulashada beddelka saxda ah waxay muhiim u tahay isku halaynta nidaamka iyo waxtarka tamarta.

3.1 Go'aaminta Awoodda La Qiimeeyay

Awoodda lagu qiimeeyay transformerka (kVA) waa in lagu saleeyaa culeyska la xisaabiyay ee qalabka ku xiran. Marka hore, xisaabi culayska dhabta ah adiga oo soo koobaya qiimaynta awooda qalabka oo aad adeegsato qodob kala duwan. Awooda la qiimeeyay waa in markaas la doortaa si ay waxyar uga badato culayskan la xisaabiyay si loo habeeyo kobaca rarka mustaqbalka.

 

3.2 Halbeegyada Waxqabadka Muhiimka ah

Markaad dooranayso transformer, waa in si taxadar leh loo qiimeeyaa cabbirada soo socda:

Heerka Korantada:Waa in uu u dhigmaa korantada sahayda iyo shuruudaha korantada ee qalabka ku xiran. Tusaale ahaan, sahayda 10kV ee u adeegaya 0.4kV waxay u baahan tahay 10kV/0.4kV transformer.

Maya - Khasaaraha rarka iyo rarka:Halbeegyadani waxay si toos ah u saameeyaan waxtarka tamarta. Qiimayaasha hoose waxay muujinayaan hufnaan wanaagsan iyo hoos u dhac ku yimid kharashyada hawlgalka.

Korontada wax-ka-qabashada:Waxay saamaysaa nidaaminta danab iyo gaagaaban - heerarka hadda jira

Heerka qaylada:Ku rakibida sawaxanka{0}}deegaanka xasaasiga ah, moodooyinka buuqa yar-(sida caadiga ah<55 dB) are preferred.

cast coil dry type transformer
tuur gariiradda nooca qalalan transformer
VPI dry type transformer
Transformer nooca qalalan VPI

 

 


 

 

 

 

4. Gaadiidka

 

 

 

4.1 Shuruudaha Gaadiidka Guud

Transformers waxa lagu keeni karaa jidka tareenka, rarida, gaadhiga, ama gaadiidka cirka. Gaadiidka iyo weelasha waa inay nadiif ahaadaan oo engegan yihiin.

4.2 Soo dejinta iyo sugidda

Transformers waa in si ammaan ah loogu hagaajiyaa gaadiidka gaadiidka dhexdiisa iyadoo la isticmaalayo taayirrada, xargaha, iyo silsiladaha wadajirka ah.

Ha xidhin ama ha jiidin gariiradda, dahaarka, taarikada, ama sunta rasaasta, sababtoo ah tani waxay dhaawici kartaa alaabta.

U janjeedha taransfooriyaha inta lagu jiro gaadiidka waa in aanu ka badnayn 30 digrii .

4.3 Dhigista iyo Kaydinta Inta lagu jiro Gaadiidka

Ha isku dhejin Transformers inta lagu jiro wareejinta ama meelaha laga baxo.

Laxaha isdhaafka ah ee alwaaxyada ah waa in la geliyo isbedelka hoostiisa, dhererkiisuna aanu ka badnayn 100 mm.

4.4 Dukumentiyada iyo Agabka la socda

Dhammaan agabka, qaybaha spare, iyo ex{0} dukumeentiyada shaqada waa in lala keenaa transformerka.

transformer loading
ku shubidda transformer
transformer shipping
Transformer maraakiibta

 

 

 

 


 

 

 

 

5. Kormeerka iyo Ogolaanshaha

 

 

 

Marka la helo Transformer-ka, macmiilku waa inuu isla markiiba sameeyaa jeegaga aqbalaadda soo socota:

5.1 Xaqiijinta saxanka magaca

Xaqiiji in xogta lagu sharraxay taarikada magaca (awoodda la qiimeeyay, qiimeynta danab, boosaska tuubada, kooxda vector, danab korantada, iwm.) ay waafaqsan tahay tilmaamaha lagu sheegay qandaraaska iibka.

