1000 kVA suuf Ku rakiban Beddelka-13.2/0.48 kV|USA 2025
Awoodda: 1000 kVA
Voltage: 13.2 / 0.48 kV
Feature: oo leh IFD

Tignoolajiyada cusub, waafaqid kaamil ah-saddexda-qalabka suufka lagu rakibay ee korantada ayaa mustaqbal cusub u horseedaya warshadaha tamarta!
01 Guud
1.1 Asalkii Mashruuca
1000 kVA saddex weji suuf ah oo ku rakiban transformer ayaa la geeyey Ameerika sanadka 2025. Awoodda la qiimeeyay ee transformerku waa 1000 kVA oo leh ONAN qaboojin. Korantada aasaasiga ah waa 13.2GrdY / 7.62 kV oo leh ± 2 * 2.5% cabirka garaaca (NLTC), danab labaad waa 0.48Y / 0.277 kV, waxay sameeyeen koox vector ah YNyn0.
Qalabkayaga -Transformers ee lagu rakibay waxaa loogu talagalay inay u adkeystaan faragelinta iyo cimilada, taasoo ka dhigaysa badbaado meelaynta meelaha caamka ah. Dhisme kastaa waxa laga dhisay bir culus{2}} birta cabbiraadda waana budo{3}}ku dahaadhay mid la dubay oo waara{4}} marka la dhammeeyo si kor loogu qaado iska caabbinta faragelinta. Waxaan bixinaa labadaba nool -hore iyo kuwa dhintay{{7}nashqada hore ee suufkayaga -Transformers ee rakiban, kuwaas oo la socda qaabaynta radial ama loop feed. Transformers-yada casriga ah ee ku rakiban suufka ayaa caadi ahaan shaqeeya naqshado hufan si loo yareeyo isticmaalka tamarta iyo kharashaadka shaqada, halka dareerayaasha dielectric ee la isticmaalo ay inta badan yihiin walxo deegaanka u fiican. Tallaabooyin ilaalin badbaado oo kala duwan ayaa lafuliyaa, sida ilaalinta culeyska xad dhaafka ah, ilaalinta gaaban{11}} ilaalinta wareegga, iyo la socodka cilada dhulka, si loo hubiyo hawlgal badbaado leh oo hoos yimaada xaalado shaqo oo kala duwan. Transformers suufka lagu rakibay ayaa lagu dabaqi karaa aagagga la deggan yahay, aagagga ganacsiga, jardiinooyinka warshadaha, iyo nidaamyada korantada ee miyiga, iyaga oo daboolaya baahida culeyska kala duwan.
1.2 Tilmaamaha Farsamada
1000kVA saddex waji oo suuf ah oo ku rakiban tafatirka tafatirka iyo xaashida xogta
|
loo geeyey
Ameerika
|
|
Sannadka
2025
|
|
Nooca
Saddex weji suuf ku rakiban transformer
|
|
Heerka
IEEE C57.12.00
|
|
Awood lagu qiimeeyay
1000kVA
|
|
Soo noqnoqoshada
60 HZ
|
|
Marxaladda
Keli
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
13.2GrdY/7.62 kV
|
|
Voltage Secondary
0.48Y/0.277 kV
|
|
Qalabka dabaysha
Aluminium
|
|
Caqabada
5.75%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
1.3KW
|
|
Load Lumista
6.94KW
|
|
Agabka
Habaynta caadiga ah
|
|
Hadallo
N/A
|
1.3 Sawirro
1000 kVA saddex weji suuf ah oo ku rakiban cabbirka beddelka iyo faahfaahinta miisaanka
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Sadexda{0}wajiga sadexaad- xudunta tiirka waxa uu ka kooban yahay saddex tiir oo si toosan loo habeeyey, mid walbana u dhigma weji koronto ah. Tiirarkani waxay ku xidhan yihiin alwaaxyo toosan, samaynta qaab-dhismeed adag oo bixiya xoog farsamo iyo xasilooni wanaagsan. Naqshadeyntani waxay hubinaysaa in transformer-ku uu u adkeysan karo culeysyo farsamo oo kala duwan inta lagu jiro hawlgalka iyadoo la ilaalinayo waxqabadka magnetic ugu fiican. Sadexda{5}}wajiga sadexaad- xudunta tiirka waxa ay samaysaa wareeg magnet xidhan, si wax ku ool ah u xoojiya qulqulka magnetic iyo yaraynta qulqulka magnetic. Xuddunta waxa ay ka samaysan tahay go'yaal bir ah oo silikoon ah oo hooseeya - kuwaas oo la isku dhufto. Xaashiyaha birta silikoonku waxay leeyihiin sifooyin koronto-magneteed heersare ah oo si wax ku ool ah u yareeya khasaaraha hadda jira iyo khasaaraha xiiq-dheeraanta.

