Rakibaadaha Transformer-ka ee Rakibaadda iyo Hagaha Hawlgalka

Apr 21, 2026

Fariin ku dhaaftid

Substation Transformer Installation and Operation Guide

 

 

 

1. Hordhac

 

 

Transformers Substation waa qaybo muhiim ah oo ka mid ah nidaamyada qaybinta korantada, loogu talagalay inay hoos u dhigaan heerarka korantada si looga faa'iidaysto badbaadada warshadaha, ganacsiga, iyo codsiyada guryaha. Transformers-yadan waxa loogu talagalay in lagu rakibo saddex -nidaamyada weji waxaana loo habayn karaa in gudaha iyo dibaddaba lagu dhejiyo suufka shubka ah, oo leh fiilooyin koronto oo sarreeya iyo - hooseya oo ka soo gala buushka qaybaha hawlgalka. Hagahan waxa uu xoojiyaa hab-dhaqanka ugu wanagsan ee ku rakibida, hawlgalka, iyo dayactirka saldhiga hoose{5}}nooca transformers.

Hagahan waxa loogu talagalay farsamayaqaannada karti u leh ee si fiican u yaqaana warshadaha{0}}la aqbalay{1}}iyo kuwa hooseeya{2}} dhaqamada iyo hababka hawlgalka badbaadada leh. Kaliya shaqaale u qalma waa in ay rakibaan, shaqeeyaan, ama adeegaan qalabkan. Farsamoyaqaannada aqoonta u leh waa in lagu tababaraa daryeelka iyo isticmaalka qalabka ilaalinta, oo ay ku jiraan dharka birta ah, muraayadaha badbaadada, gaashaanka wejiga, koofiyadaha adag, galoofyada caagga ah, dhejiska, iyo ulaha kulul-.

 

 


 

 

 

2. Macluumaadka Badbaadada

 

 

2.1 Heerarka Ammaanka iyo Xeerarka

  • IEEE C57.12.00- Shuruudaha guud ee qaybinta dareeraha- immersed, awoodda, iyo habaynta transformers.
  • IEEE C57.12.34- Shuruudaha suufka lagu rakibay, nooca-qayb-qaybinta, is-qaboojiye saddex waji qaybinta qaybinta (In ka yar ama la mid ah 10 MVA, HV In ka yar ama la mid ah 34.5 kV).
  • NEC Qodobka 450- Shuruudaha rakibidda iyo ilaalinta dabka ee transformers.
  • KDQ 480- Shuruudaha dhulka iyo isku xidhka.
  • OSHA 1910.269- Koronto-abuurista, gudbinta, iyo qaybinta; waxay u baahan tahay oo kaliya shaqaale aqoon u leh inay ku shaqeeyaan oo ay dayactiraan qalabka saldhigyada.
  • NFPA 70E (2024)- Flash flash iyo badbaadada korantada ee goobta shaqada.

 

2.2 Qeexitaannada Hadalka Khatarta

Erayga Calaamadaha Macnaha
KHATAR Xaalad khatar ah oo degdeg ah - haddii aan laga hortagin, waxay keeni doontaa dhimasho ama dhaawac halis ah.
DIGNIIN Xaalad khatar ah - haddii aan laga hortagin, waxay keeni kartaa dhimasho ama dhaawac halis ah.
KA DIGTOONOW Xaalad khatar ah - haddii aan laga hortagin, waxay keeni kartaa dhaawac fudud / dhexdhexaad ahamadhaawaca qalabka (laba heer).

 

2.3 Tilmaamaha Badbaadada Guud

  • Korontada halista ah waxay sababi doontaa dhimasho ama dhaawac shakhsiyeed oo daran. Raac dhammaan habraacyada badbaadada ee deegaanka la ansixiyay.
  • Kahor intaadan rakibin, shaqayn, ama ilaalin qalabka, akhri oo fahan buug-gacmeedka. Hawlgalka khaldan, maaraynta, ama dayactirka waxay sababi kartaa dhimasho, dhaawac, iyo waxyeelo qalab.
  • Qalabkani waamaahaloogu talagalay in lagu ilaaliyo nolosha aadanaha.
  • Qalabka awood qaybinta waa in si sax ah loogu doortaa arjiga oo ay ku rakibaan/u adeegaan shaqaale karti leh.

 

2.4 Kahortagnaanta Badbaadada Rakibaadda

  • Ka tamar ka dhig qalabka wax ku beddela ee meel fog ka hor inta aanad shaqada bilaabin.
  • Dhulka oo dhan wareegyada ka hor inta aadan samayn wax xiriir ah transformer.
  • Isticmaal bir-kulul si aad ugu shaqeysid qalabka wax-ka-qabashada beddelka. Hubi danabyada dhamaadka hawlgalka kadib.

 

 


 

 

 

 

3. Koritaanka iyo Kormeerka Hore

 

 

3.1 Warqadaha iyo Xaqiijinta

Markaad hesho transformer, soo aruuri dhammaan dukumeentiyada la xiriira rarida, oo ay ku jiraan dukumeentiyada rarida, sawirada, iyo xogta kale ee ku haboon dejinta iyo isticmaalka. Ka gudub{1}}ku hubso qalabka biilka rarista Xaqiiji in taraafikada taraafikada ay la jaanqaadaan sifooyinka dalabka, oo ay ku jiraan qiimaynta kVA, - sare iyo -qiimaynta korantada, iyo caqabada

 

3.2 Kormeerka Dibadda

Kahor intaadan dejin qalabka wax lagu beddelo, samee kormeer dhab ah:

  • Hubi in dhammaan qaybaha ku qoran biilka rarida ay joogaan.
  • Ka eeg bannaanka cutubka calaamadaha dhaawaca dibadda inta lagu jiro safarka.
  • Kormeer duubaha saamaynta haddii qalabaysan.
  • Hubi caddaynta daadinta dareeraha taangiga, valves, ama shirarka qaboojinta.
  • Iska hubi baadiyaha burburay.
  • Samee tijaabada cadaadiska haanta haddii cutubku uu eber ku akhriyo cabbirka cadaadiska.
  • Hubi in taraafikada magaca {{0} ay ku jirto KVA, sare -qiimaynta korantada, hoose -qiimaynta korantada, iyo impedance{3}}ku waafaqaan sifada dalabka.

Haddii wax burbur ah la ogaado ama la dareemo gabaabsi, u fiirso sharraxaad kooban oo ku saabsan biilka xamuulka. Transformers waxaa sida caadiga ah lagu raraa barta FOB ee wax soo saarka, waana mas'uuliyadda macmiilka inuu xareeyo cabasho ka dhan ah sidaha. Haddii transformer-ka lagu soo raray meesha FOB, ogeysii wakiilkaaga warshadda.

