2500 kVA suuf Ku rakiban Beddelka-13.2/0.48 kV|Kanada 2024
Awoodda: 2500kVA
Voltage: 13.2/0.48kV
Feature: oo leh IFD

Awooda culayska sare ee -, ilaalinta 24/7 – Saddex{3}}Safafka wejiga{4}}Ku rakiban, oo loogu talagalay baahida tamarta casriga ah!
01 Guud
1.1 Asalkii Mashruuca
Transformer-kan 2500 kVA Pad ku rakiban waxaa la geeyey Kanada 2024. Awoodda la qiimeeyay ee transformerku waa 2500 kVA, oo leh danab hoose 13.2GrdY/7.62 kV ilaa danab sare 0.48GrdY/0.277 kV. Kooxda isku xidhka ahi waa YNyn0,Transformer pad mounted waa in la hagaajiyo isku dhafka saliidda{9}}Transformer-ka tamarta shaabadaysan iyo qaybaha korantada sare iyo kuwa hooseeya, iyada oo la hagaajinayo qaab dhismeedka, qalabka wax lagu beddelo waa la yareeyaa ilaa inta suurtogalka ah, si weyn u yaraynaysaa raadraaca isku dhafka ah ee isku dhafan, muggiisu wuxuu u dhigmaa oo kaliya isla awoodda, 1 / 5 sanduuqa Yurub yar buuq, koronto la isku halayn karo, qaab-dhismeed macquul ah, rakibid dabacsan, hawl fudud, iyo gelida ugu badan ee xarunta xamuulka. Si weyn loogu isticmaalo aagagga la deggan yahay, xarumaha ganacsiga, saldhigyada, warshadaha iyo shirkadaha macdanta, garoomada diyaaradaha, tareenada, dugsiyada, isbitaallada,{15} dhismayaal sare iyo meelo kale. Transformer-ka Maraykanku waxa uu qaataa ilaalinta fiyuuska labanlaabka ah, iyo fur{17}} fiyuuska ku jira (BAY-O-NET) waa khaladka gaaban{20}} ee ka dhacaya dhinaca labaad ee fiyuuska labanlaaban ee xasaasiga ah (heerkulka, hadda) sanduuqa ilaalinta. Sanduuqa ilaalinta xaddidaadda fiyuuska ilaalinta (ELSP) ee hadda kaydinta ayaa beddela khaladaadka gudaha, oo loo isticmaalo in lagu ilaaliyo dhinaca tamarta sare.
1.2 Tilmaamaha Farsamada
2500 kVA nooca tafatirka beddelka iyo xaashida xogta
|
loo geeyey
Kanada
|
|
Sannadka
2024
|
|
Nooca
suuf ku rakiban transformer
|
|
Heerka
IEEE C57.12.00
|
|
Awood lagu qiimeeyay
2500kVA
|
|
Soo noqnoqoshada
60HZ
|
|
Marxaladda
3
|
|
Quudinta
Loop
|
|
Hore
dhintay
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
13.2GrdY/7.62 kV
|
|
Voltage Secondary
0.48/0.277 kV
|
|
Qalabka dabaysha
Aluminium
|
|
barokaca xagal
YNyn0
|
|
Caqabada
5.75±7.5%
|
|
Waxtarka
99.53%
|
|
Taabo Beddelka
NLTC
|
|
Insulant dareere ah
Saliida macdanta
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
In ka yar ama la mid ah 2.3KW
|
|
Load Lumista
In ka yar ama la mid ah 16.2KW
|
|
Agabka
Habaynta caadiga ah
|
1.3 Sawirro
2500 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Sadexda{0}wajiga shanaad-Tiirka dahaadhay xudunta birta waxay si wax ku ool ah u yaraynaysaa luminta birta iyo qaylada, iyo saddexda{2}wajiga shanaad{3}}qaab dhismeedka safku waxa uu bixin karaa qaybinta qulqulka birta oo isku mid ah, korna uqaada awooda xajinta xudunta birta ilaa goobta magnetic, waxa ayna gacan ka geysataa hagaajinta hufnaanta shaqada iyo waxqabadka qalabka. Qaab dhismeedka la daboolay wuxuu ka caawiyaa inuu hagaajiyo waxqabadka kulaylka ee xudunta u ah, hoos u dhigista heerkulka, ka hortagga kulaylka, iyo kordhinta nolosha adeegga qalabka.