2.2 Dabaylaha

Ku-haystaha buushka korantada ee hooseeya -Transformers-ku rakiban waa qayb dhismeed oo muhiim ah oo loogu talagalay in lagu sugo oo lagu dejiyo baadiyaha isku xidhka ka badan toban furin. Iyadoo la siinayo taageero farsamo oo adag, waxay hubisaa isku xidhka iyo hufnaanta rakibaadaha baadiyaha badan, si wax ku ool ah u yaraynaysa khatarta dhaawaca gariirka, baaskiil wadida kulaylka, ama xooga dibadeed, si kor loogu qaado - badbaadada wakhtiga dheer iyo isku halaynta beddelka
2.3 Haanta
Haanta saliidda beddelka waa in ay keentaa tas-hiilaadka lagu rakibayo qalabka, sida ku cad lifaaqa 2. Isla markaana, 1{2}}inji qalab rakibaadda marinnada gudaha ee hoose{6}}qayb koronto ilaa meesha mitirka korontada waa in la bixiyaa. Dhammaan albaabada waa inay awood u yeeshaan in si buuxda loo furo iyada oo aan wax xannibin ah (sida mitirka korontada, iwm.). Marka nooca go'an ee qaybta korantada hoose ay bixiso cabbirka ugu yar ee 16 1/2 inji x 33 1/4 inji oo meel banaan ah iyo joogga lagu sheegay lifaaqa 2, qalab rakibaadda looma baahna.

2.4 IFD

Ogaanshaha Cilada Dahaarka (IFD) ee transformers-ka waa nidaamka la socodka onlaynka ah ee u adeega sida aaladda digniinta ugu horayso iyadoo si joogto ah ula socota gaaska hydrogen (H₂) ee ku milmay saliidda dahaadhka. Waxay ogaataa marxaladaha bilowga ah ee cilladaha dahaarka gudaha, sida qayb ka mid ah dareeraha ama kulaylka, taas oo soo saarta hydrogen, taas oo u oggolaanaysa dayactirka firfircoon ka hor inta aan arrimahan kor u qaadin guuldarrooyinka waaweyn. Asal ahaan, IFD waxay u shaqeysaa sidii baaris caafimaad oo ka hortag ah oo loogu talagalay beddelayaasha, kor u qaadda kalsoonida iyo ka hortagga burburka musiibada iyadoo aqoonsanaysa cilladaha qarsoon marxaladdooda ugu horreysa uguna badan ee la maarayn karo.
03 Tijaabinta
3. Kormeerka Hawlaha Furitaanka iyo Xiritaanka AlbaabkaShuruudahani waxa ay qeexaysaa in ka hor inta aanay soo saaraha transformer-ka keenin qalabka, in dhawr albaab oo furitaan iyo xidhidh la sameeyo si loo hubiyo in albaabku u shaqeeyo iyo in kale, iyadoo laga fogaanayo arrimo ay ka mid yihiin qallafsanaan, qallafsanaan, ama rakibid aan habboonayn.
• Walxaha Tijaabada: Inta badan imtixaannada waxqabadka farsamada, oo ay ku jiraan inta jeer ee furitaanka albaabka iyo xidhidhiyaha, hufnaanta, iyo waxqabadka xidhidhiyaha.
• Heerarka Shuruudaha: Tijaabadani waxa ay hubisaa in xayndaabka transformer-ka ama furaha beddelka aanu jidh ahaan dhaawacmin inta lagu jiro isticmaalka, iyo in furitaanka albaabka iyo hawlgallada xidhiddu ay ilaaliyaan xaalad shaqayneed oo wanaagsan.
• Heerarka ANSI: Inkasta oo shaygan laga yaabo in aan si toos ah loogu taxay dhammaan heerarka ANSI, shuruudaha la midka ah ayaa sida caadiga ah laga helaa qeexitaannada sida ANSI C57.12.90 (Sharuudaha Imtixaanka caadiga ah ee Transformers), iyadoo la hubinayo isku halaynta dhammaan qaybaha hawlgalka dibadda.