 

3.3 Xaqiijinta Cadaadiska

Cabirka cadaadiska taangiga waa inuu muujiyaa cadaadis togan ama taban marka la helo. Waqti ka dib, cadaadiska kor u kaca ama hoos u dhaca ayaa muujinaya in haanta si fiican loo xiray. Haddii cabirka cadaadiska uu muujiyo cadaadis eber ah oo joogto ah, taangiga waxaa laga yaabaa in uu dillaaco. Xaaladahan oo kale, isla markiiba ka hubi taangiga iyo valves-ka cadaadiska si ay u dillaacaan.

 

substation transformer sample diagram
jaantuska muunada transformer substation
substation transformer sample nameplate
saxanka muunadda beddelka substation-ka

 

 


 

 

 

 

4. Wax ka qabashada

 

 

4.1 Kor u qaadida iyo kaxaynta

Isticmaal wiish si aad kor ugu qaaddo transformers substation. Qaboojiyaha kor u qaadida waxaa lagu bixiyaa meel u dhow sare ee haanta transformerka{1}kuwani waa meelaha kaliya ee isku xidhka ee loo isticmaalo qaadista Ka qaadista transformerka meel kasta oo kale oo ku taal transformerka waa badbaado.

Shuruudaha qaadista furaha:

  • U ogolow in aan ka badnayn 15 digrii ka leexinta jihada toosan.
  • Xaglaha jiidaya fiilada waa in aanay ka badan 30 darajo toosan. Isticmaal baararka fidsan si aad kor ugu qaaddo dharbaaxayaasha si toos ah si aad u yareyso suurtagalnimada in haanta qallafsanto ama waxyeelo soo gaarto rinjiga.
  • Weligaa ha ku xidhin xarkaha wax qaadista mid ka mid ah xadhig qaadis mid kale. Hal suun ama silsilad waa in loo qoondeeyaa jillaab kasta.
  • Ha ku qaadin transformer-ka leh fargeeto sababtoo ah xasilinta miisaanka waxay keeni kartaa khatar badbaado leh.
  • Ha ku xidhin fiilooyinka wax qaadista hiitarka ama meelaha kale ee qalabka.
  • Hubi culayska taransfooriyaha sida ku cad warqadda magaca ka hor inta aanad qaadin.

 

4.2 Garaacista, Skidding, iyo Rollers

Haddii transformer-ka aan lagu qaadi karin wiish, waxa laga yaabaa in la dulmaro ama lagu dhaqaajiyo rollers:

  • Isticmaal kaliya suufka jackingka ee lagu siiyey haanta. Ha u isticmaalin radiatoor ama qayb kale oo ka mid ah taransfooriyaha si aad ugu xidho transformerka meesha, waayo taasi waxa ay u horseedi kartaa dhaawac joogto ah oo soo gaara transformerka iyo daadinta saliidda.
  • Hubi in ugu yaraan laba jaakooyin la isticmaalo iyo in laba geesood oo isku xiga la wada kiciyo isla mar ahaantaana si siman looga fogaanayo in saldhiga la dagaalamo.
  • Jaakooyinku waxa la dhigi karaa oo keliya cidhifyada saldhigga beddelka - waligaa ha hoos gelin shirarka qaboojiyaha, valves, ama qaybo bir ah.
  • Markaad isticmaalayso rollers, isticmaal inta ugu badan ee lagama maarmaanka ah si aad u qaybiso miisaanka si isku mid ah. Cabbirka giraangiraha waa inuu awoodaa inuu taageero miisaanka beddelka.
  • Si aad u jiiddo, ku dheji khadadka jiidida godadka saldhigga ee labada gees ee transformerka. Ha ku xidhin xadhkaha jiidaya samaynta ama qaybaha kale ee birta ah.

 

4.3 Tixgelinta Gaarka ah ee Maareynta

Taxadiro dheeri ah waa in la qaadaa marka la qabanayo transformers heerkulka jawiga ka hooseeya 0 darajo (32 darajo F). Xaaladahan oo kale, dareeraha dahaadhka ah ee beddelka ayaa laga yaabaa inay kordhiyeen viscosity, taas oo saamayn karta maaraynta iyo hawlgallada xiga.

 

substation transformer loading
ku shubista taransfooriyaha substation
substation transformer shipping
substation transformer maraakiibta

 

 


 

 

 

 

5. Tilmaamaha Kaydinta

 

 

5.1{1} Kaydinta Gaaban (90 maalmood ama ka yar)

Mar kasta oo ay suurtagal tahay, Transformer-ka waa in lagu kaydiyaa meesha uu joogto. Kaydinta muddada gaaban{1}

  • Ku kaydi transformers meel nadiif ah, engegan, oo ammaan ah.
  • Xarunta wax lagu kaydiyo waa in aanay yeelan isbeddello heerkul ah oo asal ah.
  • Ka hubi dareeraha dahaadhka ah ee xoogga dielectric.
  • Ku kaydi transformer-ka si siman, oo aan ka badnayn 4 darajo ee leexinta.
  • Transformer-ka waa in aan lagu kaydin iyadoo ay jiraan gaasas daxalaysa (tusaale, koloriin).

 

5.2{1} Kaydinta Muddada dheer (in ka badan 90 maalmood)

Kaydinta in ka badan 90 maalmood, samee kormeero xilliyeed si loo hubiyo in qalabku ku sii jiro xaalad wanaagsan:

  • Iska hubi daboolka ilaalinta ee duurka; ku beddelo haddii ay dhaawacmaan.
  • Diiwaangeli dareeraha - heerka iyo cadaadiska / akhrinta faakuumka.
  • Cabbir oo diiwaan geli heerkulka hawada deegaanka.
  • Unugyada buste nitrogen engegan leh, hubi oo beddel baakadaha qalajiyaha ee armaajooyinka kontoroolka iyo qolalka hawada laga soo saaro inta lagu jiro muddada dayactirka joogtada ah.

 

5.3 Taxaddar Kaydinta

  • Weligaa ha ku kaydin transformer-ka jaakadaha ama xannibaadda ku meel gaadhka ah.
  • Weligaa ha ku kaydin qalabka wax beddelka ah ee rollers-ka.
  • Waligaa ha ku kaydin substation meel u dhow meelaha qoyaanka sareeyo, heerka milixda, ama hawada wasakhaysan.
  • Dusha sare ee transformerka waa in laga ilaaliyaa miridhku iyo daxalka.
  • Radiyeeriyeyaasha la go'i karo ee goonida loo kaydiyay, furayaasha hiitarka waxaa lagu raraa koofiyadaha ilaalinta ku meel gaarka ah. Hubi in koofiyadahan ilaalinta la xidhay ka hor kaydinta. Waligaa ha ku kaydin shirarka hiitarka dhulka ama meelaha ay ka qoyan karaan.