5.2 Hubinta dukumentiyada

Xaqiiji in dhammaan dukumeentiyadii hore ({0}) ay dhammaystiran yihiin oo waafaqsan shuruudaha heshiiska.

5.3 Agabka iyo Qaybaha

Ka hubi dhammaan qaybaha burburay iyo agabka lidka ku ah liiska baakadka si aad u xaqiijiso in aanay jirin waxyeelo ama shay maqan.

5.4 Kormeerka Xaalada Jirka

Ka baadh taransfooriyaha iyo qaybaha uu ka kooban yahay burburka ama barokaca muuqda.

Hubi khadadka isku xirka dabacsanaan ama dillaac.

Iska ilaali dildilaaca ama waxyeelada kale

Ka saar alwaaxyada isgoysyada ah haddii ay jiraan.

5.5 Kaydinta Kormeerka Kadib

Haddi aan taransfooriyaha la galinayn isla markaaba baadhista ka dib, waa in dib loo baakadeeyaa oo si haboon loo kaydiyaa.

 

 


 

 

 

 

6. Kaydinta

 

 

 

6.1 Xaaladaha Kaydinta

Alaabooyinka iyo agabka u baahan kaydinta waa in aan kiisaskooda la furin marka laga reebo hubinta iyo aqbalida. Kormeerka ka dib, isla markaaba dib u xir.

Kaydinta muddada dheer-, dhig transformers iyo accessories meel engegan, nadiif ah, oo si fiican{1}}Qol hawo leh

Ha ku kaydin kiimikooyinka ama walxaha daxalka isku qol.

Ha rarin alaabta.

6.2 Gudaha vs. Kaydinta Dibadda

Nooca qallalan{0} waa in lagu kaydiyaa gudaha Haddi gaaban - kaydinta dibaddu waa mid aan laga maarmi karin caqabadaha goobta awgeed:

Ha furin daboolka.

Hubi oo ilaali daboolka si aad biyuhu u ilaalinayaan.

Dhig biraha isgoysyada ah ee ka hooseeya beddelka (dhererka in ka yar ama la mid ah 100 mm).

6.3 Xadka Muddada Kaydinta

Kaydinta dibadda waa in aanay ka badnaan laba bilood. Heerkulka jawigu inta lagu jiro kaydinta dibadda waa inuusan hoos uga dhicin -10 digrii .

Dry-type transformers indoor storage
Qalalan{0}nooca transformers kaydinta gudaha
dry type transformer storage
kaydinta transformer nooca qalalan

 

 

 


 

 

 

 

7. Rakibaadda ugu dambeysa ee Goobta

 

 

 

7.1 Kahor{1} Diyaarinta Rakibaadda

Kahor intaadan bilaabin rakibidda:

Baro qeexitaannada rakibidda, xogta taarikada magaca, iyo sawirka guud ee si taxadar leh.

Diyaarso qalabka ku habboon ee wax qaadista (wiishashka, fargeetoyada, wiishashka xamuulka) iyo wiishka.

7.2 Qaadista iyo Wax ka qabashada

Habka qaadista saxda ah waa muhiim si looga hortago burburka qalabka:

Kor u qaadida waa in lagu sameeyaa iyadoo la isticmaalayo dhamaan giraangiraha kor u qaadida qalabka isku mar isku mar ah{0}} waligaa ha qaadin faraanti gaar ahaaneed

Marka kor loo qaadayo transformer-ka aan baakadnayn ama laga saarayo baakidhkiisa, xagasha wax-qaadista waa in aanu dhaafin 60 digrii .

Transformers-ka lagu soo raray -kuwa shubayaasha (OLTC) ee ku xidhan, wiish adoo isticmaalaya faraantiyada kor u qaadida transformerka kaliya{1}}ha qaadin OLTC.

