1500 kVA suuf ku rakiban beddelka qiimaha-0.6/13.8 kV|USA 2025

1500 kVA suuf ku rakiban beddelka qiimaha-0.6/13.8 kV|USA 2025

Dalka: Ameerika 2025
Awoodda: 1500 kVA
Voltage: 13.8GrdY/7.97-0.6Y/0.346kV
Muuqaalka: oo leh laba bushings dhibic dhexdhexaad ah LV
U dir sooji

 

 

20251029154054500177

Loogu Talo Galay Adkeysiga: Casriyeyn Shabakaddaada suufka Sadexda Waji ah -Transformer Rarkan.

 

 

01 Guud

1.1 Sharaxaada Mashruuca

1500 kVA saddex weji suuf ah oo ku rakiban transformer ayaa la geeyey Kanada 2025. Awoodda lagu qiimeeyay taransfooriyaha waa 1500 kVA oo leh qaboojin KNAN. Korontada sare waa 13.8GRDY/7.97kV oo leh ±2*2.5% taping range (NLTC), danab yar waa 0.6Y/0.346 kV, waxay samaysteen koox vector ah YNyn0.

Sadexdan -wajiga{1}ku rakiban Transformer waxa loogu talagalay qaybinta awooda sare -waxqabadka, iyada oo la isticmaalayo saliida dabiiciga ah ee FR3 deegaanka u fican waxaana lagu farsameeyay K- 4 ka mid ah si uu u maareeyo culayska iswaafajinta{6}}. Waxay ka kooban tahay nidaam ilaalin oo dhammaystiran oo ay ku jiraan shaashadda dhulka hoostiisa oo u dhaxaysa dabaylaha iyo xidhayaasha hillaaca isku dhafan. Dhanka sare - dhanka korantada waxa lagu qalabeeyay 600A midaysan -nidaamka baadiyaha iyo bash dhexdhexaad ah oo gooni ah oo leh 2{13}}dalool dalool{15}}nooca birta naxaasta ah. Midka hoose -dhinaca danabku wuxuu ka shaqeeyaa duurka xabagta leh ee leh 10-dalool oo bar naxaas ah oo ay ku jiraan laba baadiyaha dhexdhexaadka ah oo go'an. Intaa waxaa dheer, waxaa lagu rakibay laba duurka dhulka hoostiisa ah: mid loogu talagalay shaashadda HV-LV iyo mid kale oo loogu talagalay isku xirka barta dhexdhexaadka ah. Cutubka waxaa lagu ilaaliyaa buste nitrogen ah waxaana lagu dhammeeyaa qalabka caadiga ah ee cagaarka ah (Munsell 9 GY 1.5/2.6) daahan loogu talagalay adkeysiga iyo iska caabinta daxalka.

 

 

 

1.2 Tilmaamaha Farsamada

1500 kVA suuf ku rakiban nooca tafatirka beddelka iyo xaashida xogta

loo geeyey
USA
Sannadka
2025
Nooca
suuf ku rakiban transformer
Heerka
IEEE C57.12.34
Awood lagu qiimeeyay
1500 kVA
Soo noqnoqda
60HZ
Marxaladda
3
Quudinta
Loop
Hore
dhintay
Nooca qaboojinta
KNAN
Korantada aasaasiga ah
13.8GRDY/7.97 kV
Voltage Secondary
0.6Y/0.346 kV
Qalabka dabaysha
Aluminium
barokaca xagal
YNyn0
Caqabada
5.75%
Waxtarka
DOE2016,99.48%
Taabo Beddelka
NLTC
Riixista Range
±2*2.5%
Wax Xamuul ah ma jiro
1.6 kW
Load Lumista
10.27 kW

 

1.3 Sawirro

1500 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.

image003 image005

 

 

02 Wax-soo-saarka

2.1 Core

Sadexda{0}wajiga, shanta- xudunta addinka suufkan -Transformer-ka ku rakiban waxa laga dhisay -permeability silicon steel laminations. Nashqaddeeda gaarka ah waxay ka kooban tahay saddex addin oo waaweyn oo loogu talagalay guriyeynta saddexda qaybood ee dabaysha, oo ay ku dheggan yihiin laba addin oo harqood oo dheeraad ah. Isku xidhkaani waxa uu bixiyaa - dariiqa diidmada saddexaad ee qulqulka birlabeedka, si wax ku ool ah u yareeya - khasaaraha rarka iyo buuqa hawlgalka. Intaa waxaa dheer, waxay si weyn u wanaajisaa awoodda transformer-ku u leeyahay in uu u adkeysto culeysyada aan dheellitirneyn oo uu maareeyo qulqulka iswaafajinta.