Kahor intaadan taransfooriyaha u dhigin adeega kaydinta la dheereeyey ka dib, hubi marawaxada, alaarmiga iyo wareegyada xakamaynta, iyo xoogga dielectric ee dareeraha dahaadhka ah.

 


 

 

 

 

6. Rakibaadda

 

 

 

6.1 Goobta Rakibaadda iyo Aasaaska

Transformer-ku waa inuu ku yaal suuf shub ah oo awood ku filan leh si uu u taageero miisaanka unugga sida ku qoran warqadda magaca. Diyaarinta goobta saxda ah waxay lama huraan u tahay cimriga beddelka -si fiican{2}}goobta loo diyaariyey waxay kordhin kartaa cimriga transformerka ilaa 25%.

Shuruudaha rakibidda:

  • Suufku waa inuu ahaadaa mid siman, siman, fidsan, iyo cabbirka saxda ah si loo daboolo furitaanka qolka. Wax nusqaan ah looma ogola inta u dhaxaysa qaybta iyo suufka.
  • Transformer-ku waa in uu ku fadhiistaa si siman oo siman oo sariirta ah. Ku dhaji qalabka wax-ka-beddelka ee suufka.
  • Transformer-ka waa in lagu rakibaa si uusan u janjeerin wax ka badan 4 digrii. Marka la leexiyo in ka badan 4 digrii, fiyuusyada gudaha, fiyuusyada, furayaasha, xudunta, iyo gariiradaha waxaa laga yaabaa inaanay si buuxda ugu dhex milmin dareeraha dielectric, taasoo suurtogal ah inay keento cillad dielectric ah ama dhibaatooyinka qaboojinta taasoo horseedaysa kulayl iyo hoos u dhac nolosha adeegga ah.
  • Waa in ay jirtaa ugu yaraan 2 cagood (qiyaastii 600 mm) oo nadiifin ah oo ku wareegsan wareegga wareegga.
  • Ku rakibida gudaha, albaabbada hawada qolku waa inay ku yaalaan heer dabaq ah oo leh meelo laga baxo sida ugu macquulsan. Bixi qiyaastii 20 cagood oo laba jibbaaran midkiiba meesha laga soo galo iyo meesha laga baxo 1000 kVA ee awoodda beddelka. Haddii habka hawo-qaadista uu yahay mid la hagaajin karo, waa in si joogto ah loo furo si looga fogaado kulaylka inta lagu jiro qaladka hawlwadeenka.
  • Ku rakibida meelaha daxalka leh ee leh cusbada ama kiimikooyinka waa in laga fogaadaa, sababtoo ah kuwani waxay keenayaan hoos u dhaca rinjiga difaaca oo keena daxalka birta khafiifka ah.

Transformers-yadan waxaa loo dhisay inay ku shaqeeyaan meel sare ilaa 3300 cagood (qiyaastii 1000 mitir) celcelis ahaan 30 darajo iyo 40 digrii heerkulka deegaanka ugu badan, haddii aan si kale loo cayimin. La xidhiidh soo saaraha ka hor inta aanad ku shaqayn taransfooriyaha caadiga ah meelaha sare.

 

6.2 Dhulka

Si joogto ah u demi transformer-ka si waafaqsan halbeegyada maxaliga ah iyo kuwa qaranka. Dhulka iska caabinta oo hooseeya oo sugan oo waxtar leh ayaa muhiim u ah ilaalinta:

  • Ku xidh fiilada dhulka culus ee suufka dhulka ee ku yaal xagga hoose ee haanta.
  • Haddii beddelka loo qaabeeyey inuu ku shaqeeyo nidaam dhexdhexaad ah oo qotodheer, isku xirka dhexdhexaadku waa inuu ahaadaa mid adag oo joogto ah oo leh caabbinta ugu yar.
  • Hubi in - isku xidhka dhulka hoos u dhiga ee saxda ah la aasaasay mar walba.

OSHA 29 CFR 1910.269(l)(11) waxay u baahantahay in aan -hadda- qaadin qaybaha birta ah ee qalabka (sida kiisaska transformerka) in loola dhaqmo sidii tamar ku jirta tamarta ugu sareysa taas oo ay soo bandhigaan ilaa loo shaqeeyaha uu eego rakibaadda oo uu go'aamiyo in qaybahan si fiican loo qotomiyey ka hor intaanay shaqada bilaaban.

 

6.3 Sare{1}Xiriirka Voltage

Heer sare{0}Voltage ee qiimaynta 2.4kV iyo ka badan ayaa sida caadiga ah la soo dhex maraa gidaarka taangiga iyadoo la isticmaalayo resin epoxide ama bushings porcelain.

Shuruudaha isku xirka:

  • Isticmaal kaliya isku xirka dabacsan ee marinnada baadiyaha si aad uga hortagto rarka makaanikada ee xad dhaafka ah.
  • Weligaa ha u isticmaalin bushing sidii xubin dhismeed si aad u taageerto qaybaha kale ee hadda socda-
  • Xidhiidhada oo dhan waa in si habboon loo ruxruxo si looga fogaado kulaylka ama keenaya in xidhiidhku xumaado. Tixraac jaantusyada wareegyada soo saaraha ee qiimayaasha gaarka ah.
  • Hubi in sagxadaha isku xidha ee xidhidhiyayaashu ay xor ka yihiin burburka iyo burburka.
  • Ka fogow diiqada xad dhaafka ah ee cantilever ee culeyska culus ee fiilada oo sarreeya- iyo mid hooseeya{1} Cadaadiska cantilever-ka ee xad-dhaafka ah wuxuu u horseedi karaa shaqo-la'aanta baadiyaha iyo dareeraha dareeraha dielectric.
  • Xirayaasha hillaaca ee qiimeynta saxda ah waa inay ku yaalliin sida ugu dhow ee suurtogalka ah joojinta beddelka.

 

6.4 Hoose{1}Xiriirka Voltage

Xaaladaha intooda badan, cutubyada substation-ka ayaa lagu qalabayn doonaa meel-ka-baxyada. Ku xidh fiilooyinka xagga hoose ee baadiyahan si aad u yarayso walbahaarka cantilever ee waxyeelaya baadiyaha. Tirada isku xirayaasha dabacsan waa in lagu go'aamiyaa qiimeynta transformer-ka ee hadda, maaha in lagu qiimeeyo qiimeynta hadda ee baarka baska.

 

6.5 Shuruudaha Guud ee Xiriirinta

Dhammaan xidhiidhada waa in la sameeyaa iyada oo aan culays aan loo baahnayn la saarin meelaha baadiyaha ah. Qabanqaabiyeyaasha waa in si adag loogu xidhaa meesha oo si habboon loo taageero, iyada oo la siinayo gunnada ballaarinta iyo foosha. Xidhiidhada tuubada waa in la badalaa KALIYA marka labada sare -voltage and low-xadhkaha korantada gabi ahaanba la shidayo- Si badbaado leh u xaqiiji in aanay wax danab ahi ka jirin terminalka ka hor inta aanad sii wadin.