Marka bartamaha cuf-jiidadka la damiyo, hagaaji dhererka fiilooyinka qaadista si waafaqsan dheelitirnaanta.

Si taxadar leh ula tacaala inta lagu guda jiro habka isu imaatinka.

Lifting and Handling of dry type transformer

7.3 Qaabka goobta iyo nadiifinta

Shuruudaha nadiifinta

Fogaanta Ugu Yar

Beddelka gidaarka ama xannibaadda

Ka weyn ama la mid ah 500 mm

Inta u dhaxaysa transformers ku xiga

Ka weyn ama la mid ah 500 mm

Transformer sare -dhinaca korantada ee gidaarka

Ka weyn ama le'eg 800 mm (la taliyay)

Transformer hoose -dhinaca korantada ee gidaarka

Ka weyn ama le'eg 600 mm (la taliyay)

Balaadhka marinka shaqada

Ka weyn ama la mid ah 1200 mm

Beddelka deyrka/xakamaynta

Ka weyn ama la mid ah 600 mm

Inta u dhaxaysa laba transformers (heerka naqshadaynta)

Ka weyn ama la mid ah 1.0 m

7.4 Fogaanta Badbaadada Ugu Yar (Sare-Goolka Korantada ilaa Dhulka)

Masaafada ugu yar ee badbaadada ee u dhaxaysa kirishbooyada tamarta leh iyo dhulka waa inay u hoggaansamaan GB 10237Tijaabada Heerka Dahaadhka iyo Tijaabada Dahaarka ee Hawada Sare:

Qiimaynta HV

In ka yar ama la mid ah 1 kV

6 kV

10 kV

15 kV

20 kV

35 kV

Nadiifinta saafiga ah (mm)

40

60

90

120

160

250

Nidaamyada 12 kV, masaafada saafiga ah ee daboolka hawadu waa inay ka weyn tahay ama la mid tahay 125 mm; Nidaamyada 40.5 kV, Ka weyn ama la mid ah 360 mm. Masaafada gurguurta ayaa ka weyn ama la mid ah 18 mm/kV dahaarka dhoobada iyo ka weyn ama la mid ah 20 mm/kV ee dahaarka organic.

7.5 Aasaaska iyo Koritaanka

Aasaaska beddelka waa in ay lahaadaan biraha barroosinka ee la qotomiyey si waafaqsan sawirka guud ee sawirka si ay ula jaan qaadaan godadka koronto-bilaha.

Aasaaska la taaban karo waa in ay lahaadaan awoodda wax-qaadista oo ka weyn ama la mid ah 1.5 jeer miisaanka beddelka, oo leh weecasho heer siman In ka yar ama la mid ah 2 mm/m.

Wixii seismic ah ama gariirka {{0}Rakibaadaha xasaasiga ah, gariirka caagga{1} suufka qoynaya ( dhumucdiisu ka weyn tahay 10 mm) waa in lagu rakibaa dhammaan afarta gees.

Transformers-ka ku qalabaysan taayirrada aan shaqaynayn, taayirrada waxa loo rogi karaa 90 digrii dhanka leexashada. Marka la meel dhigo ka dib, taayirrada waa in meesha laga saaraa ama lagu xidhaa meesha, oo transformer-ka lagu hagaajiyaa iyada oo la adeegsanayo biraha barroosinka ah.

Dabagalka (saldhiga maraakiibta) waa in la burburiyaa ka dib meelaynta.

7.6 Isku xirka Cable iyo Basbar

Fiilooyinka soo galaya iyo kuwa baxaya ama baska waa in si sax ah loo taageero oo la isku dhejiyaa si looga hortago culeyska farsamada ee terminaalka beddelka.

Kala-goysyada baska naxaasta ah waa in la nadiifiyaa oo lagu dahaadhay dufan wax dhaqaajiya ka hor inta aan la xidhin.