image007

 

2.2 Dabaylaha

image009

Transformer-ku waxa uu leeyahay nashqadaha dabaysha ee kala duwan ee danab sare iyo hoose. Dabaysha hoose -Voltage-ku waxa ay isticmaashaa foornada naxaasta ah, kaas oo siinaya gaagaaban oo aad u fiican Dabaylaha sare -Voltage waxaa lagu dhisay nabar silig aluminium ah oo siman, kor u qaadaya hufnaanta booska, wanaajinta qaybinta danabka, iyo kordhinta kala daadinta kulaylka. Labada dabayshaba waa faaruq{6}} waa la qalajiyey oo lagu miiray saliid dahaadhid, ka dibna si ammaan ah laysugu keenay haan adag oo shaabadaysan, hubinta awoodda makaanikada sare, khasaaraha yaraaday, iyo- isku halaynta hawlgelinta muddada dheer.

 

2.3 Haanta

Taangiga waxaa laga dhisay {{0}xoog, daxal - bir adkaysi u leh si loo hubiyo adkeysiga iyo nolosha adeeg dheer ee jawiga dibadda. Hermetically ayaa loo xidhay si looga hortago qoyaanka soo gelaya waxaana ka buuxsamay saliid dahamiya oo bixisa dahaarka korantada iyo qaboojinta labadaba. Taangigu wuxuu leeyahay naqshadeynta derbiyada la xoojiyay, taas oo u oggolaanaysa in ay u adkeyso isbeddelka cadaadiska gudaha iyo cadaadiska farsamada iyada oo la ilaalinayo jaangooyooyinka is haysta. Intaa waxaa dheer, waxay ku qalabaysan tahay baalal qaboojin oo dibadeed si kor loogu qaado kulaylka kala daadsanaanta, hubinta hawlgal xasiloon oo ku jira xaalado culeys oo kala duwan. Qalabyada ay ka midka yihiin qalabka cadaadiska cadaadiska, buuxinta valves, iyo suufka dhulka ayaa si isku mid ah loogu rakibay badbaadada iyo shaqeynta.

image011

 

2.4 Kulanka ugu dambeeya

image013

Kulanka kama dambaysta ahi waxa uu ku lug leeyahay is-dhexgalka saxda ah ee xudunta iyo isku-xidhka gariiradda, saliidda dahaadhka, iyo dhammaan agabka muhiimka ah oo loo sameeyo hal unug oo adag. Dhaawaca buuxa iyo xudunta engegan -Ururka gariiradda ayaa si taxadir leh loogu dejiyaa haanta birta ah ee xidhan, daxalka, taas oo markaa faaruq ah{3}} oo ay ka buuxdo saliid dahamiya dielectric si loo baabi'iyo wixii qoyaan ama hawo ah. Qaybaha muhiimka ah sida hiitarka dibadda, baadiyaha hoose iyo sare, beddelayaasha tuubada, aaladaha cadaadiska cadaadiska, iyo fiilooyinka ilaalinta ayaa si taxadar leh loo rakibay oo isku xiran. Isku soo wada duuboo dhamaantiis waxa lagu hayaa meel la xidhi karo, bir aan cimilo lahayn oo loogu talagalay badbaadada, adkeysiga, iyo rakibida tooska ah ee jawiga dibadda, buuxinta xal qaybinta awoodeed oo kooban oo la isku halayn karo.

 

 

03 Tijaabinta

Maya

Shayga Tijaabada

Unug

Qiimaha Ogolaanshaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbiraadaha iska caabinta

%

Heerarka dheelitir la'aanta iska caabbinta ugu badan

2.68

Gudub

2

Imtixaanada saamiga

%

Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5%

Astaanta isku xirka: YNyn0

-0.04% ~ 0.02%

Gudub

3

wajiga- imtixaanada xidhiidhka

/

YNyn0

YNyn0

Gudub

4

Maya- khasaarooyinka rarida iyo xamaasadda hadda

/

I0 :: bixiyaan qiime la qiyaasay

0.29%

Gudub

P0: bixi qiimaha la qiyaasay (t:20 darajo)