Transformers-ka ku qalabaysan looxyada terminaalka gudaha waxaa sida caadiga ah lagu raraa koronto sare oo ku xiran, ilaa si kale uu u cayimo macaamilka.

Marka xiriirada alaarmiga ama kontaroolada la keeno qalabyada transformer-ka, sanduuqa xiriirinta ayaa laga yaabaa in la bixiyo si loo fududeeyo joojinta fiilada macaamiisha ama marinka.

 

6.6 Dheecaan Dielectric

Transformer-ka si fiican ayaa loogu engejiyey warshadda waxaana lagu rariayaa dareere dahaaran (ama saliidda macdanta, dareeraha ester-ka dabiiciga ah, ama dielectric kale oo la ansixiyay) ilaa heerka saxda ah. Dheecaanka dielectric waa inuu lahaadaa ugu yaraan awoodda dielectric ee 30 kV marka cusub, la tijaabiyey si waafaqsan ASTM D-877.

Noocyada dareeraha dahaadhka ah ee sida caadiga ah loo isticmaalo waxaa ka mid ah:

  • Saliidda MacdantaSaliida isbedbedelka badan ee la isticmaalo, oo bixisa awood dielectric sare ah (30-50 kV) iyo kulaylka wanaagsan ee daadinta, laakiin leh olol sare iyo walaac deegaanka.
  • Dareeraha Ester-ka Dabiiciga ah: Qudaar -Dielectric ku salaysan noolaha, aan - sunta ah, iyo dabka - u adkaysta, bixiya dulqaadka qoyaanka sare iyo heerka oksaydhka oo gaabis ah.

Heerarka: heerkulka hawlgalka caadiga ah ee dareeraha dielectric guud ahaan waa 25 digrii. Iska ilaali tamarta heerkulka hooseeya halkaasoo heerka dareeruhu uu soo bandhigi karo qaybaha muhiimka ah ee gudaha. Ku shaqee cutubka oo kaliya gudaha qiimeynta lagu sheegay sariiradda magaca.

 

6.7 Cadaadiska Transformer

Transformer-ka waxa lagu soo raray cadaadis togan oo ku dhawaad ​​+2 ilaa +3 PSIG ee nitrogen qalalan ee warshadda heerka badda. Heerkulka iyo isbeddellada sare awgeed, cadaadisku aad ayuu u kala duwanaan karaa marka dhalmada.

Tixgelinta cadaadiska muhiimka ah:

  • Transformer-ka waa in lagu sii daayo jawiga ka hor inta aan la gelin adeegga kaliya marka cadaadiska xad dhaafka ah uu jiro.
  • Heerka saliidda ayaa hoos u dhici doona qiyaastii 1/2 inji 10 darajo kasta oo hoos u dhaca heerkulka -tani waxay badanaa keentaa faakuum yar oo taangiga waana caadi.
  • Ha u ogolaan haanta in ay dhaafto in ka badan 3 PSIG vacuum (negative 3 PSIG), maxaa yeelay taangiga wuu isbedeli doonaa. Ha u ogolaan taangiga in ka badan 5 cadaadiska PSIG. Qallooca taangiga wuxuu ka bilaabmaa cadaadiska 7 PSIG.
  • Ha ku darin nitrogen is beddelka qabow si aad dib ugu soo celiso cadaadis togan. Haddii sidaas la sameeyo waxay sababi kartaa cadaadis iyo dhaawac xad dhaaf ah{1} Cadaadiska heerkulka saliidda 25 darajo waa inuu ahaadaa inta u dhaxaysa 0.5 iyo +1.0 PSIG.

Markaad hawada ka baxayso cadaadiska beddelka, fur furaha cadaadiska cadaadiska. Keliya soo bixi transformer marka heerkulka saliidu uu yahay ku dhawaad ​​25 digrii . Ha qaadin muunadda saliidda marka cadaadiska beddelka uu ka hooseeyo 0 PSI.

 

 


 

 

 

 

7. Kahor{1}Kormeerida Tamarta iyo Tijaabada

 

 

Kahor intaadan tamarsiin isbedbedelka, kormeerka tamarta ka hor- waa in la dhammeeyaa. Kahor - kormeerida tamarta iyo imtixaanada waa in ay sameeyaan kaliya farsamoyaqaano shahaado haysta oo wata qalabka badbaadada iyo baadhista ku haboon.

 

7.1 Kormeerka iyo Imtixaanada loo baahan yahay

A. Tijaabada Beddelka Isbeddelka (TTR).Samee tijaabada saamiga si aad u xaqiijiso -ilaa{1}} saamiga dabaysha labaad Tijaabada TTR waxay ku siinaysaa tilmaanta caafimaadka transformerka iyadoo la eegayo saamiga ka leexashada dabaylaha sare-marka la barbar dhigo dabaylaha hoose-voltage Tani waxay muujin kartaa wareegyada furan ama - xidhiidhada iska caabinta sare.

B. Tijaabada iska caabinta dahaarka (Megger)Samee tijaabada dahaadhka 1000-volt si aad u cabbirto caabbinta dahaadhka u dhexeeya dabaylaha iyo dabaylaha kasta ilaa dhulka. Tijaabadani waa in la sameeyaa ka hor inta aan taransfooriyaha la gelin adeegga iyo waqtiyo kala duwan inta lagu jiro meertada nolosheeda. Xirmooyinka buushka waa inay nadiif ahaadaan oo engegaan baaritaanka ka hor, sababtoo ah qashinka iyo qoyaanku waxay saameyn karaan akhrinta.

C. Taabo Dejinta Beddelka: Hubi in beddelaha tuubada uu ku qotomo goobta korantada ee saxda ah iyo in furaha la dhigay uu si fiican u fadhiyo. Weligaa ha ku shaqayn beddelka tuubada tamarta leh.

D. Taxanaha/Multiple ama Delta/Wye Switch Settings: Haddii lagu qalabeeyo beddelka delta/wye, hubi in loo dhigay booska saxda ah. Labada shixnado waxa loogu talagalay de{1}}hawlgal tamar leh oo keliya.

E. Dejinta: Hubi in tafaftiruhu leeyahay xidhiidh hoose oo adag -

F. Xidhiidhada la xidhay: Hubi in dhammaan isku xidhka xidhxidhan ay ruxruxmeen si waafaqsan miiska maroodiga soo saaraha. Transformers-yada caadiga ah, xirmooyinka ku dhejinta buushka: 4-xajinta aluminiumka kabka bushku waxay u baahan yihiin 70-80 in-lb; laba - godka kaynta xajintu waxay u baahan yihiin 55–65 in -lb; Qalabka daboolka waa in lagu adkeeyaa ilaa 25 ft-lb.

