1500 kVA suuf ku rakiban beddelka qiimaha-23.9/0.416 Kv|Jamaica 2025
Awoodda: 1500 kVA
Voltage: 23.9GrdY/13.8-0.416y/0.24kV
Feature: leh fur jabinta

Awood la isku halayn karo, si badbaado leh u dhisan – suufkayaga -Badelayayaasha Raran ayaa ku sii wadi doona.
01 Guud
1.1 Sharaxaada Mashruuca
1500 kVA saddex weji suuf ah oo ku rakiban transformer ayaa la geeyey Jamaica sanadka 2025. Awooda lagu qiimeeyay transformerku waa 1500 kVA oo leh ONAN qaboojin. Korantada aasaasiga ah waa 23.9GrdY / 13.8 kV oo leh ± 2 * 2.5% cabirka garaaca (NLTC), danab labaad waa 0.416y / 0.24 kV, waxay sameeyeen koox vector ah YNyn0.
Qalabkan 1500kVA ah-Transformer-ka lagu rakibay waa unug qaybineed adag, saliid{2}}ka buuxa oo loogu talagalay codsiyada tamarta dhulka hoostiisa ah iyo kuwa bannaanka ee la isku halayn karo. Ku dhexjira meel aan cimiladu lahayn, daxal - xidhidh bir ah oo adkaysi u leh, waxay ka kooban tahay badbaadada lama huraanka ah iyo qaybaha hawlgalka, oo ay ku jiraan fiyuusyada bayonetka iyo kuwa hadda - xaddidaya fiyuusyada ilaalinta culayska badan, aaladda cadaadiska cadaadiska iyo cabbiraadda cadaadiska faakuumka ee la socodka cadaadiska gudaha, iyo heerkulbeeg saliid leh tilmaame heerka dareere ah ee maaraynta kulaylka ugu habboon. Cutubku waxa uu ku qalabaysan yahay fur jabinta culayska oo geli koofiyad boodh ah si loogu beddelo culayska badbaadada leh, oo ay weheliso damin{7}} beddelka wareegga hagaajinta korantada. Ku habboon xadhkaha korantada ee magaalooyinka, goobaha warshadaha, iyo is dhexgalka tamarta la cusboonaysiin karo, transformer-kani waxa uu hubinayaa waxtarka sare, dayactirka hooseeya, iyo u hogaansanaanta heerka badbaadada warshadaha. Nashqaddeeda is haysta, tamper{10}naqshadeeda adkaysi u leh waxay keentaa qaybinta awood la isku halayn karo iyadoo taageerta isku xidhka xariijimaha caqliga leh ee mustaqbalka.
1.2 Tilmaamaha Farsamada
1500 KVA suuf ku rakiban nooca tafatirka tafatirka iyo xaashida xogta
|
loo geeyey
Jamaica
|
|
Sannadka
2025
|
|
Nooca
suuf ku rakiban transformer
|
|
Heerka
IEEE StdC57.12.34-2022
|
|
Awood lagu qiimeeyay
1500 kVA
|
|
Soo noqnoqoshada
50HZ
|
|
Marxaladda
3
|
|
Quudinta
Loop
|
|
Hore
dhintay
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
23.9GrdY/13.8kV
|
|
Voltage Secondary
0.416y/0.24 kV
|
|
Qalabka dabaysha
Aluminium
|
|
barokaca xagal
YNyn0
|
|
Caqabada
5%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
1.8 kW
|
|
Load Lumista
16.8 kW
|
|
Agabka
Habaynta caadiga ah
|
1.3 Sawirro
1500 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Qaab dhismeedka shanta ah - (saddexda addin ee waaweyn + labada addin ee soo laabashada) waxay wanaajisaa summaynta qulqulka, yaraynaysaa jiidashada magnetka ee aan dheeli tirnayn waxayna yaraynaysaa - khasaarooyinka rarka. Maaraynta wanaagsan ee qulqulka iswaafajinta iyo eexda DC ee xadhkaha korantada casriga ah. Xudunta birta silikoon ee xidhan waxay yaraynaysaa khasaaraha hadda jira, taas oo keenta hawlgal aamusnaan ah -ku habboon rakibaadaha magaalada. Dhismaha asaasiga ah ee adag wuxuu u adkeysanayaa - xoogag wareeg ah, kor u qaadaya isku halaynta beddelka Dariiqa qulqulka ee la hagaajiyay waxa ay yaraynaysaa soo saarista kulaylka, iyada oo hagaajinaysa maaraynta kulaylka ee saliidda{9}} haanta ka buuxsantay.

