750 kVA Pad Mount Transformer-25/0.6 kV|Kanada 2025

750 kVA Pad Mount Transformer-25/0.6 kV|Kanada 2025

Dalka: Kanada 2025
Awoodda: 750 kVA
Voltage: 25D-0.6Y/0.347 kV
Feature: leh fur jabinta
U dir sooji

 

 

750 kva pad mount transformer

Awood la isku halayn karo, Nakhshad is haysta - Transformers-ka suufka lagu rakibay ee Shabakad Wacan!

 

 

01 Guud

1.1 Sharaxaada Mashruuca

750 kVA saddex weji suuf ah oo ku rakiban transformer ayaa la geeyey Kanada 2025. Awoodda la qiimeeyay ee transformerku waa 750 kVA oo leh ONAN qaboojin. Korantada aasaasiga ah waa 25D kV oo leh ± 2 * 2.5% garaacista (NLTC), danab labaad waa 0.6y / 0.347 kV, waxay sameeyeen koox vector ah Dyn1.

CSA{0} suufka shahaadaysan -Transformers-ku rakiban waxay la kulmaan heerarka adag ee ay dejisay Ururka Istaandarada Kanada (CSA) ee waxqabadka korantada, adkeysiga, iyo adkeysiga deegaanka. suufka -Transformers-ku rakiban waa unug qaybin koronto oo adag, is haysta, oo aad u hufan oo loogu talagalay rakibaadda dibadda ee heerka dhulka. Ku lifaaqan xayndaab adkeysi leh, fara-ku-tiris ah{5}, Transformers-yadani waxay bixiyaan beddelka awood ammaan ah oo la isku halayn karo ee magaalooyinka, xaafadaha, iyo codsiyada warshadaha. Booskooda - nashqada kaydinta waxay yaraynaysaa raadka iyadoo la hubinayo helitaanka fudud ee dayactirka.

Iyada oo leh dahaar sare leh, iska caabin daxal, iyo dhismo aan cimiladu lahayn, suuf -Transformers rakiban waxay keenaan waxqabad joogto ah jawiyo kala duwan{1}laga bilaabo shabkadaha smart iyo nidaamyada tamarta la cusboonaysiin karo ilaa dhismayaasha ganacsiga iyo shabakadaha tamarta. Injineerada badbaadada, hufnaanta, iyo cimri dhererka, waa doorashada lagu kalsoon yahay ee qaybinta awoodda casriga ah.

 

 

 

1.2 Tilmaamaha Farsamada

1500 kVA suuf ku rakiban nooca tafatirka beddelka iyo xaashida xogta

loo geeyey
Jamaica
Sannadka
2025
Nooca
suuf ku rakiban transformer
Heerka
CSA 2.1-06
Awood lagu qiimeeyay
750 kVA
Soo noqnoqoshada
60HZ
Marxaladda
3
Quudinta
Loop
Hore
dhintay
Nooca qaboojinta
ONAN
Korantada aasaasiga ah
25D kV
Voltage Secondary
0.6Y/0.347 kV
Qalabka dabaysha
Aluminium
barokaca xagal
Dyn1
Caqabada
4.75%
Taabo Beddelka
NLTC
Riixista Range
±2*2.5%
Wax Xamuul ah ma jiro
1.4 kW
Load Lumista
8.03 kW
Agabka
Habaynta caadiga ah

 

 

1.3 Sawirro

750 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.

750 kva pad mount transformer diagram 750 kva pad mount transformer nameplate

 

 

02 Wax-soo-saarka

2.1 Core

Qalabkan 750kVA ah -Transformer-ka rakiban waxa uu adeegsadaa - darajo sare oo CRGO ah oo ku xidhan daahyada xudunta u ah sadex sax ah-waji, sadex-qaabaynta addimada. Talaabada -Laminations ee dhabta ah waxay ka kooban tahay 45 darajo kalagoysyo kala-goys ah iyo isku xidhid epoxy si loo yareeyo khasaaraha loona hubiyo xasilloonida qaabdhismeedka. Naqshadaynta labeenta ee la wanaajiyay waxa ay keentaa hufnaan sare, oo buuxinaysa heerarka CSA, oo wata koofiyadaha birta amorphous ee ikhtiyaarka ah{9}} codsiyada waxtarka sare leh. Dhismaha adagi wuxuu dammaanad qaadayaa waxqabad la isku halayn karo marka loo eego bay'ada tamarta ee dalbanaysa.