G. Heerka dareeraha Dielectric: Hubi in is beddelka si sax ah loo buuxiyay adiga oo eegaya cabbirka heerka dareeraha ama cabbirka aragga. Tilmaamaha heerka dareeraha waa inuu u dhexeeyaa calaamadaha "Sare" iyo "Low" ee cabbirka. Transformers-ka aan lahayn heerka dareeraha ama cabbirka aragga, hubi heerka dareeraha adiga oo ka saaraya furka heerka 25 darajo. Ha ka bixin furka heerka saliidda marka saliidda beddelka ay ka sarreyso 40 digrii .

H. Transformers hadda: Haddii lagu qalabeeyo transformers-ka hadda jira (CT-yada), tiirarka CT-ga ee la xidhiidha waa in lagu xidhaa culeyska cabbiraadda ama gudbinta culeyska habboon. Haddi aanay CT-du ku xidhnayn culayska cabbiraadda, waa in si wadajir ah loo soo gaabiyaa oo dhulka la dhigaa ka hor inta aan tamar-is-beddelka samayn.

I. Xakamaynta Xakamaynta Qalabka: Xaqiiji in dhammaan fiilooyinka kontoroolka ay ku xiran yihiin oo shaqeynayaan.

J. Baadhista Cilada Gudaha (haddii qalabaysan yahay): Haddii koronto-bixiye uu leeyahay cillad gudaha ah (IFD), qufulka dhoofinta waa in meesha laga saaraa ka hor tamarta. U rog qufulka dhoofinta (qaybta bannaanka ee cas) 90 digrii saacad ka hor si aad meesha uga saarto.

K. Agabka: Xaqiiji shaqaynta dhammaan agabka la xidhiidha ama la'aanta, oo ay ku jiraan aaladaha cadaadiska cadaadiska, cabbirada heerkulka, cabbirada heerka dareeraha, iyo cadaadiska - cabbiraadaha vacuum.

L. Kormeerka Haamaha Dibadda: Hubi in daloosha gacan-ka-beddelka uu xiran yahay, iyo wax kasta oo daboolaya oo lagu rakibay. Hubi in daboolada godadku ay si adag u xidhmeen oo qalabkii cadaadiska mishiinka dib loo dajiyay.

M. Kormeerka nadiifinta: Hubi in dhammaan isku xirka khadka ay ilaaliyaan nadiifinta saxda ah heerar kasta oo lagu dabaqi karo.

N. Taageerayaasha: Haddii la qalabeeyo, hubi in taageerayaashu si xor ah u wareegayaan oo ay shaqaynayaan. Taageerayaasha, had iyo jeer xaqiiji ka hor tamarta inay si xor ah u miiqdaan.

O. Radiator Valves: Haddii lagu keeno hiitarka la go'i karo, hubi in dhammaan valves-ka raadiyaha ay furmeen wakhtiga hore{0}}tamarta. Ku guuldareysiga in la furo furayaasha waxay dhaawici doontaa kuleyliyaha

P. Buuxinta: Si fiican u nadiifi baadiyaha oo hubi inaysan jirin timo dildilaaca ama waxyeelo kale. Hubi in dusha sare ee lammaanuhu ay ka nadiif yihiin burburka iyo burburka.

 

7.2 Guud ahaan kahor- Badbaadada Tamarta

  • Ha kicin adigoon dhamaystirin-baaritaannada tamarta hore.
  • Ha kicin adiga oo aan nadiifin baadiyaha.
  • WALIGAA ha ku dhaqmin taransfoorka wax ka baxsan qiimeynta saxanka.
  • Hubi in heerkulka dareeraha dielectric-ku aanu ka hoosayn xadka u cayimay soo-saaraha ee hawlaha bilowga qabow (sida caadiga ah -20 darajo saliidda macdanta, 0 digrii R- Dheecaan temp, ama -10 digrii ee dareeraha ester-ka dabiiciga ah).

Haddii aad samaynayso Tijaabada Soo noqnoqoshada Aad u Hooseeyso (VLF), ha ka badin 115% danab beddelka magaca muddada 30 daqiiqo ah. Ha ku samayn tijaabada qalabka beddelka ee booska xidhan. Hubi in dadka xidhaya, haddii ay jiraan, ay go'an yihiin ka hor intaysan bilaabin baaritaanka.

 

substation transformer is undergoing testing
transformer-ka substation waxa uu ku socdaa tijaabo
The transformer has completed the test
Transformer-ku wuu dhammeeyey imtixaankii

 

 


 

 

 

 

8. Tamarta

 

 

8.1 Kahor{1} Jeegagaga Dambe ee Tamarta

Xaqiiji waxyaabaha soo socda ka hor tamarta:

  • Dhammaan xidhiidhada dibadda ayaa si sax ah loo sameeyay (wajalaynta isku xidhka bushings terminal, iwm.)
  • Dhammaan xidhidhisku waa cidhiidhi oo ammaan ah
  • Dhammaan wareegyada xiriirka kaabayasha ayaa shaqeeya
  • Ma jiraan wax caddaynaya qoyaanka
  • Dhammaan xidhidhka xidhani waa cidhiidhi
  • Ma jiro qalab ama shay kale oo lagaga tagay korka taransfooriyaha ama meel kasta oo xayndaab ah
  • Heerka dareeruhu waa sax
  • Transformer-ku waxa uu hayaa cadaadis togan
  • Awoodda dareeraha dahaadhka ah ee dareeraha ah ayaa buuxiya shuruudaha (ugu yaraan 26 kV, oo leh dareere cusub 30 kV ama ka weyn)
  • Isku xirka dhexdhexaadka ah iyo kan dhulka ayaa si sax ah loo sameeyay
  • Dhammaan daboolayaasha ilaalinta waa la xiray oo si adag ayaa loo xiray

 

8.2 Boostada{1} Xaqiijinta Tamarta

Kadib tamar siinta transformerka,laakin ka hor inta aan la shubin,xaqiiji waxyaabaha soo socda:

A. Xaqiijinta VoltageKahor inta aanad ku shubin qalabka wax-ka-beddelka, hubi in wax-soo-saarka danabka labaad uu sax yahay. Isticmaal voltmeter-ka AC si aad u cabbirto danabka oo aad u xaqiijiso inay ku raacsan tahay danabyada sare sida ku xusan tabeelka magaca.