2.2 Dabaylaha

Danab sare
ZGS taxane danab sare terminal ku qalabaysan danab sare bushing hal ama double) loo isticmaalo in lagu xidho nooca suxulka fiilo cable ama nooca suxulka si buuxda u xiraha dahaaran, qaybta live waxaa shaabadeeyey in jidhka dahaaran, samaynta qaab-dhismeedka si buuxda u dahaaran, dusha terminal aan lagu soo oogin, (karta dhulka), si loo hubiyo in ammaanka shakhsi. Haddii ay dhacdo xaalad degdeg ah, fiilada fiilada waa la xiri karaa oo bixi kartaa marka qalabka si buuxda loo raro. Sababtan awgeed, fiilada fiilada waxay sidoo kale u dhaqmi kartaa sida beddelka culeyska. Muujinta tooska ah ama tilmaame cilad ayaa lagu rakibi karaa fiilada sida loo baahdo. Dhererka derbiga ayaa lagu alxanayaa madaxa hore ee taangiga cadaadiska sare ee transformer-ka ee u dhow buushka cadaadiska sare, kaas oo loo isticmaalo in lagu hagaajiyo nooca taageerada la hagaajin karo ee madaxa baadiyaha. Marka fiilada fiilada la shido, isla markiiba waxaa la gelin karaa nooca taageerada wadajirka baadiyaha.
danab hooseeya
Waxa jira meelo hoose -Voltage outlet terminal inta u dhaxaysa-dhexdhexaadka korantada, iyo hooseeya -voltage main circuit breaker iyo laanta wareegta wareegtada, hoose - hadda, mitirka voltaji iyo qalabka magdhowga tamarta falcelinta ayaa la bixiyaa sida loo baahdo. Marwaxada axial waxa lagu rakibi karaa xaga sare ee ugu hoosaysa-voltage inta u dhaxaysa shuruudaha isticmaalaha, iyo qalabka xakamaynta heerkulka gaarka ah ayaa si toos ah u xakameyn kara kulaylka marawaxada iyadoo loo eegayo heerkulka inta u dhaxaysa. Waxaa lagu rakibi karaa telemetry haddii loo baahdo. Tijaabada qaybinta isku dhafan ee leh shaqada isgaadhsiinta fog, oo lagu kabo mid hooseeya -voltage iyo ka hooseeya - kontaroolaha korantada, waxa uu xaqiijin karaa shaqada ilaalinta ee maya
2.3 Haanta
Marka loo eego sawirada naqshadeynta, taarikada birta ah ayaa la gooyaa cabbirro iyo qaabab kala duwan oo loogu talagalay isu imaatinka xiga. Hababka goynta waxay noqon karaan mashiinka goynta CNC, goynta laser ama goynta oksijiinta. Saxanka birta ah ee la gooyey waa la foorarsaday, qallafsanaan iyo habab kale si loo sameeyo qaybo kala duwan oo taangiga ah, sida saxanka hoose, saxanka dhinaca, saxanka sare, iwm Alxanka ka dib, waxaa lagama maarmaan ah in la sameeyo kormeerka muuqaalka iyo saxitaanka cabbirka si loo hubiyo in shuruudaha naqshadeynta la buuxiyey. Ka dib alxanka la dhammeeyo, dusha sare ee haanta waxaa lagu daaweeyaa si looga hortago daxalka iyo miridhku. Hababka caadiga ah waxaa ka mid ah ciid-qarxinta, ciid-jaridda iyo jebinta, oo ay ku xigto dahaarka ka-hortagga- rinjiga daxalka. Sanduuqa waxa uu qaataa nashqada ka hortaga daxalka iyo daawaynta rinjiyeynta buufinta gaarka ah, kaas oo lagu dabaqi karo degaano adag oo kala duwan, sida duufaano badan iyo aagag wasakhaysan oo badan.

2.4 Kulanka ugu dambeeya


03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
% |
Heerka ugu sarreeya ee iska caabbinta dheelitir la'aanta In ka yar ama la mid ah 5% |
3.28 |
Gudub |
|
2 |
Imtixaanada saamiga |
% |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: YNyn0 |
-0.02% ~ -0.01% |
Gudub |
|
3 |
wajiga- imtixaanada xidhiidhka |
/ |
YNyn0 |
YNyn0 |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% kW |
t: 20 darajo I0: bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay Dulqaadka wax qabad la'aan waa +10% |
0.25 2.354 |
Gudub |
|
5 |
Load khasaaraha danab impedance iyo hufnaan |
% kW kW |
t: 85 darajo Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay Dulqaadku waa ± 7.5% Dulqaadka wadarta rarka luminta waa +6% Waxtarka aan ka yarayn 99.53% |
5.85 15.580 17.934 99.53 |
Gudub |
|
6 |
Tijaabada Korantada ee La dabaqay |
kV |
HV&LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
kV |
Danab la dabaqay (KV): 26.4 Muddada: 40 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
8 |
Tijaabada daadinta |
kPa |
Cadaadiska la dabaqay: 20kPA Muddada: 12h |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
9 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV&LV ilaa Dhulka: |
8.68 |
/ |
|
10 |
Tijaabada Dielectric Oil |
kV |
Ka weyn ama la mid ah 45 |
53.80 |
Gudub |
|
11 |
Imtixaanka buuqa |
dB |
51-55 |
57.3 |
Gudub |
|
12 |
Tijaabada dareenka hillaaca |
kV |
mawjad buuxda, hirka badh |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |


04 Baakaynta iyo dhoofinta


05 Goobta iyo Kooban
Gebagebadii, Sadexda Waji ee Baasaboorka Saxiixa ah ayaa u taagan hufnaantiisa sare, badqabkiisa, iyo cimri dhererkiisa, taasoo ka dhigaysa mid si weyn loogu dabaqi karo mashaariicda kala duwan ee ganacsiga, warshadaha, iyo kaabayaasha dadweynaha. Haddi ay ahaan lahayd{1}qaybinta awooda sare ama hawlgalka xasiloon ee deegaan adag, alaabtani waxa ay keentaa xalal lagu kalsoonaan karo si ay u taageerto maaraynta tamarta hufan iyo faa'iidooyinka dhaqaale ee mudada dheer-. Dooro Transformer-ka Saddexda Waji ee suufka ah si aad u xoojiso mashaariicdaada oo aad gacan uga geysato mustaqbalka tamar cagaaran oo hufan.