Hagaha Delta iyo Wye Transformer Connections

May 08, 2026

Fariin ku dhaaftid

delta and wye connection

 

 

 

 

1. Hordhac

 

 

Saddex -Nidaamyada qaybinta korantada weji waxay si aad ah ugu tiirsan yihiin laba nooc oo isku xidhka is beddelka aasaasiga ah: Delta (Δ) iyo Wye (Y). Nidaamyadani waxay go'aamiyaan sida loo bixiyo tamarta iyo qulqulka, sida rarka la isugu xiri karo, iyo sida nidaamku uga jawaabo cilladaha iyo dheellitirka. FahamkaIsku xirka Delta iyo Wyewaxay lama huraan u tahay injineerada korantada, maamulayaasha xarunta, iyo farsamayaqaanada naqshadeeya, shaqeeya, ama ilaaliya nidaamyada korantada.

Hagahan waxa uu daboolayaa sifooyinka, faa'iidooyinka, xaddidaadaha, iyo codsiyada la taaban karo ee nooc kasta oo isku xidhka ah, oo ay weheliso qaabaynta isku dhafan ee ugu caansan iyo shuruudaha xulashada.

 

 


 

 

 

2. Fahamka Delta iyo Wye Connections

 

 

 

Wye Connection

2.1 Wye Connection

Xidhiidhka Wye (ama Xiddigga), hal daraf mid kasta oo ka mid ah saddexda dabaysha beddelka ayaa ku xidhan barta dhexe ee guud ee loo yaqaan dhexdhexaadka. Darafyada kale waxay ku xidhmaan saddexda weji, iyagoo samaynaya qaab u eg xarafka "Y". Isku xidhkani waxa uu abuuraa afar -nidaamka siligga{3}}saddex weji kirishtaan iyo daawadeen dhexdhexaad ah.

Barta dhexdhexaadka ah waxay bixisaa laba heer oo danab oo kala duwan: xariiq -ila- khadka laydhka (caadi ahaan ka sarreeya) iyo xariiq -ila- danab dhexdhexaad ah (hoose). Tusaale ahaan, nidaamka 480Y/277V wye waxa uu bixiyaa 480V inta u dhaxaysa wejiyada saddex{8}}qalabka wejiga iyo 277V laga bilaabo weji kasta ilaa dhexdhexaad hal{10} culayska wejiga. Xidhiidhka xisaabta waxa lagu tilmaamay sidainfo-243-47, taasoo la micno ah danab xariiqda waa ku dhawaad ​​1.732 jeer danab wajiga.

Xidhiidhada Wye waxa kale oo ay ogoladaan dejinta barta dhexdhexaadka ah, kaas oo dejiya tixraac danab deggan oo abuura - dariiqa soo celinta caqabada hoose ee qulqulka cilada Dhexdhexaadku wuxuu noqon karaa mid si adag loo qotomiyey, lagu dhejiyay iyada oo loo marayo resistor, ama bidix sabaynaysa iyadoo ku xidhan shuruudaha nidaamka. Si kastaba ha ahaatee, haddii dhexdhexaadka laga tago iyada oo aan dhulka la dhigin ama uu go'o, dulqaadka ciladuhu si weyn ayuu hoos ugu dhacayaa oo korantada lama filaanka ah waxay dhaawici kartaa qalabka.

 

 

2.2 Isku xirka Delta

 

Xidhiidhka Delta waxa uu ku biiraa dhammanta beddelka beddelka kasta{0}}ilaa{1}}dhamaadka si uu u sameeyo wareeg saddex xagal xidhan. gees kasta oo ka mid ah saddexagalka wuxuu u adeegaa sidii barta isku xirka hal xariiq oo weji ah. Si ka duwan nidaamka Wye, Delta ma laha meel dhex dhexaad ah-waa saddex-nidaamka siligga oo leh kaliya saddexda weji kirishtaan.