B. Diidashada: Ku wareeg wareegga wareegga oo si taxadir leh u baadh wax kasta oo daadanaya. Haddi daloosho la helo, de{1}tamar geli transformerka oo isla markiiba wax ka qabso

C. HawlgalkaHubi ka dib marka la shubo in aanay jirin waxyaabo aan caadi ahayn oo la arkay sida qaylada xad dhaafka ah, gariirka, ama kulaylinta. Transformer-ku waxa uu soo saari doonaa qaylo dhaanta inta lagu jiro hawlgalka caadiga ah. Haddii dhawaaqyo xad dhaaf ah ama aan caadi ahayn la arko, isla markiiba baar.

D. Cabbiraadaha: Hubi in cabbirka heerka dareeraha iyo cabbiraadda heerkulku ay tilmaamayaan heerar sax ah iyo heerkul ku hoos jira.

E. Radiator ValvesTransformers-ka leh hiitarka la goyn karo, mar kale xaqiiji in dhammaan hiitarka hiitarka ay FURAN yihiin.

 

 


 

 

 

 

9. Hawlgalka

 

9.1 Xaaladaha Hawleed ee Caadiga ah

Transformers waa in lagu shaqeeyaa oo kaliya qiimeynta ku qeexan saxanka beddelka. Hawlgalka culeyska dheeriga ah ee raaga ayaa qiyaas ahaan gaabin doona nolosha adeegga la saadaaliyay ee saliidda macdanta{1}} transformer-ka buuxa.

Si joogto ah u baadh dhammaan cabirrada inta lagu jiro hawlgalka. Heerka dareeraha waa inuu ahaadaa mid caadi ah, iyadoo la tixgelinayo saameynta heerkulka. Cadaadis eber ah oo dheer ayaa muujin kara gaas soo daayo waana in la baaro. Heerkulka dareeraha ah waa inuusan ka sarreyn qiimaha naqshadeynta ee ku yaal sariirta iyo heerkulka deegaanka.

 

9.2 Beddelida Hawlaha

tap changers

Taabo Beddelayaasha: Tuubada -Beddeliyuhu waxa uu bixiyaa hab lagu beddelo saamiga korantada ee de{1}}Transformer tamar leh iyada oo aan la jebinin qalabka beddelka Waxa lagu maamulaa gacan wareeg ah. Ha ku shaqayn beddelka tuubada inta uu tamar ku jiro.

De-Hawlgalka Bedelka Tamarta Tamarta leh(Nooca Wareega):

Dib u celi furka qufulka si aad u nadiifiso saxanka tusmada.

Ka soo saar gacanta si aad u nadiifiso saxanka tusmada.

U rog gacanta ilaa meesha aad rabto. Tilmaamuhu waa inuu ku dhacaa booska saxanka tusmada.

Haddii suufka - sifo qufuli karo la isticmaalo, adkee furka qufulka ilaa uu ka soo baxayo, ka dibna ku xidh daloolka la bixiyey.

Beddelayaasha tuubada tooska ah, u soo jiid buro-bararka dibadda, u rog booska cusub, una ogolow inay si toos ah dib ugu dhacdo heerkeeda.

Raad Jebinta Wareegyada: Furayaashan waxa kaliya oo lagu shaqayn karaa in lagu xidho qalab toosan oo kulul -qalabka xadhkaha dibadda ee gacanka isha oo u rogaya booska "ON" ama "OFF". Marka heerkulka dareeraha dahaadhka ahi uu ka yar yahay -20 digrii ee saliidda beddelka caadiga ah ama in ka yar -10 digrii ee saliidda khudradda, hoos{4}} agabka raritaanka saliidda waa in aan loo isticmaalin samaynta ama jebin rarka. Taa baddalkeeda, ka tamar geli qalabka wax beddelka ({6}) ee isha fog ka hor inta aanad ka hoos shaqayn -qalabka rarka saliidda.

 

9.3 Korjoogteynta iyo Kormeerka Xiliga ah

Waa in la sameeyaa kormeer wakhtiyeedka ah inta uu ku shaqaynayo transformer-ka:

Kormeerka DibaddaMar mar hubi xaaladda rinjiga iyo dhammaynta, gaar ahaan marka ay la kulmaan xaaladaha jawiga xun. Haddii cimiladu dhacdo, si fiican u nadiifi haanta, ka tirtir wixii dareere ah ee daatay, oo ku celi rinji la oggolaaday. Marmar is baadho oo adkee dhammaan kala-goysyada xidhan oo hubi inay dillaacayaan.

Kormeerka Cabbirka: Si joogto ah u kormeer dhammaan cabirrada. Dukumeenti akhrinta oo ay ku jiraan heerkulka jawiga iyo culeyska beddelka.

Hawlaha Dayactirka Sannadlaha ahWaxyaabaha soo socda waa in la baaraa sanad walba:

  • Heerka dareeraha Dielectric: Hubi qiyaasta dareeraha dielectric. Haddii heerka uu ka hooseeyo magac ahaan, ka hubi calaamadaha daadinta.
  • Heerkulka dareeraha: Hubi cabbirka heerkulka dareeraha heerkulka sarreeya. Is barbar dhig heerkulka unugyo la mid ah.
  • BuuxintaKa hubi xaalada baadiyaha HV iyo LV wasakh, jajab, waxyeelo kulaylka, ama bilicda.
  • Valve Relief CadaadisHubi wasakhda, burburka, iyo hawlgalka saxda ah.
  • Qab-qablayaasha Hillaaca: Hubi burburka oo xaqiiji xidhiidhka dhulka oo sax ah.
  • Fiyuusyada iyo XidhiidhadaFiyuusyada bayoneetka, hubi joogitaanka dareeraha; isku xirka fiilada, hubi calaamadaha kulaylka.
lightning arrester

danab xidhe

LV bushing

LV kaynta

pressure relief valve

valve cadaadiska cadaadiska

thermometer

heerkulbeegga

pressure vacuum gauge

cadaadiska vacuum gauge

liquid level gauge

qiyaasta heerka dareeraha

 

 


 

 

 

 

10. Dayactirka

 

 

10.1 Tijaabooyin waqtiyeedka ah

Tijaabooyin iyo baaritaannada soo socda ayaa lagula talinayaa si loo joogteeyo transformer-ka substation:

  • Akhriska QiyaastaCabbir oo diiwaan geli akhrinta cabbirka, heerkulka jawiga, iyo culeyska beddelka bil ka dib tamarta ka dibna sannad kasta ka dib. Hayso diiwaanka qiyamka tijaabada si aad u go'aamiso marka dib u habeynta ama buuxinta adeega loo baahan yahay.
  • Xakamaynta Xakamaynta: Hubi in dahaarka fiilooyinka kontoroolka uu ku jiro xaalad wanaagsan iyo in cimiladu ay daboolan tahay. Is barbar dhig tamarta korantada korantada korantada iyo danabka lagu sheegay jaantuska fiilooyinka.
  • Rinjiyeynta: Sannad kasta kormeer rinjiga taransfooriyaha si uu u waxyeelleeyo cimilada iyo miridhku. Dib u hagaaji wixii waxyeelo ranji ah oo la helo.
  • Insulators Bushing: U baadh baadiyaha unugga iyo dahaadhiyeyaasha qalliinka ee xidhidhiyaha sannadkiiba. Nadiifi dusha sare marka aan tamar-marinaha tamar la siinin.

