Awoodda: 2500kVA
Voltage: 34.5/0.6kV
Tilmaam: LV Side Flanged -Ku rakiban Bushings

Ku-xoojinta xariijimaha dhulka hoostiisa ee xariifka ah oo leh 2500 kVA transformers koronto oo loo dhisay hufnaan iyo badbaado.
01 Guud
1.1 Asalkii Mashruuca
Sannadkii 2025, waxaan u dhiibnay labo koronto oo la deggan yahay 2500kVA macmiil gudaha Mareykanka si ay u taageeraan nidaamka qaybinta awoodda dhulka hoostiisa oo casri ah. Loo dhisay si uu ula kulmo IEEE Std C57.12.34-2022 iyo DOE 2016 heerarka hufnaanta tamarta, qalabkan ku rakiban suufka ayaa bixiya isku halaynta sare, kayd tamarta, iyo faa'iidooyinka deegaanka ee mudada dheer.
Cutubku wuxuu leeyahay quudin loop ah, nakhshad hore oo dhintay, hubinta hawlgal ammaan ah iyo dayactir fudud ee deegaan magaalo oo is haysta. Waxay isticmaashaa saliidda ester-ka dabiiciga ah ee FR3, dab - badbaado leh, dareere dahaadhan biodegradable oo ku habboon guryaha, ganacsiga, iyo rakibaadaha hay'adaha halkaasoo badbaadada iyo waaritaanku ay muhiim u yihiin.
Iyada oo leh xayndaab xiran iyo dhinac{0}ku rakiban korantada hoose ee meesha laga soo baxo, transformer-kan korantada ee la degan yahay waxaa loo hagaajiyay isku xirka fiilada dhulka hoostiisa ee casriyaynta shabaqyada smart, degmooyinka ganacsiga, jardiinooyinka warshadaha, iyo saldhigyada tamarta. Raadkeeda is haysta iyo hawlgal xasilloon ayaa ka dhigaya meel ku habboon meelaha bannaan iyo qaylada xaddidan.
Marka la isku daro waxtarka sare (99.53%), dahaarka adag, iyo hagaajinta korantada dabacsan, cutubkani waxa uu bixiyaa la isku halayn karo, hooseeya{1}Xalka dayactirka ee ku haboon codsiyada xidhidh ee Waqooyiga Ameerika.
1.2 Tilmaamaha Farsamada
2500kVA qeexida beddelka koronto ee deegaanka iyo xaashida xogta
|
loo geeyey
Ameerika
|
|
Sannadka
2025
|
|
Nooca
Saddex weji suuf Buur Transformer
|
|
Heerka
IEEE Std C57.12.34-2022
|
|
Awood lagu qiimeeyay
2500 kVA
|
|
Soo noqnoqoshada
60 HZ
|
|
Quudinta
Loop
|
|
Hore
dhintay
|
|
Marxaladda
Saddex
|
|
Nooca qaboojinta
KNAN
|
|
Insulant dareere ah
FR3 Saliid
|
|
Korantada aasaasiga ah
34.5 kV
|
|
Voltage Secondary
0.63 kV
|
|
Kooxda Vector
YNyn0
|
|
Qalabka dabaysha
Aluminium
|
|
Caqabada
5.75%
|
|
Heerka Waxtarka iyo Khasaaraha
DOE 2016
|
|
Waxtarka
99.53 %
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
2.4 kW
|
|
Load Lumista
15.79 kW
|
1.3 Sawirro
2500kVA cabbirka beddelka korantada ee deegaanka iyo faahfaahinta miisaanka
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Xuddunta waxay ka kooban tahay saddex lugood oo waaweyn iyo laba lugood oo caawiya. Qulqulka magnetic wuxuu dhex maraa lugaha waaweyn iyo kuwa caawiya labadaba, isagoo siinaya wadooyin dheeraad ah oo hagaajiya xiritaanka qulqulka. Naqshadani waxay hubisaa hawlgal xasiloon oo ku hoos jira culeys aan dheeli tirnayn iyo maya - xaaladaha rarka, yaraynta gariirka iyo buuqa. Shanta - xudunta lugta waxay u socotaa si degan oo la isku halleyn karo, taasoo ka dhigaysa mid ku habboon qaybinta magaalooyinka iyo isticmaalka ganacsiga halkaas oo loo baahan yahay buuq yar iyo isku halaynta sare.