Delta Connection

Qaabeynta Delta, korantada xariiqdu waxay la mid tahay korantada wejiga ee wareeg kasta, halka hadda xariiqda loo qaybiyo sida dabaysha weji kasta ay qaado qiyaastii 58% (info-80-44) ee xariiqda hadda jirta. Naqshadaynta xidhan-Naqshadda loop-ku waxay bixisa wareeg xoogan oo hadda jira iyo wax qabad heersare ah oo ka hooseeya culeysyo culus. Xataa haddii hal - unug weji ah oo ku yaal bangiga Delta uu guuldareysto, labada soo haray waxay sii wadi karaan bixinta saddex{4}}awood weji qiyaastii 58% awoodda asalka ah-oo badiyaa loo yaqaan "furan-delta".

Maqnaanshaha barta dhexdhexaadka ah waxay fududaynaysaa {{0}koronta sadexaad- gaarsiinta weji sare laakiin waxay soo rogtaa xaddidaadyo: Xidhiidhada Delta ma bixin karaan hal - culeyska wejiga si toos ah iyada oo aan qalab dheeraad ah la helin, iyo dhul dhigistu waxay u baahan tahay habab gaar ah sababtoo ah dhexdhexaad dabiici ah ma jiro.

 

 


 

 

 

3. Kala duwanaanshiyaha muhiimka ah marka la eego

 

 

Muuqaal

Delta (Δ)

Wye (Y)

Habaynta

Loop saddex xagal xiran

Qaabka xiddiga oo leh dhexdhexaad dhexe

Fiilooyinka

3-nidaamka siliga (wajiyada kaliya)

4-nidaamka silig (+ dhexdhexaad ah)

Xiriirka Voltage

info-173-43

info-243-47

Bar dhexdhexaad ah

Midna ma jiro

La heli karo (waxaa lagu saleyn karaa)

Hal -Awoodda wejiga

Si toos ah uma keeni karo culayska weji keliya{{0}

Laba danab oo hal -waji iyo saddex{1}} ah

Yaraynta harmonic

Dabinnada harmonics saddex laabma gudaha

Aad u nugul (waxay u baahan tahay dhimis)

Dulqaadka qaladka

Sii wad furnaanta-delta ka dib markii hal gariiradku guuldareysto

Waxay ku xiran tahay qaabeynta dhulka dhexdhexaadka ah

Codsiyada caadiga ah

Sare - gudbinta korantada, matoorada warshadaha culus

Nidaamyada qaybinta, isku qasan{0} isticmaalka dhismayaasha, goobaha ganacsiga

 

Jadwalku waxa uu tusinayaa in Delta ay mudnaan siiso adkaanta iyo hufnaanta sadexda culays ee culus - culayska wejiga, halka Wye uu bixiyo kala duwanaansho iyo salid badbaado leh nidaamyada leh noocyada rarka isku dhafan.

 

 


 

 

 

4. Isku-habaynta Transformer

 

 

Transformers-ku waxay isku dari karaan Delta iyo Wye dabaylohooda aasaasiga ah iyo kan sare ee afar hab oo caadi ah. Nooca dabaysha aasaasiga ah ayaa marka hore la taxay (dhinaca H, xaraf weyn), oo ay ku xigto nooca dabaysha labaad (dhinaca X, farmaajo hoose).

 

 

4.1 Delta-Wye (Δ-Y)

 

 

Kani waa isku xirka sadexda weji ee inta badan la isticmaalo- Midda kowaad waa Delta{{2}la habeeyey, halka ka labaadna uu isticmaalo xidhiidhka Wye, sida caadiga ah dhex-dhexaadka ah.

Waa maxay sababta ay caan u tahay:Aasaaska Delta waxa uu ka go'doomiyay nidaamka korka ee dheeli tir la'aanta hoose iyo iswaafajinta. Dhaqdhaqaaq kasta oo dhexdhexaad ah oo uu dhaliyo hal aan dheeli tirnayn{1} culayska wejiga ee dhinaca labaad waxa uu ku wareegaa dabaylaha Delta halkii uu ku noqon lahaa isha koowaad. Tani waxa ay abuurtaa xuduud koronto oo nadiif ah{3}}korka sare waxa uu arkayaa saddex dheeli tiran-nidaamka siligga, halka qulqulka hoose uu xamili karo hal isku dhaf ah-waji iyo saddex- culaysyo weji leh oo dhexdhexaad ah.