 

10.2 Muunada Dareeraha Dahaarka ah

Tijaabooyin dareere ah waa in si joogto ah loo qaadaa oo la falanqeeyaa. Waxaa lagu talinayaa in la qaado muunad hal toddobaad gudaheed ka dib tamarta, iyo sannad kasta ka dib.

Habka muunada saxda ah:

  • Tusaalooyinka waa in laga soo qaadaa waalka muunada ee ku yaal xagga hoose ee haanta beddelka.
  • Heerkulka dareeruhu waa inuu ka sarreeyaa heerkulka hawada ku hareeraysan si looga fogaado in uu qoyaanka dareeraha ku ururiyo.
  • Isticmaal weel qallalan oo nadiif ah (sida caadiga ah{0} dhalooyinka afka)
  • Ha u oggolaan in dareeruhu ku firdhiyo weelka helaya - daadinta waxay keeni kartaa hawo iyo qoyaan.
  • Ku luqluq dhalada saddex jeer iyadoo dareeraha laga qaadayo.
  • Markaad samballada ka soo qaadayso xagga hoose, soo jiid dareere ku filan si loo hubiyo in muunadku ka yimaado taangiga hoose, ee aan lagu kaydin dareeraha tuubada muunada (kaas oo ay ku jiraan uumi iyo dheecaan).
  • Muunad-qaadista, bir ama tubbo aan - caag ahayn waa in la isticmaalaa sababta oo ah saliiddu waxay ka soo daadisaa baaruudda caagga, taas oo waxyeello u geysan karta qaybaha beddelka.
  • Tijaabi xoogga dielectric si waafaqsan ASTM D-877. Haddii awoodda dielectric ay hoos uga dhacdo 26 kV, dareeraha waa in la sifeeyaa ilaa laga tijaabinayo 26 kV ama ka sii fiican.

 

10.3 Falanqaynta Gaaska Kala Diray (DGA)

Falanqaynta Gaaska Kala Dila waa qalab lagu ogaanayo xaaladda koronto-baddeyaasha iyadoo la cabbirayo gaaska ku milmay saliidda dahaarka. Hababka tarjumaadda ee DGA waxaa ka mid ah IEEE C57.104, kaas oo bixisa habraacyo faahfaahsan oo lagu qiimeeyo xaaladda beddelka iyadoo la adeegsanayo qalabyada iyo hababka falanqaynta.

  • Hagaha DGA wuxuu ka hadlayaa:
  • Aragtida jiilka gaaska ee ku jira transformer
  • Fasiraadda natiijooyinka falanqaynta gaaska kala diri
  • Nidaamyada hawlgalka ee la soo jeediyay
  • Farsamooyinka ogaanshaha kala duwan
  • Daraasado xaaladeed iyo tusaaleyaal
  • Shuruudaha iyo tilmaamaha qiimaynta

Hagaha IEEE C57.104 waxa uu quseeyaa - saliida macdanta adeega -Transformers immersed waxaana loogu talagalay in lagu siiyo hawlwadeenka macluumaadka waxtarka leh ee ku saabsan adeega qalabka

 

10.4 Dayactirka Bushing

Bushings waa in la beddelo kaliya marka loo baahdo. Waa in taxaddar la sameeyaa si looga fogaado dildilaaca suufka ama dusha sare ee waxyeelo. Hababka beddelka way kala duwan yihiin iyadoo ku xidhan nooca baadiyaha:

Taxaddar guud kahor shaqada baadiyaha ka hor:

  • Deji{0}Transformer-ka oo dami dhammaan wareegyada ilaa iyo ka soo baxa transformerka.
  • Ku xir meesha "furan" furayaasha furaha ee xariiqyada sahayda ee u socda iyo ka soo baxa transformerka.
  • Haanta hawada ku sii daadi ilaa cadaadisku eber yahay.
  • Haddii baadiyaha uu ka hooseeyo heerka dareeraha, hoos u dhig heerka si ku filan si looga hortago luminta dareeraha.

Sawir Qaadista Ka saarida Nooca Ledhka:

  • Fur oo ka saar daboolka sare ee terminalka si aad u muujiso xadhigga xadhigga ledhka ee barbaradka leh.
  • Ku xidh silig jiid, xadhig, ama usha silig si aad ugu hagto sunta rasaasta dhexda daloosha baadiyaha.
  • Ka saar nuts-ku-jiidka-ku-xidhka looska ee taangiga si aad u sii dayso saxanka xajinta.
  • Ka saar baadiyaha, adoo hagaya kirishbooyada rasaasta iyo istaarka meesha laga saaro iyada oo loo sii marayo salka baadiyaha.

Shuruudaha beddelka:

  • Dhalooyinka isku dhejiska ah waa in la adkeeyaa sida lagu qeexay miiska torque-ga ee soo saaraha.
  • Gaaska ku hoos jira flange kaynta koraya iyo gasketyada sare waa inay ahaadaan kuwo cusub ama xaalad fiican ku jira.
  • Dusha sare ee gaasku waa inay nadiif ahaadaan oo siman yihiin.
  • Ka dib marka la dhammeeyo, cadaadiska tijaabi transformerka.

 

10.5 Dayactirka Radiator

Transformers-ka leh radiators la go'i karo, rakibidda saxda ah iyo hababka ka saarista waa in la raaco:

Koritaanka:

  • Ka soo saar oo hubi hiitarka kasta. Ka saar cidhifyada indhaha la' oo nadiif ah oogayaasha gaasaska.
  • Kahor inta aanad ka saarin geesaha indho la'aanta ah, hubi in valves-ka ceejinta ay xiran yihiin (sare iyo hoose).
  • Radiyeeriyeyaasha mid mid ugu dheji taangiga dhanka midigna kor u yaal (dhinaca sare=lugaha wax lagu qaado).
  • Had iyo jeer isticmaal gaasaska cusub. Adkee dhammaan bolts valves oo dib u dhig 24 saacadood ka dib.
  • Ku dheji baararka adag (haddii ay jiraan) u dhexeeya hiitarka.
  • Ku rakib taageereyaasha (haddii ay jiraan) oo ku xidh fiilooyinka xakamaynta korantada.

Buuxinta:

  • Fur hawada - daloolka hawada sare ee hiitarka.
  • Qayb ahaan fur waalka ceejinta hoose ee ku yaal haanta.
  • Marka saliidda hawada ka baxdo{0}, xidh hawada{1} isla markiiba
  • Si buuxda u fur furayaasha ceejinta ee sare iyo hoose.