1.563kW

Dulqaadka wax qabad la'aan waa +10%

/

5

Load khasaaraha danab impedance iyo hufnaan

/

t:85 darajo

dulqaadka impedance waa ± 7.5%

dulqaadka wadarta rarka luminta waa +6%

/

Gudub

合格

Z%: qiimaha la qiyaasay

5.95%

Pk: qiimaha la qiyaasay

9.867kW

Pt: qiimaha la qiyaasay

11.430 kW

Waxtarka aan ka yarayn 99.48%

99.50%

6

Tijaabada Korantada ee La dabaqay

kV

LV: 10kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada adkaysiga korantada ee keentay

kV

Danab la dabaqay (KV):2Ur

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

Muddada:48

Inta jeer (HZ): 150

8

Tijaabada daadinta

kPa

Cadaadiska la dabaqay: 20kPA

Wax daadsan iyo maya

Waxyeello

Gudub

Muddada:24h

9

Cabbirka iska caabinta dahaarka

HV -LV to Ground :

0.887

/

LV-HV ilaa Dhulka:

1.14

HV&LV ilaa Ground

0.623

10

Tijaabada dareenka hillaaca

kV

hir buuxa

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

 

image015
image017

 

 

04 Baakaynta iyo dhoofinta

4.1 Xirxirida

Marka hore, dhig lakabka shandad bireed ee daasadda ah saxaaradda wax beddelka ka dibna ku dabool beddelka. Qalajiyaha geli bacda daasadaha, ka dibna xir bacda markaad ka baxayso meel bannaan. Isticmaal faakuum nadiifiye si aad gaaska uga soo saartid bacda dhex-furkan, ka dibna ku xidh furka mashiinka wax lagu xidho. Marka xigta, ku dheji ilaalinta geesaha agagaarka transformerka (qalabka ilaalinta geesku waxay noqon karaan xumbo, balaastiig ama kartoonnada geesaha, iyo ilaalinta geesaha kartoonada waxay ka samaysan yihiin kartoon gaar ah oo la riixay), oo ku duub transformerka filim ilaalin ah. Ugu dambeyntii, samee baakadaha dibadda ee sanduuqa alwaax, iyo sanduuqa alwaax waa in lagu buufiyaa calaamadaha forklift iyo bartamaha calaamadaha cuf-jiidadka.

 

4.2 dhoofinta

Transformer-ka waxaa lagu rari doonaa shuruudaha DDU (Delivered Duty Unpaid) ilaa meesha ugu dambeysa. Transformer-ka, oo si ammaan ah loo jeexjeexay oo lagu xannibay weelka xamuulka ee badda si looga hortago beddelidda, waxaa lagu rari doonaa iyada oo la adeegsanayo isku-darka xamuulka badda iyo gaadiidka xamuulka ah ee ugu dambeeya. Iibiyuhu waxa uu qaadanayaa dhammaan khataraha iyo kharashaadka, oo ay ku jiraan gaadiidka gudaha, dhoofinta dhoofinta, xamuulka caalamiga ah, fasaxa kastamka, dhammaan cashuuraha/canshuurta (marka laga reebo cashuuraha/canshuurta soo dejinta Maraykanka, kuwaas oo loogu talagalay koontada iibsadaha halkii shuruudood ee DDU), keenista wadada kama dambaysta ah, iyo caymis buuxa. Bixinta waxa la dhammeeyaa keliya marka cutubka si badbaado leh looga dejiyo oo lagu soo bandhigo goobta loo qoondeeyey ee ciwaanka loo socdo.

 

 

05 Goobta iyo Kooban

Sida xudunta u ah shabakadaha qaybinta casriga ah, saddexdayada-xadhkaha wejiga{1}ku rakiban transformers waxa ay dhexgalaan nakhshad adag, farsamayaqaan sare, iyo tijaabo adag si loo hubiyo -mudad dheer, waxqabad la isku halayn karo ee deegaan kala duwan oo baahi badan leh. Waxaa naga go'an inaan gaarsiino kaliya alaab, laakiin wadarta xalalka awooda iyo taageero farsamo oo buuxda-. Doorashada xalalkeena waxay ka dhigan tahay maalgelinta badbaadada, hufnaanta, iyo adkeysiga{6}} awood ku siinaysa inaad dhisto nidaam qaybinta caaqil iyo caqli badan.

20251029154054501177

 