Codsiyada caadiga ah:Qaybaha utility hoos u dhigaya danab gudbinta (13.8 kV, 34.5 kV) ilaa heerarka qaybinta (208Y/120V, 480Y/277V); dhismayaal ganacsi oo u baahan labadooduba saddex{6}}Korantada mootooyinka wejiga ah iyo nalka 120V; dhirta warshadaha quudinta darfaha qaybinta sare; iyo xarumaha xogta u baahan helitaan dhexdhexaad ah oo xasilan oo loogu talagalay qalabka IT. Dugsiga sare ee 208Y/120V wuxuu ku dhow yahay meel walba meelaha ganacsiga ee Waqooyiga Ameerika.

Faa'iidooyinka:

  • Waxay siisaa dhexdhexaad sal leh oo badbaado leh oo hal - raran ah
  • Waxa uu ka soocaa nidaamka aasaasiga ah ee is-waafajinta sare (triplen harmonics ku xayiran Delta)
  • Waxay si wax ku ool ah u xakameysaa culeysyada aan dheeli tirnayn iyadoon wax la taaban karin
  • Wuxuu sahla talaabada wax ku oolka ah - hoos u dhigida tamarta

Xaddid:Waxay soo bandhigaysaa isbeddelka wejiga 30-degree ee u dhexeeya danabyada aasaasiga ah iyo kuwa sare (hoos ayaa lagaga doodayaa), kaas oo ay tahay in la tixgeliyo marka la barbar dhigo transformers. Sidoo kale, hordhaca Delta ma bixin karaan dhexdhexaad nidaamyada korka.

Dyn1

4.2 Wye -Delta (Y-Δ)

 

 

Dugsiga hoose ee Wye iyo heerka sare ee Delta, isku xidhka waxa badanaa loo isticmaalaa jaranjarada{0}}hoos u dhaca arjiyada halka hoose u baahan yahay xidhiidh dhexdhexaad ah, ama talaabooyinka{1}}kor u kaca arjiyada marka la rogayo isbedbedelka.

Codsiyada:Tan waxa laga heli karaa -talaabada saamiga{1} hoos u dhaca xaaladaha isbedbedelka si loo quudiyo rarka matoorada warshadaha ama gudaha wareegyada mootooyinka ee matoorada waaweyn. Codsiyada bilawga mootada, Dabagaalaha waaweyn{3}}matoorada qafiska ayaa mararka qaarkood lagu xidhaa Wye si loo bilaabo (yaraynta qulqulka hadda ilaa qiyaas ahaan hal-saddex meelood ee caadiga ah) ka dibna loo beddelo Delta si uu u ordo, taas oo inta badan loo yaqaan "Wye-Delta ama Star{{6}Delta starter".

Faa'iidooyinka:

  • Primary Wye wuxuu bixiyaa bar dhex dhexaad ah oo dhulka korka ah haddii la rabo
  • Delta Secondary waxay bixisaa faa'iidooyin la mid ah kuwa Delta-saddex adag-wax soo saarka wejiga, dulqaadka cilada leh ee furan{2}}karti delta, iyo go'doomin iswada leh oo saddex jibaaran
  • U fiican arjiyada u baahan hir bilawga sare ama nadiifinta saddexda weji - bilaa dhexdhexaad ah

Xaddid:Delta labaad si toos ah uma keeni karto culayska weji keliya iyada oo aan qalab dheeraad ah la helin. Isku-dheellitirka culeyska dhexdhexaadnimada aasaasiga ah marka la quudinayo dugsiga sare ee Delta waxay noqon kartaa mid adag.

Yd±15°,Yd11

4.3 Delta-Delta (Δ-Δ)

 

 

Labada hoose iyo kuwa sare ee Delta, isku xidhkani waxa uu bixiyaa saddex{0}waxqabad waji leh oo adag iyo awooda lagu sii wado ku shaqaynta furan{1}}qaabka delta ee awooda la dhimay haddii hal gariirad ku guuldareysto. Aad bay ugu habboon tahay-kuwa hooseeya-voltage, sare-arjiyada hadda jira halka sadex- culayska wejigu badan yahay oo baahida dhexdhexaadnimadu ay tahay mid aad u yar, sida culayska matoorka warshadaha iyo qalabka alxanka. Si kastaba ha ahaatee, ma bixiso xidhiidh dhexdhexaad ah labada dhinac, sidaas darteed si toos ah uguma adeegi karo hal - xariiq weji - ilaa - culaysyo dhexdhexaad ah.