Shuruudaha Torque ee xirayaasha:

Cabbirka Bolt

M10

M12

M16

M20

Torque (Nm)

30

33

35

45

7.7 Dhulka

Dejinta saxda ah ayaa muhiim u ah badbaadada:

Xayndaabka beddelka, xudunta, iyo barta dhexdhexaadka ah waa inay si madaxbanaan u qotomaan.

Daariyaasha dhulka waa in ay isticmaalaan fiilo naxaas ah oo leh iskutallaab - aag ka weyn ama la mid ah 50 mm².

Iska caabbinta dhulka waa in ay ka yar tahay ama la mid tahay 4Ω.

 

dry type transformer site installation
rakibaadda goobta beddelka nooca qalalan
dry type transformer site install
goob qalalan ku rakib transformer

 

 

 


 

 

 

 

8. Kormeerka Kahor Adeegga

 

 

 

Kahor inta aan transformer-ka la gelin adeegga, kormeerrada soo socda waa in la sameeyaa:

8.1 Kormeerka Farsamada

Hubi dhammaan xirayaasha iyo xirayaasha; dib u adkee - sida loo baahdo

Xaqiiji in dhammaan qaybaha si habboon loo rakibay oo loo xafiday.

Ka saar wax kasta oo qalaad ama boodhka urursan (tixraac Qaybta 11.2 ee nidaamka nadiifinta).

8.2 Nidaamka qaboojinta iyo Kormeerka Xakamaynta heerkulka

Hubi taageereyaasha si aad u hubiso in hawlgal caadi ah

Hubinta halista ah:Hubi jihada wareega ee sadexda{0} taageereyaasha beddelka wejiga Socodka hawadu waa inuu ka yimaadaa gariiradda hoosteeda. Haddii jihadu khaldan tahay, beddel habka isku xigxiga si waafaqsan tilmaamaha.

Hubi xakamaynta heerkulka iyo cutubyada bandhiga heerkulka si ay u hawlgalaan caadiga ah.

Hubi in si sax ah loo dejiyo heerkulbeegyada heerkulbeegyada iyo qalabyada si waafaqsan tilmaamahooda.

Xaqiiji in dareemaha xakamaynta heerkulka si sax ah loo geliyo godadka cabbirka heerkulka dabaylaha (xool-galinta 80mm ka weyn ama la mid ah).

8.3 Heerarka Xakamaynta Heerkulka ee Default

Halbeegyada caadiga ah ee caadiga ah ee qalalan{0}noocyada heerkulka beddelka waa:

Heerka Heerkulka

Ficil

In ka yar ama la mid ah 80 digrii

Taageerayaashu way joojiyaan

Ka weyn ama la mid ah 100 digrii

Taageerayaashu waxay si toos ah u bilaabaan

Ka weyn ama la mid ah 130 digrii

In ka badan- alaarmiga heerkulka

Ka weyn ama la mid ah 150 digrii

Safarka heerkulka ka badan-

 

 

 


 

 

 

 

9. Tijaabi Adeegga Kahor

 

 

 

Tijaabooyinka soo socda waa in la sameeyaa ka hor inta aan taransfooriyaha la gelin adeegga:

9.1 Cabbirka Iska caabinta DC

Cabir iska caabinta DC ee dabaylaha dhammaan goobaha tuubada si aad u xaqiijiso xidhiidhka saxda ah oo aad u aqoonsato xidhiidh kasta oo dabacsan.

9.2 Heerka Korantada iyo Tijaabada Kooxda Vector

Cabbir saamiga korantada ee dhammaan boosaska tuubada oo xaqiiji calaamadinta kooxda vector.

9.3 Xaqiijinta dhulka

Hubi in qalabka wax beddelka (transformer) iyo xudunta u yihiin kuwo si joogto ah u fadhiya.