2.2 Dabaylaha

Guryaha korantada ee la degan yahay ee ku rakiban isbedbedelku waxa ay adeegsadaan dabaylaha foil yar oo hooseeya iyo - silig koronto-ku-wareegaya oo leh kirishbooyada aluminium fidsan si loo horumariyo khasaaraha. Gariiradu waxay ka samaysan tahay aluminium si ay u dhaqdo iyo miisaankeeda fudud. Sawirka, shaqaale ayaa adkaynaya biraha saxanka ah ee riixaya si uu u ilaaliyo gariiradda, isaga oo isu diyaarinaya tallaabada xigta ee riixida. Tani waxay xaqiijinaysaa isku-duubni adag, waxay xoojisaa xasilloonida farsamada, waxay yaraynaysaa gariirka, waxayna kordhisaa kalsoonida iyo waxtarka inta lagu jiro hawlgalka.
2.3 Haanta
Sadexda{0}Transformer-ka korantada ee wejiga waxa leh haanta bir khafiif ah oo xidhan oo dabool xidhan, budo{1}}ku dahaadhay RAL 9003 oo cadaan u ah iska caabinta daxalka. Ku qalabaysan lugaha wax-qaadista iyo suufka jackingka si fudud loo maareeyo. Waxay ku gudubtaa tijaabada daadinta cadaadiska 50kPa muddo 12 saacadood ah iyada oo aan lahayn wax daadsan ama qallafsanaan, hubinta shaabad la isku halayn karo iyo sharaf dhisme.

2.4 LV dhinaca Flanged -Ku rakiban Bushings

Sadexda{0}wajiga suufka lagu rakibay transformer-ka waxa uu leeyahay nashqad dhinaca gees ka gees ah oo danab hoose leh, taas oo u ogolaanaysa xidhidh fudud oo aamin ah fiilooyinka dhulka hoostiisa. Dhinaca - ee ku rakiban marinnada LV-ga waxa ilaaliya sanduuqa fiilada ee xidhan, hubinta badbaadada, meel bannaan{3}ku rakibida wax ku oolka ah ee shabakadaha qaybinta magaalooyinka iyo nidaamyada korantada ganacsiga.
2.5 Kulanka ugu dambeeya
Xudunta & Golaha Gariiradda
Dabaysha aluminiumka (YNyn0) ayaa lagu dhejiyay xudunta qaboojinta KNAN. Dahaarka iyo kala dheeraynta waxay la kulmaan 34.5 kV/0.63 kV iyo 5.75% qeexida impedance.
Diyaarinta Haamaha
Haanta lagu dahaadhay rinjiga FR3 u adkaysta. Qaybaha muhiimka ah: waalka gargaarka cadaadiska, saliidda/ faakuumka cabbiraadaha, iyo buuxi furka deked cadaadis ah.
Meelaynta Golaha
Xudunta - gariiradda ayaa ku go'an gudaha haanta. NLTC (± 2 × 2.5%) gacanta lagu fidiyay daboolka.
Is dhexgalka dhinaca HV
Raad jebinta furaha, bayonetka iyo fiyuusyada CLF oo lagu rakibay mayd{0}}qol hore ee quudinta loop.
Buuxinta vacuum
Saliid FR3 ayaa lagu buuxiyey wax ka yar ama la mid ah 0.5 mbar vacuum. Waalka daadi oo lagu daray deked muunad
Korjoogteynta Rakibaadda
Heerkulbeegga saliidda sare iyo 4-20 mA fiilooyinka dareeraha ayaa lagu xidhay sanduuqa terminalka.
Xadhkaha ugu dambeeya & Tijaabada
Xadhkaha beddelka tuubada, cabbiraha, iyo dareemayaasha (ku calaamadsan A/B/C). Iska caabinta dahaarka iyo wax - lumitaanka culeyska (2.4 kW bartilmaameed) oo la tijaabiyay.