Dd0

 

4.4 Wye-Wye (Y-Y)

 

 

Wye - Wye waa qaabaynta ugu dhaqaalaha badan, oo bixisa dhibco dhexdhexaad ah labada dhinac mana jiro isbeddel weji ah oo u dhexeeya danab hoose iyo sare, kaas oo fududeeya isbarbardhigga transformers badan. Waxay si fiican ugu shaqeysaa culeysyada dheellitiran iyo nidaamyada u baahan dhexdhexaadinta kor iyo hoosba. Si kastaba ha ahaatee, Wye{{3}Transformers Wye aad bay ugu nugul yihiin arrimaha iswaafajinta ilaa dhexdhexaadka aasaasiga ah aan si adag loo qotomin ama lagu darin dabaylaha Delta. Isku dheellitirnaanta culeyska taxaddarka leh ayaa loo baahan yahay si looga hortago culeyska dhexdhexaadka ah ee culeyska hal waji oo aan dheeli tirnayn-

Yy0y6

YNyn0


 

 

 

5. Voltage iyo Xiriirka Hadda

 

 

Xisaabinta saamiga leexashadu way kala duwan yihiin iyadoo ku xidhan qaabaynta:

Delta-Wye (Δ-Y):Talaabada -hoos udhaca delta-wye transformer oo leh saamiga rogrogmada N (guud ilaa sare ee gariiraddaba), korantada laynka sare waainfo-510-48. Taa beddelkeeda, xisaabinta waxaa ku jira ainfo-36-44arrin ay sabab u tahay beddelka laga soo bilaabo danab khadka Delta oo loo beddelay khadka Wye-oo loo beddelay{1}} danab dhexdhexaad ah.

Wye-Delta (Y-Δ):Wixii wye{0}}Transformer-ka delta, korantada xariiqda sare waxa ay la xiriirtaa tamarta wejiga koowaad ee saamiga leexashada, laakiin dheeraad ahinfo-36-44Xidhiidhku wuu khuseeyaa iyadoo ku xidhan haddii aad xilka ka degayso ama kor u kacayso.

Delta-Delta (Δ-Δ) iyo Wye{2}}Wye (Y-Y):Isku xidhka {{0}isku xidhka isku xidhka, beddelka danabku wuxuu raacayaa saamiga leexashada fudud:info-571-43, oo leh danabyada xariiqda si toos ah u miisaamaya.

 

 


 

 

 

6. Tixgelinta Aasaaska

 

 

Dhul-ku-dhigiddu waa qodobka keliya ee ugu muhiimsan ee la taaban karo marka la dooranayo inta u dhaxaysa Delta iyo Wye.

Wye Grounding Options:Marka dhexdhexaadka Wye uu joogo, wuxuu noqon karaa midkood:

  • Si adag loo saleeyay:Si toos ah ugu xidhan dhulka (inta badan waxa loo yaqaan danab ka hooseeya 600V). Tani waxay ku siinaysaa dariiqa soo celinta cilladda impedance ee ugu hooseysa.
  • Iska caabinta ayaa salka ku haysa:Dhexdhexaad ku xiran dhulka iyada oo loo marayo resistor kaas oo xaddidaya cilada dhulka hadda qiimaha la sii go'aamiyay, sida caadiga ah 5-400 amperes. Tani waxay yaraynaysaa burburka inta lagu jiro cilladaha iyadoo weli bixinaysa dareenka gudbinta.
  • Aasaas la'aan ama falcelin ku salaysan:Dhexdhexaadku waa ka go'doonsan yahay dhulka ama wuxuu ku xiran yahay reactor. Ku yar nidaamka deegaanka casriga ah ama nidaamyada ganacsiga laakiin laga helo xarumaha warshadaha qaarkood ama nidaamyada aasaasiga ah ee iska caabbinta sare -