9.4 Cabbirka Caabbinta Dahaarka (Windings)

Tijaabi

Shuruudaha

Megohmmeter

HV–LV & HV–Dhulka

Ka weyn ama la mid ah 300 MΩ

2500 V

LV–Dhulka

Ka weyn ama la mid ah 100 MΩ

2500 V

Xaaladaha tijaabada:Heerkulka 20-30 digrii, qoyaan qaraabo ah oo ka yar ama la mid ah 90%

Qiimaha iska caabinta dahaarka ayaa hoos u dhici doona xaaladaha qoyan. Xaaladaha qoyan, qiimaha iska caabintu waa inuusan ka yarayn 2 MΩ 1000 V ee danab la qiimeeyay (akhrinta oo lagu qaaday 25 darajo hal daqiiqo). Transformers ee noqday qoyan ama muujinaya calamadaha uumi/baraf, daawaynta qalajinta waa in la sameeyaa ka hor adeega oo u adkeysata tijaabinta korantada, iyada oo aan loo eegin qiyamka caabbinta dabaysha.

9.5 Tijaabada Iska caabinta Dahaarka Muhiimka ah

Ka saar saxanka gogoldhigga ubucda ka hor inta aanad tijaabin.

Tijaabi

Shuruudaha

Megohmmeter

Xudunta – Clamps & Dhulka

Ka weyn ama la mid ah 2 MΩ

500 V

Daloolin - Gariiradda & LV

Ka weyn ama la mid ah 100 MΩ

500 V

Xaaladaha tijaabada:Heerkulka 20-30 digrii, qoyaan qaraabo ah oo ka yar ama la mid ah 90%

Marka lagu jiro xaaladaha qoyan, qiyamka la qiyaasay wuu yaraan doonaa. Qalajinta daawaynta ka dib, qiimaha iska caabintu waa in uu ka weynaadaa ama la mid yahay 0.1 MΩ ka hor inta aan qalabka beddelka loo gelin adeegga.

9.6 Daaran - Korjoogteynta Bedelka Tabaha (OLTC) Kormeerka

Transformers-ka ku qalabaysan OLTC, baadh oo tijaabi si waafaqsan tilmaamaha soo saaraha OLTC ka hor inta aan la hawlgelin.

9.7 Inta jeer ee Korontada U adkeysiga Imtixaanka Korantada

Codso inta jeer ee korontadu u adkeyso danabka 85% ee tamarta tijaabada warshadda.

9.8 Kooban Imtixaanka Ogolaanshaha

Marka la dhammeeyo imtixaanada oo dhan, dukumeentiga soo socda ee aqbalitaanka waa in la diyaariyaa: warbixinaha tijaabada (ay ku jiraan natiijooyinka tijaabada siidaynta qayb ahaan, In ka yar ama la mid ah 10 pC), diiwaanada rakibaadda, iyo xogta komishanka heerkulka xakamaynta.

dry type transformer test
tijaabada beddelka nooca qalalan
dry type transformer tests
imtixaanada transformer nooca qalalan

 

 

 


 

 

 

 

10. Adeegga iyo Hawlgalka

 

 

 

10.1 Taabo hagaajinta booska (aan ahayn -Farxiyo)

Transformers oo leh - beddelayaasha tuubada wareega (tusaale, qiimaynta danabka 10,000 V ± 2 × 2.5%):

Taabo Booska

Korontada soo saarta

2–3

10,500 V

3–4

10,250 V

4–5

10,000 V

5–6

9,750 V

6–7

9,500 V

Haddii danabka nidaamka korantada deegaanka uu yahay 10 kV, ku xidh tuubooyinka booska 4-5.

Haddii danabka sahaydu uu dhaafo 10,500 V, la qabso booska tuubada sare ka dib markaad ka baxdo danab sare.

Haddii danabka sahaydu uu ka hooseeyo 9,500 V, la qabso booska hoose ee tuubada ka dib markaad ka baxdo danab sare.

Dhammaan hagaajinta tuubada waa in la sameeyaa iyadoo korontadu ay go'an tahay.