amorphous metal core

 

2.2 Dabaylaha

3 winding transformer

3-da dabaysha ee dabaysha ayaa leh saxan{1}}HV/LV-dabaylaha la farsameeyay iyadoo la isticmaalayo kirishbooyada aluminiumka oo leh walxo daaha. Dabaysha HV waxay shaqaalaysiisaa lakab{3}} nashqad boogaha, halka LV ay u adeegsato dhismo foorno/helical awood hadda sare leh. Qaabeynta 3 dabaysha ayaa awood u siinaysa beddelka korantada dabacsan. Axial/radial bracing waxay u adkeysaneysaa - xoogag wareeg ah.

 

2.3 Haanta

Beddelka taangiga saaxiibtinimada ah- waxa uu leeyahay daxal - adkaysi u leh, budo{2}}xarado bir dahaarsan oo leh sunta rasaasta{3}}Rinji bilaasha, oo bixisa ilaalinta UV iyo badbaadada deegaanka. Diiditaanka 100%{6}}Nashqada taangiga cagaaran ee aan caddayn waxay ka hortagtaa faddaraynta ciidda iyadoo la taageerayo dareeraha FR3 biodegradable. Waxaa loo naqshadeeyay joogteynta iyo waxqabadka, waxay soo saartaa hawlgal xasilloon (<65dB) and includes reinforced lifting points with optional seismic bracing.

eco-friendly tank

 

2.4 Kulanka ugu dambeeya

transformer leads

1. Isku-xidhka Dabayluhu & Cutubka Duubista

Silidh dabaylaha HV/LV ee lugaha xudunta u ah, hubinta meelaynta dahaarka habboon.

Geli harqoodyada harqoodka oo xir xudunta si aad u sameysid wareeg magnet oo dhamaystiran.

2. Isku xirka Korontada

Ku xidh hogaanka adoo isticmaalaya alxanka ama bolting, beddelayaasha siliga tuubada, baadiyaha, iyo marinada kale; xaqiiji fasaxyada.

3. Qalajinta Qaybta Firfircoon

Ku wareeji qaybta firfircoon (xuddunka + dabaysha) foornada si aad hawo u qallajiso faakiyuum{1}}kuleyl{2}}ilaa qoyaanku ka soo baxo heerarka.

4. Rakibaadda Haamaha

Ku rid qaybta firfircoon ee engegan taangiga, toosi, oo ku xafid boolal isku dhejis ah; xidh daboolka haanta.

5. Kordhinta Agabka

Ku rakib qalabyada sida baadiyaha, aaladaha cadaadiska cadaadiska, cabirada saliidda, fiyuuska bayooliska, iyo xadhkaha kontoroolka.

6. Saliida Buuxinta & Xidhida

Vacuum-ku buuxi saliid dahaarka ilaa heerka la cayimay. Ka dib markaad dejiso, tijaabi xoogga dielectric saliidda iyo qoyaanka; samee baaritaanada ugu dambeeya ee daadinta.

 

 

03 Tijaabinta

Maya

Shayga Tijaabada

Unug

Qiimaha Ogolaanshaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbiraadaha iska caabinta

%

Qiyaasta dheelitir la'aanta iska caabbinta ugu badan

0.81

Gudub

2

Imtixaanada saamiga

%

Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5%

0.00

Gudub

3

wajiga- imtixaanada xidhiidhka

/

Dyn1

Dyn1

Gudub

4

Maya- khasaarooyinka rarida iyo xamaasadda hadda

/

I0 :: bixiyaan qiime la qiyaasay

0.53%

Gudub

P0: bixi qiimaha la qiyaasay

1.197kW

Dulqaadka wax qabad la'aan waa +10%

/

5

Load khasaaraha danab impedance iyo hufnaan

/

t:85 darajo

dulqaadka impedance waa ± 7.5%

dulqaadka wadarta rarka luminta waa +6%

/

Gudub

Z%: qiimaha la qiyaasay

4.55%

Pk: qiimaha la qiyaasay

7.325kW

Pt: qiimaha la qiyaasay

8.522kW

Waxtarka aan ka yarayn 99.15%

99.25%

6

Tijaabada Korantada ee La dabaqay

kV

HV: 50kV 60s

LV: 10kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada adkaysiga korantada ee keentay

kV

Danab la dabaqay (KV):