Marka la beddelo qaabaynta, go'aanka lagu qotominayo dhexdhexaadnimada xidhiidhka Wye wuxuu si toos ah u saameeyaa doorashada beddelkayaal iman kara, xirayaasha qalliinka, baadiyaha, iyo qaybaha kale. Nidaamyada Wye ee salka ku haya, qaybaha waxaa lagu doortaa iyadoo lagu salaynayo wejiga{1}}ilaa{2}}koronta dhulka. Nidaamyada aan dhulka lahayn, qaybaha waa in lagu qiimeeyaa wejiga{4}}ilaa{5}}

Caqabadaha Grounding Delta:Meel dhexdhexaad ah la'aanteed, nidaamyada Delta looma saldhigi karo si la mid ah nidaamyada Wye. Halkii:

  • Dhulka geesta:Hal weji kaari waxa uu si ula kac ah ugu xidhan yahay dhulka-habka ugu fudud laakiin waxa uu ku abuuraa danab sare labada weji ee kale marka loo eego dhulka.
  • Xarunta - dejintii la taabtay:Qaybaha labaad ee Delta qaar ka mid ah, barta dhexe ee hal dabayshu waxay noqon kartaa xuddun - la taabtay oo la dejiyay si loo bixiyo awood xaddidan oo hal -waji ah, sida 240/120V saddex- waji afraad -Nidaamka silig delta (sidoo kale loo yaqaan "sare-lugta delta").
  • Transformers dhulka hoostiisa: A Zig-zagama Wye-Transformer-ka dhulka la dhigo Delta ayaa lagu dari karaa si loo abuuro dhex dhexaad macmal ah oo lagu dejiyo nidaamka Delta aan dhulka lahayn ee jira.

ZN

Xusuusin Badbaadada Muhiimka ah:Dhexdhexaadinta Wye ee si adag u dhisan waxa ay bixisa - dariiqa wax u dhimi kara qulqulka cilada dhulka, taas oo u ogolaanaysa fiyuusyada wareegyada iyo fiyuusyada in ay si dhakhso ah u nadiifiyaan khaladaadka. Tani waa sababta ugu weyn ee Wye Secondary loogu doorbiday dhismayaasha ganacsiga, tas-hiilaadka daryeelka caafimaadka, iyo goobaha kale ee nadiifinta khaladaadka iyo badbaadada shaqaaluhu ay ugu muhiimsan yihiin.

 

 


 

 

 

 

7. Wajiga Shift ee Delta{1}}Wye iyo Wye{2}}Transformers Delta

 

 

Nuance farsamo oo muhiim ah: gudaha Delta-Wye iyo Wye-Transformers Delta, tamarta hoose iyo tan sare waxay si dabiici ah u beddeshaa 30 darajo. Isbedelka wejigani kuma dhaco dabaylaha laftooda ee waa sida dabayshu isugu xidhan yihiin. Gaar ahaan, xariiqda -ilaa{6}}koronta xariiqda dhanka Wye waxa loo raray 30 darajo marka loo eego xariiqda-oo loo jeediyo{9}}koronta khadka dhinaca Delta.

Ogeysiiska Saacadda (Kooxaha Vector):Xidhiidhada beddelka ayaa inta badan lagu calaamadeeyaa iyadoo la isticmaalayo calaamadaynta saacada si loo muujiyo marxaladda wareejinta{0} tusaale ahaan, "Dy11" macneheedu waa Delta primary (D), Wye secondary (y), oo leh marxalad wareeg ah oo u dhiganta 11 saacadood saacadii, ama 330 darajo (oo u dhiganta -30 darajo). "Yd1" macneheedu waxa weeye in dugsiga sare uu ka dhigan yahay 30 darajo.