10.2 Hawlgalka OLTC

Transformers-yada leh {{0}kumbuyuutarrada tabaha, tixraac qeexida OLTC ee gaarka ah. Transformer-ka waxa la gelin karaa adeega kaliya ka dib marka OLTC si sax ah loo hagaajiyo. Korontada ka saar ka hor inta aanad wax hagaajin ah samayn.

10.3 Xakamaynta heerkulka iyo Muujinta

Transformers oo ku qalabaysan heerkul-kooreyaal iyo bandhigyada heerkulka:

Marka hore tamar geliya transformerka,kadibna xoog ku qaboojiyaha heerkulka oo soo bandhig.

Ku habbee qalabka sida waafaqsan tilmaamaha heerkulka heerkulka u dhigma.

10.4 Tamarta bilowga ah

Ha samayn -jabka rarka{1}} xidhitaanka hawlgallada Jadwalka ugu sarreeya - xidhidhiyaha degdega ah ee hadda ugu sarreeya waxa laga yaabaa inuu gaadho 8-10 jeer inta hadda la qiimeeyay-tani waa caadi.

Si tartiib tartiib ah u kordhi culeyska yar ilaa weyn inta aad la socoto dhawaaqyada aan caadiga ahayn.

10.5 Maya -Hawlgalka Xamuulka

Ma jiro{0}}Hawl galka xamuulku waa inuu u hoggaansamaa IEC 905Xeerka Qalalan{0}Nooca Awood beddelayaasha. Hawlgalka culeyska xad dhaafka ah ee muddada gaaban waa la oggol yahay iyadoo lagu salaynayo heerkulka jawiga iyo xaaladaha culeyska bilowga ah.

10.6 Awoodda culeyska xad dhaafka ah

Marka heerkulka deegaanku uu ka hooseeyo qiimaha la qiimeeyay, awoodda wax-soo-saarku si la qiyaasi karo ayay uga sarraysaa qiyamka la qiimeeyay, iyo lidkeeda.

Awooda culayska badan ee nooca qalalan{0}noocku waxay ku xidhan tahay heerkulka deegaanka, xaaladaha rarka hore{1}, sifooyinka kulaylka dahaarka, iyo wakhtiga kulaylka joogtada ah. Curyaaminta xad-dhaafka ah waa in laga helaa soo saaraha codsiyada gaarka ah.

10.7 Shuruudaha Hawlgalka ee Gaarka ah

Nooca qalalan{0}Transformers waxa la gelin karaa adeega isla markiiba ka dib tamarta bilowga ah iyada oo aan la daaweyn gaar ah.

Si kastaba ha ahaatee, haddii transformer-ku uu ku shaqaynayay hawo qoyan ama ay muujiso calaamado uumi/baraxan, daawaynta qalajinta waa in la sameeyaa ka hor qaliinka xiga.

10.8 Habka Tamarta Koowaad

Ha samayn -tamar qaadis saddex jeer, iyadoo 5-daqiiqo u dhaxayso hawlgal kasta, oo la soco qulqulka hadda.

Ku shaqee wax ka yar ama la mid ah 30% 24 saacadood si aad u xaqiijiso waxqabadka.

Kor u kaca heerkulka dabayshu waa inaanu ka badnayn 100 K dahaarka heerka F.

 

 


 

 

 

 

11. Dayactirka

 

 

 

11.1 Inta jeer ee Kormeerka

Deegaanka

Inta jeer ee Kormeerka

Nadiifi, deegaan engegan

Sanadkii hal mar

Deegaanka wasakhaysan

3-6 bilood kasta

Transformers-yada cusub ee shaqada loo dhiibay waa in ay helaan kormeerkooda ugu horreeya 2-3 bilood ka dib marka ay shaqeeyaan, kadibna ay ku xigto kormeero dhammaystiran oo sannadle ah ka dib. Dib-u-habeeyn dhamaystiran ayaa lagu talinayaa 3-5 sano kasta, ama sida ay ku taliyaan soo saaraha iyadoo lagu saleynayo xaaladda qalabka.