03 Tijaabinta


Imtixaanka Joogtada ah iyo Heerka Imtixaanka
1. Cabbiraadaha iska caabinta: Marka loo eego IEEE C57.12.90-2021 Farqada 5
2. Tijaabada Saamiga: Marka loo eego IEEE C57.12.90-2021 Farqada 7
3. Wajiga{1}}Tijaabada xidhiidhka: Marka loo eego IEEE C57.12.90-2021 Farqada 6
4. Wax khasaare ah oo la saaray ma jiro iyo hadda wax culays ah: Sida ku cad IEEE C57.12.90-2021 faqradda 8
6
6. Tijaabada Korantada ee La Codsaday: Marka loo eego IEEE C57.12.90-2021 Farqada 10.6
7. Tijaabada adkaysiga korantada ee keentay: Marka loo eego IEEE C57.12.90-2021 Farqada 10.5.1
Cabbirka iska caabinta dahaarka
8. Tijaabinta Leak ee Cadaadiska Dareeraha Immersed Transformers: Tijaabada daadinta ee 50KPa waa in la sameeyaa 12h iyada oo aan wax daadin. Ma jiro qallooc joogto ah.
9. Cabbirka iska caabbinta dahaarka
Natiijooyinka Imtixaanka
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
% |
Heerarka dheelitir la'aanta iska caabbinta ugu badan |
4.58 |
Gudub |
|
2 |
Imtixaanada saamiga |
% |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: YNyn0 |
0.01% ~ 0.03% |
Gudub |
|
3 |
wajiga- imtixaanada xidhiidhka |
/ |
YNyn0 |
YNyn0 |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
/ |
I0 :: bixiyaan qiime la qiyaasay |
0.18% |
Gudub |
|
P0: bixi qiimaha la qiyaasay (t:20 darajo) |
2.281kW |
||||
|
Dulqaadka wax qabad la'aan waa +10% |
/ |
||||
|
5 |
Load khasaaraha danab impedance iyo hufnaan |
/ |
t:85 darajo dulqaadka impedance waa ± 7.5% dulqaadka wadarta rarka luminta waa +6% |
/ |
Gudub |
|
Z%: qiimaha la qiyaasay |
6.00% |
||||
|
Pk: qiimaha la qiyaasay |
15.091kW |
||||
|
Pt: qiimaha la qiyaasay |
17.372 kW |
||||
|
Waxtarka aan ka yarayn 99.53% |
99.55% |
||||
|
6 |
Tijaabada Korantada ee La dabaqay |
kV |
LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
U adkaysiga korantada ee la kiciyay |
kV |
Danab la dabaqay (KV):2Ur |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
Muddada:48 |
|||||
|
Inta jeer (HZ): 150 |
|||||
|
8 |
Tijaabada daadinta |
kPa |
Cadaadis la dabaqay: 50kPA |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
Muddada:12h |
|||||
|
9 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV -LV to Ground : |
1.40 |
/ |
|
LV-HV ilaa Dhulka: |
1.53 |
04 Baakaynta iyo dhoofinta
4.1 Xirxirida


4.2 dhoofinta

05 Goobta iyo Kooban
SCOTECH waxa sharaf u ah in ay keento suufka ku rakiban macmiilkayaga Maraykanka, taas oo ka qayb qaadanaysa baahiyahooda awood qaybin xalal la isku halayn karo oo hufan.
Iyada oo diiradda la saarayo buuxinta heerarka IEEE iyo DOE, kooxdeennu waxay si taxadar leh u qaabeeyeen, u soo saareen, oo tijaabiyeen beddelaadaha korantada ee la deggan yahay si loo hubiyo waxqabadka iyo waarta. Mashruucani wuxuu ahaa dadaal iskaashi, waxaanan qadarinaynaa kalsoonida macmiilkayagu nasiyay.
Sida shirkad ay ka go'an tahay horumarinta joogtada ah, waxaan ku dadaaleynaa inaan nadiifino khibradeena injineernimada iyo awoodaha adeeg si aan u taageerno kaabayaasha tamarta caalamiga ah. Waxaan rajeyneynaa fursadaha mustaqbalka si aan u bixino xalal tayo sare leh oo waara{1}
Waad ku mahadsan tahay inaad dooratay SCOTECH{0}waxaanu wali u heellan nahay heerka sare ee tignoolajiyada awooda iyo qanacsanaanta macmiilka.

Hot Tags: Transformers koronto la deggan yahay, soo saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
500kVA Pad Mount Transformer-14.4/0.208 kV|USA 2025
1000 kVA suuf ku rakiban beddelka-22.86/0.48 Kv|USA ...
1500 kVA Dhulka Ku rakiban Beddelka-34.5/0.48 kV|USA...
1000 kVA suuf Buurta Beddelayaasha Iibka-4.16/0.48 k...
750 kVA Pad Mount Transformer-25/0.6 kV|Kanada 2025
1500 kVA Pad Mount Transformer-13.8/0.46 kV|Guyana 2025
U dir sooji