Waa maxay sababta isbeddelka wajigu muhiim u yahay:Isbedelka wejiga 30-degree maaha arrin ku jirta rakibaadda intooda badan, laakiin waxay noqotaa mid muhiim ah marka la barbar dhigo qalabka wax beddelka. Haddii laba transformers oo leh kooxo kala duwani ay si isbarbar-dhig ah isugu xiran yihiin, qulqulo waaweyn oo wareegaya ayaa dhalin kara. Marka la isku xidho transformers is barbar socda, kooxda vector waa in ay iswaafajiyaan ama si sax ah loo magdhabaa. Tusaale ahaan, Dy11 mararka qaarkood waxa lala barbar-dhigi karaa Yd1 haddii isbeddelka wareegga wareegga ku habboon la sameeyo.

Isbedelka wajigu waa maqan yahaygudaha Delta-Delta iyo Wye-Xiriirka Wye, kaas oo fududeeya isbarbardhiga.

 


 

 

 

8. Tixgelinta Wadaagga

 

 

Dabaylaha Delta waxay door muhiim ah ka ciyaaraan xakamaynta qallooca iswaafajinta. Triplen harmonics (saddexaad, sagaalaad, shan iyo tobnaad, iwm.) si dabiici ah ayay u xayiran yihiin waxayna ku wareegaan dabaylaha Delta gudaheeda halkii ay ku faafin lahaayeen khadka sahayda. Sifadan ayaa ka dhigaysa Delta{3}}Delta iyo Delta-Qabaynta Wye si gaar ah wax ku ool ah si looga hortago qallooc ku yimaada rarka aan tooska ahayn ee saameeya nidaamyada korka

Wye- Transformers Wye aad bay ugu nugul yihiin gudbinta sawaxanka iswaafajinta ee u dhexeeya isha iyo rarka. Sababtan awgeed, marka xidhiidhka Wye -Wye loo baahan yahay sababo kale dartood, dabaysha sare ee Delta ayaa mararka qaarkood lagu daraa si loo siiyo harmonics-yada saddex-geesoodka ah waddo ay ku wareegaan.

 

 


 

 

 

 

9. Sida loo doorto qaabaynta saxda ah

 

 

Xulashada qaabeynta transformer-ka ugu fican ee codsi la siiyay waxay ku lug leedahay isu dheellitirnaanta dhowr arrimood:

9.1 Nooca Xamuulka iyo Kala Duwanaanshaha

Saddexda saafiga ah- culayska wejiga (matoorada waaweyn, qalabka warshadaha culus, alxanka) waxay si fiican ula shaqeeyaan qaab kasta, laakiin Delta{1}}Delta waxay bixisaa dulqaad adag oo khaladka ah iyo awooda ay ku sii wadato shaqada furan{2}}delta ka dib guuldarada. Culaysyo isku dhafan oo u baahan labada-waji iyo hal-awood weji waxaa sida ugu fiican u adeega Delta-qaabaynta Wye, kaas oo bixisa dhexdhexaad salka ku haya{{7} qayb qaybinta weji iyada oo ka soocan ta hoose ee dheelitir la'aanta sare.

9.2 Shuruudaha Dejinta

Haddii dhex-dhexaadnimo sal-dhig ahi ay muhiim u tahay ilaalinta nidaamka iyo nadiifinta khaladaadka, heerka labaad ee Wye ayaa lagama maarmaan ah. Delta{1}Wye waa doorashada dabeeciga ah ee nidaamyada qaybinta ee u baahan dhexdhexaad, salka ku haya dhinaca culayska. Haddi nidaamku aanu u baahnayn dhex dhexaad oo uu ku shaqayn karo dhulka aan dhulka lahayn ama geesta dhulka, Delta-Delta waxa laga yaabaa inay ku haboon tahay.

9.3 Mawduuca Harmonic

Nidaamyo leh - soo saara culeysyo (xawaaladaha soo noqnoqda ee kala duwan, sahayda korontada beddeleysa, nalka LED,xarunta xogtaqalabka) ka faa'iidayso iswaafajinta{0}}awoodda dabinka ee dabaylaha Delta. Delta-Wye ama Delta-Dhismaha Delta ayaa lagu talinayaa xaaladahan oo kale.

9.4 Shuruudaha Bilaabidda Matoorada Waaweyn

Matoorada waaweyn ee u baahan in la dhimo - bilawga korantada waxa laga yaabaa inay ku habboonaato Wye{1}}Qabaynta bilawga Delta, halkaasoo mootada laga bilaabo Wye si loo xaddido qulqulka hadda ka dibna u wareego Delta si uu u socdo.