11.2 Nadiifinta

Hubi oo nadiifi boodhka urursan si aad u hubiso hawo habboon oo aad uga hortagto burburka dahaarka.

Fiiro gaar ah u yeelo dahaadhiyeyaasha iyo baloogyada suufka hoose.

Isticmaal hawo qallalan oo ciriiri ah si aad u afuufiso tuubooyinka iyo tuubooyinka qaboojinta (cadaadiska hawada oo cadaadisay In ka yar ama la mid ah 0.2 MPa).

11.3 Kormeerka Muuqaalka

Hubi waxyaabaha soo socda inta lagu jiro kormeer kasta:

Xidhiidhiyayaasha, xidhayaasha, iyo qaybaha kirishbooyada ee miridhku ama daxalka.

Sagxadaha dahaadhan ee calamadaha gurguurta iyo kaarboonaynta.

Kaalmee dahayeyaasha dildilaaca ama calaamadaha dheecaanka.

Taageerada qaboojinta ee hawlgalka caadiga ah.

Isku xirka tamarta sare iyo hoose ee calaamadaha kulaylka.

Xudunta iyo dabaysha ee midabka, ur, ama cilladaha kale ee aan caadiga ahayn.

11.4 Tijaabada Dahaarka Xiliga ah

Inta lagu jiro dayactirka la qorsheeyay (qiyaastii shantii sanaba mar), cabbir caabbinta dahaarka si waafaqsan Qaybaha 9.4 iyo 9.5 si loo go'aamiyo in qalabku sii wadi karo adeegga. Tijaabada caabbinta dahaarka joogtada ah ayaa sidoo kale lagu talinayaa 6-12 biloodba mar.

dry type transformer cleaning
Nadiifinta beddelka nooca qalalan
dry type transformer manufacturing
wax soo saarka transformer nooca qalalan

 


 

 

 

 

 

12. Rakibaadaha Transformer ee La Xidhiidha & Tilmaamaha Hawlgalka

 

 

 

Transformers nooca qallalan waxaa badanaa lagu isticmaalaa gudaha gudaha iyo meelaha qoyaanka leh. Wixii bannaanka, saliidda ka buuxo, ama codsiyada tiirarka ku rakiban, fadlan tixraac soo socda hagayaasha rakibidda iyo hawlgalka dhammaystirka ah.

 

 

 


 

 

 

 

13. Taxadirka Badbaadada

 

 

 

12.1 Gelitaanka iyo Ilaalinta

Transformers-ka ku shaqeeya bilaa xero waa in lagu rakibaa deyrar ilaalin gaar ah ama waardiye si looga hortago shilalka aan badbaadada lahayn.

Qalabyada dibadda ama nus-maskaxda ah{0}kumbuyuutarrada dibadda, dariiqyada ilaalinta go'an ee dhererkoodu yahay ugu yaraan 1.5 mitir waa in lagu bixiyaa agagaarka transformerka, iyada oo ugu yaraan 0.5 mitir u dhexaysa dulmarta beddelka iyo tareenka.

12.2 Ficilada Mamnuucay

Qofna ma taaban karo transformerka inta uu tamar ku jiro.Dhammaan shaqada korantada waa in lagu sameeyaa tamar-malaha si sax ah -tamar la dejiyay, la xiray, oo la calaamadeeyay

12.3 Shaqaale Tayo leh

Dhammaan tijaabooyinka, hubinta dahaarka, iyo shaqada dayactirka ee transformerka waa in ay sameeyaan xirfadlayaal koronto u tababaran oo aqoon u leh.

12.4 U Diyaargarowga Gargaarka Koowaad

Qorshaha jawaabta degdegga ah, oo ay ku jiraan hababka gargaarka degdegga ah ee shoogga korantada, waa in la sameeyaa oo shaqaalaha loo tababaraa si ku habboon.

 

 

U dir sooji