2 Uur

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

Muddada:48

Inta jeer (HZ): 150

8

Tijaabada daadinta

kPa

Cadaadiska la dabaqay: 20kPA

Muddada: 12h

Wax daadsan iyo maya

Waxyeello

Gudub

9

Cabbirka iska caabinta dahaarka

GΩ

HV -LV ilaa Ground

10.6

/

LV-HV ilaa Ground

10.4

HV&LV ilaa Ground

9.12

10

Tijaabada Saliida

/

Xoogga Dielectric;

57.3 kV

Gudub

Nuxurka qoyaanka

9.9 mg/kg

Qodobka Burburinta

0.00247%

Falanqaynta Furan

0.03

Falanqaynta Chromatography ee Gaaska

/

 

750 kva pad mount transformer test
pad mount transformer routine test

 

 

04 Baakaynta iyo dhoofinta

4.1 Xirxirida

Xirmada koronto-bixiyeha{0}ku rakiban waxay adeegsataa sanduuq alwaax adag ah oo lagu xoojiyay xadhkaha birta ah, oo leh meelo fargeeto ah ama dhibco kor loogu qaado wax ka qabashada. Cutubku wuxuu ku hubsaday saqafka alwaax ee gudaha sanduuqa, oo lagu daboolay xumbo ama caag si uu u nuugo shoogyada. Alaabta lagu xidho ayaa si gooni ah loogu soo ururiyey qaybo lakabyo ah. Banaanka waxaa lagu daboolay baco aan biyuhu lahayn oo ay ku jiraan bacaha qallajiya, halka calaamaduhu ay tilmaamayaan xudunta cufisjiidka, ilaalinta qoyaanka, "Ha leexin," iyo tilmaamo farsamo. Nakhshad xidhmadan wax beddelka ahi waxa ay hubisaa in aanay shoogga lahayn, qoyaanka - adkaysi u leh, iyo - ilaalinta dibadda ee muddada, oo lagu bixiyo xaalad si buuxda u xidhan si ay u sahlanaato - kormeerka goobta iyo rakibida

transformer technical specifications

 

4.2 dhoofinta

export clearance documents

suufka {{0}Mounted Transformer waxa lagu soo rari doonaa shuruudaha CIF ilaa Dekedda Vancouver, Canada. Iibiyuhu waxa uu habeeyaa gaadiidka iyo caymiska aasaasiga ah, isaga oo siinaya ISPM 15 -IsPM 15 alwaax qiiqa ah (birta{4}}ku xidhay shoog{8}}suunka nuugista) iyo maaraynta dukumentiyada fasaxa dhoofinta ( qaansheeg ganacsi, liis baakad, shahaadada asalka, iwm.). Rariddadu waxay isticmaashaa 40ft weelasha sare ee furan ama maro fidsan, iyada oo saldhiga transformer-ku alxanayo lana daalacday si loo sugo, oo ay la socoto la socodka heerkulka inta lagu jiro safarka. Daboolista caymiska. Dekadda Vancouver waxay u baahantahay in horay loogu dhawaaqo nooca saliidda beddelka (oo raacaya xeerarka EPA-ga Kanada), shahaado CSA (haddii ay khusayso), iyo jadwalka daaqadda hirarka ee dejinta. Dukumeentiyadu waa inay ku jiraan Bill of Lading (oo leh CCN Kanada) iyo warbixinta saliidda ee MSDS.

 

 

05 Goobta iyo Kooban

Iyada oo ah tiirka nidaamka qaybinta awooda, suufkan {{0}Mounted Transformer waxa uu keenaa tamar la isku halayn karo, hufan, iyo deegaan -saaxiibtinimo beddelka tamarta warshadaha, ganacsiga, iyo kaabayaasha dadweynaha. Lagu farsameeyay bir silikoon duuban oo silikoon ah dhisme si buuxda u xidhan, waxa ay hubisaa luminta hoose{4}} hawlgal degan iyada oo buuxinaysa ilaalinta IP67 iyo heerarka caalamiga ah ee adag. Naqshadeynta taangiga is haysta ayaa wanaajisa booska, iyo isku xirka kormeerka smart ayaa awood u siinaya maareynta fog. Waxaa shahaado siisay CSA/UL u hogaansanaanta Waqooyiga Ameerika, waxay dammaanad qaadaysaa waxqabadka waara ee cimilo xumida iyo - xaaladaha culayska sare - taasoo ka dhigaysa doorashada ugu fiican ee kaabayaasha casriga casriga ah.

CSA certificated

 