9.5 Nidaamka Heerarka Voltage iyo Tallaabada -Kor ku lid ah. Tallaabada - Hoos

Delta-Wye waxaa caadi ahaan loo istcimaalaa tilaabada{1}} hoos u dhaca codsiyada laga bilaabo dhexdhexaadka{2}}qaybinta korantada ilaa hoose-isticmaalka Voltage Wye-Delta inta badan waxaa loo isticmaalaa in la qaado-sidoo kale, laakiin doorashada dhexdooda ayaa ku soo degi karta in dhex dhexaad looga baahan yahay dhinaca hoose ama sare.

9.6 Balaadhinta Mustaqbalka iyo Dib u Celinta

Delta-Qalabaynta Delta waxa ay ogolanaysaa in la furo{1}}delta kaabta{2}haddii mid ka mid ah taransfooriyaha bangiga uu ku guuldareysto, labada soo hadhay waxay sii wadi karaan bixinta ku dhawaad ​​58% ee sadexda weji- la qiimeeyay. Tani waxay noqon kartaa tixgelin muhiim ah xarumaha muhiimka ah.

 

 


 

 

 

10. Kooban

 

 

Isku xirka Delta iyo Wye mid walbaa wuxuu u adeegaa doorar kala duwan sadex-qaybinta awooda wejiga, iyo isku dhafka Delta{1}Qaabka qaabaynta Wye waa shaqada warshadaynta hoos u dhigista tamarta gudbinta ilaa heerar la isticmaali karo halka dhulka xasiloon iyo culaysyo isku dhafan loo baahan yahay. Delta way ka sarraysaa halka sadexda weji awoodeedu - gudbinta korantada iyo cilada loo dulqaadanayo ay ugu muhiimsan yihiin, xidhxidhan{4}}Nashqada loop waxa ay bixisa rar wadaag heersare ah, iyo maqnaanshaha dhex dhexaadnimadu maaha xadid. Wye wuu ka sarreeyaa halka wax-ku-oolnimada, hawlgalka salka ku haya, iyo hal isku qasan -waji lagu daray saddex{7}} culaysyo weji ah ayaa loo baahan yahay, iyadoo bixisa awoodaha korantada ee labada ah iyo tixraac dhexdhexaad ah oo deggan.

Meesha ugu badan ee kulanka labadan caalim waa Delta-Transformer-ka Wye: Aasaaska Delta waxa uu ka go'doomiyaa nidaamyada korka ee isudheellitir la'aanta hoose iyo iswaafajinta, halka Wye secondary uu bixiyo dhexdhexaad, dhexdhexaad ah oo dhab ah- culaysyada aduunka oo si naadir ah isu dheeli tiran. Fahamka goorta iyo sababta loo isticmaalo qaabayn kasta waxay u ogolaataa injineerada inay wanaajiyaan waxqabadka, u maareeyaan noocyada kala duwan ee xamuulka si wax ku ool ah, oo ay u xakameeyaan kharashaadka mashruuca. Markaad shaki gasho, dhammaan- tirada ku xeeran ee hoos u dhigida awooda isku dhafan{5}}ee isticmaalka xarumaha waa Delta-Wye, maadaama ay bixiso isku dheelitirnaanta ugu wanaagsan ee isku dheelitirnaanta, badbaadada, iyo waxqabadka.

 


 

 

 

11. Eray ku saabsan Badbaadada

 

 

Had iyo jeer u hoggaansan dhammaan xeerarka korantada ee khuseeya iyo heerarka badbaadada markaad la shaqaynayso transformers. Weligaa ha u qaadan in nidaamka la tamarsiiyay iyada oo aan la tijaabin. Ilaalinta qulqulka iyo dhulka oo si sax ah loo cabbiro ayaa lama huraan u ah hawlgal ammaan ah. Haddii aadan hubin dhinac kasta oo ku saabsan xulashada beddelka ama rakibidda, la tasho injineer koronto haysta ama xirfadle aqoon leh.

 