 

10.6 Dib-u-buuxinta Dayactirka ka dib

Ka dib markii dayactirka la dhammeeyo, ku buuxi unugga faakuum yar oo 3 PSIG ah (ugu badnaan) dareere qallalan oo dareere ah ilaa heerka dareeraha 25 darajo. Marka loo baahdo in lagu daro ama lagu buuxiyo transformer-ka dareeraha dielectric, shaqada waa in lagu sameeyaa qol nadiif ah oo qalalan. Isticmaal saliid - tuubbo adkaysi u leh - waligaa ha isticmaalin tuubo caag ah.

 

10.7 Dayactirka Dhamaystirka Dibadda

U baar xaaladda dibadda ee taransfooriyaha waqtiyo joogto ah. Haddii cimiladu dhacdo, si fiican u nadiifi dusha oo ku rinji rinji sare{1}} sida uu ku taliyey soo saaraha.

 

10.8 Qaybaha Spare

U hay baakadaha kaydka ah ee godka godka iyo gaasaska kasta{0}}nooca bushings ee la isticmaalo. Qaybaha kale ee cusboonaysiinta waxaa laga dalban karaa wakiilka warshada deegaanka. Markaad dalbanayso qaybo ama adeeg codsanayso, bixi sharaxaad dhamaystiran oo ku saabsan qaybta ama dhibaatada iyo lambarka taxanaha beddelka oo dhamaystiran sida ku qoran magaca taarka.

 

 


 

 

 

 

11. Heerarka lagu dabaqi karo

 

 

Heerarkan soo socda ayaa lagu tixraacay hagahan oo dhan waana in lagala tashadaa macluumaad faahfaahsan:

Heerarka IEEE:

  • IEEE C57.12.00 - Shuruudaha Guud ee Dareeraha{1}}Qaybinta Immersed, Power, and Regulation Transformers
  • IEEE C57.12.34 – Shuruudaha suufka -Ku rakiban, Qayb{2}}Nooca, Nafta{3}}La qaboojiyey, Saddex-Waji beddelayaasha Qaybinta
  • IEEE C57.12.90 - Koodhka Tijaabada dareeraha{1}}Qaybinta Immersed, Power, and Regulation Transformers
  • IEEE C57.94 - Tababarka lagu taliyay ee Rakibaadda, Hawlgalka, iyo Dayactirka Qalalan
  • IEEE C57.104 - Hagaha Tafsiirka Gaasaska Ka Soo Baxay Saliida Macdanta{1}
  • IEEE C57.106 - Hagaha Aqbalaada iyo Dayactirka Saliida Dahaarka ee Qalabka

Heerarka NEMA:

  • NEMA TR 1 - Transformers, Regulators iyo Reactors

Heerarka ANSI/NETA:

  • ANSI/NETA ATS - Halbeegga Tilmaamaha Tijaabada Ogolaanshaha ee Qalabka Korontada iyo Nidaamyada
  • ANSI/NETA MTS - Halbeegga Tilmaamaha Tijaabada Dayactirka ee Qalabka Korontada iyo Nidaamyada

Heerarka ASTM:

  • ASTM D-877 - Habka Tijaabada Caadiga ah ee Dielectric Dielectric Voltage of Insulating dareeraha Isticmaalka Disk Electrodes
  • ASTM D-923 - Hababka caadiga ah ee Muunalada ee Dareeraha Dahaarka Korontada

Heerarka Badbaadada:

  • OSHA 29 CFR 1910.269 - Korantada Korantada, Gudbinta, iyo Qaybinta
  • NFPA 70E - Heerka Badbaadada Korantada ee Goobta Shaqada
  • NEC Qodobka 450 - Beddelayaasha iyo Gawaarida Beddelayaasha (oo ay ku jiraan Xiriirada Sare)
  • NEC Qodobka 480 - Batariyada Kaydinta

 

CSA standards substation transformer
CSA halbeegyada is beddelka substation-ka
IEEE standards substation transformer
IEEE halbeegyada isbedbeddelka substation-ka

 

 


 

 

 

 

12. Rakibaadaha Transformer ee La Xidhiidha & Tilmaamaha Hawlgalka

 

 

Marka laga soo tago transformers-ka substation-ka, noocyada kale ee transformers-ka ayaa si weyn loogu isticmaalaa habka gudbinta korontada iyo qaybinta. Nooc kastaa wuxuu leeyahay rakibaad gaar ah, hawlgal, iyo shuruudo badbaado. Tixraac tilmaamahan soo socda si aad u hesho dabool dhammaystiran ee codsiyada is beddelka caadiga ah.

 

 

 


 

 

 

 

13. Gabagabo

 

 

Rakibaadda saxda ah, hawlgalka, iyo dayactirka tafaftirayaasha xarunta ayaa lama huraan u ah hubinta muddada dheer{0}isku halaynta, badbaadada, iyo waxqabadka. Adigoo raacaya nidaamka lagu sheegay hagahan {{2}laga bilaabo helitaanka iyo maaraynta bilawga ah iyada oo la adeegsanayo rakibaadda, tijaabinta, tamarta, iyo dayactirka socda{3} farsamayaqaanadu waxay si weyn u kordhin karaan nolosha adeega transformerka iyagoo yaraynaya khatarta qalab la'aanta iyo dhaawaca shakhsi ahaaneed.

Qodobbada muhiimka ah ee lagu maareeyo transformerka guusha leh:

  • Badbaadada marka hore- Had iyo jeer raac dhammaan heerarka badbaadada ee lagu dabaqi karo (IEEE, NEMA, NEC, OSHA, NFPA). Weligaa ha u tanaasulin borotokoolka badbaadada.
  • Maareynta saxda ah- Isticmaal dhibcooyinka qaadista ee loo qoondeeyay oo joog meelaynta heerka 4 digrii inta lagu jiro rakibidda.
  • Kormeer buuxa- Samee tijaabin horudhac ah oo dhammaystiran - tamarta, ay ku jirto TTR, caabbinta dahaarka, tayada dareeraha, iyo hubinta shaqaynta ee dhammaan agabka.
  • Dayactirka joogtada ah- Hirgeli jadwalka kormeerka iyo imtixaanada sanadlaha ah, oo ay ku jiraan falanqaynta DGA iyo baadhista tayada dareeraha.
  • Dukumeenti- Ilaali diiwaannada qiyamka tijaabada, akhrinta cabbirka, iyo hawlaha dayactirka si loo aqoonsado isbeddellada oo loo go'aamiyo marka dib u habeyn loo baahan yahay.

Macluumaad dheeri ah ama su'aalo farsamo oo gaar ah, la xiriir wakiilka warshadda soo saaraha.

 