04 kale
4.1 shuruud
suufka -Transformers-ka ee lagu rakibay waa in ay ku jiraan taangiga beddelka iyo qaybo ka mid ah fiilada tamarta sare iyo mid hoose. Taangiga beddelka iyo qolalka waa in la isugu keeno sidii unug loogu rakibo suuf. Waa inaan bannaanka laga helin bilal qaawan, boolal ama qalab kale oo dibadda laga saari karo. Ma jiraan meelo bannaan oo ay ka soo galaan walxaha shisheeye sida laamo, biraha ama fiilooyinka ay ku xiran karaan qaybo nool. Hab ku habboon waa in la bixiyaa xirida albaabada qolka. Xirmada quful hex 1/2-inji ah oo leh fasalka dunta NC 2 kana soocan aaladda qufulka waa in sidoo kale la bixiyaa sida ku cad lifaaqa. Naqshadeynta qaabdhismeedku waa in ay xaddidaa gelitaanka biyaha (marka laga reebo daadadka) ee qolalka si looga fogaado in ay saamayso shaqada caadiga ah ee beddelka.

4.2 qalabyada

Transformer-ku waa in lagu qalabeeyaa lix (6) ESNA, Permali, Qaybaha, Maloney Cental ama Westinghouse sare{1}} godad kaynta korantada (ANSI C119.2), dibeda ku dheggan, si ay u aqbalan culayska{3}} jebinta furayaasha si ay ugu shaqeeyaan transformer ka nidaamka aasaasiga ah nooca giraanta. Qalabyada Elastimold Style 164BA giraanta kor u qaadida waa in lagu bixiyaa meelaha lagu muujiyay Lifaaqa 1. Baabuur, Nitrile ama walxo kale oo ay degmadu ansixisay waa in lagu bixiyaa qalab xadidaya. Qalabka gaaska waa in si sax ah loo rakibaa si loo hubiyo in - godadka sare ee kaynta korantada ay had iyo jeer la xiriiraan taangiga dhulka dhigay. Dhererka hogaanka sare - waa in uu ku filnaado si loo fududeeyo - bedelka goobta ceelasha kaynta.
05 Goobta iyo Kooban
Gebagebada, saddexda{0}xajmiga suufka ku rakiban transformer-ka waxa uu ka dhigan yahay xal aad u hufan oo la isku halayn karo oo loogu talagalay baahiyaha qaybinta korontada ee dibadda. Iyada oo nashqaddeeda adag, tignoolajiyada dahaarka sare leh, iyo awoodaha qaboojinta wax ku ool ah, transformerkani waxa uu hubinayaa waxqabadka ugu fiican iyo cimri dhererka, xitaa xaaladaha deegaanka ee adag. Is haysta, suuf -ku rakiban qaabayntiisa kaliya ma badbaadinayo meel laakiin sidoo kale waxa ay kordhisaa badbaadada iyo fududaynta rakibaadda. Haddi ay ahaan lahayd codsiyada ganacsiga, warshadaha, ama dawlada hoose, sadexdayada -Transformers ee ku rakiban suufka wejiga waxay keenayaan awooda iyo kalsoonida aad ku kalsoonaan karto. U dooro transformers-keena xal tamar waara oo wax ku ool ah kaas oo buuxinaya baahida muuqaalka tamarta ee maanta.

Hot Tags: 1000 kva suuf ku rakiban transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
500 kVA Dhintay suufka hore ee ku rakiban beddelka-2...
4000 kVA 3 Waji suuf Ku rakiban Badaha-24.94/0.6 kV|...
3000 kVA Transformer-25/0.6 kV|Kanada 2025
3000 kVA suuf Ku rakiban Beddelka-25/0.6 kV|Kanada 2025
500 kVA Utility Pad Ku rakiban Beddelka-24/0.48 kV|U...
1000 kVA Saliid Buuxsan oo Ku rakiban Beddelka-13.8/...
U dir sooji