2.2 Dabaylaha

Sadexda -wajiga -Transformer-ku rakiban waxa uu leeyahay bireed horumarsan - boogta LV (hoose -voltage) dabaysha iyo lakab{4}} nakhshad dabaysha HV (sare{5}}voltage), hubinta waxqabadka ugu fiican iyo isku halaynta. Dabaysha LV waxa ay isticmaashaa-kuleelka naxaasta leh ee saraysa, kaas oo siinaya heer aad u fiican-karti u adkeysiga wareega iyo kala daadinta kulaylka hufan. Dabaysha HV waxay shaqaalaysiisaa saxan -lakab{11}]
Muhiimka u ah naqshadeynta waa giraanta xagasha, oo si xeeladaysan loo meeleeyay cidhifyada dabaysha iyo dhibcooyinka walaaca si loo xakameeyo qaybinta goobta korantada, la yareeyo dheecaanka qayb ka mid ah, loona wanaajiyo xoogga dielectric. Isku darka foil{1}} nabarka LV iyo lakabka - nabarka HV, oo ay weheliso dahaarka la xoojiyay iyo giraanta xagasha, waxay hubisaa waxtarka sare, xasiloonida kulaylka, iyo cimri dhererka{3} cimri dhererka dalabaadka codsiyada qaybinta awooda.
2.3 Haanta
Taangiga saddexda-wajiga-Transformer-ku rakiban yahay waa sax{2}}waxaa laga soo farsameeyay hoose{3}}taarikada birta kaarboon (Q235B) iyada oo loo marayo hab wax soo saar adag. Waxay ku bilaabataa goynta leysarka CNC iyo foorarsiga saxnaanta cabbirka, oo ay ku xigto alxanka arc quuska ah (SAW) ee tolmada waaweyn, kaas oo mara X-ray/baadhista ultrasonic si loo hubiyo sharafta qaabdhismeedka. Oogada haanta waa la toogtaa -qaraxay ( darajada Sa2.5) waxaana lagu daaweeyaa nidaam dahaadh badan oo lakabka ah, oo ay ku jiraan epoxy primer (80-100 μm) iyo polyurethane topcoat (60-80 μm) ee iska caabinta cimilada.
Ka hor inta aan la isku keenin, taangiga waxaa la mariyaa tijaabada cadaadiska 50 kPa iyo ogaanshaha daadinta helium si loo xaqiijiyo xajinta hawada. Nashqadan adag, daadinta{2}Naqshadda caddayntu waxay hubisaa nolosha adeeg ka badan 30 sano, iyada oo u hoggaansanta IEEE C57.12.25 iyo IEC 60076 heerarka.

2.4 Kulanka ugu dambeeya

1. Rakibaadda Dabaysha iyo Isku-xidhka Muhiimka ah:
Ka saar harqoodyada sare ee xudunta, ka dibna ku dheji dabaylaha HV/LV ee lugaha xudunta u ah, hubinta isku xidhka dahaarka saxda ah iyo hagaajinta farsamada.
Talaabada Furaha: Dib ugu geli harqoodyada sare ee harqoodka sare mid mid si is dhexgal ah si loo yareeyo diidmada birlabeedka. Ku hubso qalabka isku dhejinta oo xaqiiji dejinta ubucda ah iyo wax - khasaare ah
2. Isku xirka Korontada:Dhameystir alxanka rasaasta ama isku xirka xirmooyinka, rakib beddelayaasha tuubada, oo duub walxaha dahaarka.
3. Qalajinta xudunta iyo gariiradda:Geli dhammaan qaybta firfircoon ee foornada qallajisa si aad u kululeyso faakuumka si aad uga saarto qoyaanka. Ka saar marka caabbinta dahaarka ay buuxiso heerarka.
4. Golaha Haamaha:Ku rid qaybta firfircoon ee engegan taangiga, xidh daboolka, oo hubi qaboojinta hawada.
5. Rakibaadda Agabka:Ku rakib bushings, qalabka cadaadiska cadaadiska, cabbirada heerka saliidda iyo qalabyada kale.
6. Buuxinta Saliidda iyo Joogsiga:Ku buuxi saliid dahaarka hoostiisa maraq ilaa laga gaarayo heerka saliidda caadiga ah.
03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
% |
Heerarka dheelitir la'aanta iska caabbinta ugu badan |
2.77 |
Gudub |
|
2 |
Imtixaanada saamiga |
% |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: YNyn0 |
-0.04% ~ 0.08% |
Gudub |
|
3 |
wajiga- imtixaanada xidhiidhka |
/ |
YNyn0 |
YNyn0 |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
/ |
I0 :: bixiyaan qiime la qiyaasay |
0.24% |
Gudub |
|
P0: bixi qiimaha la qiyaasay (t:20 darajo) |
1.599kW |
||||
|
Dulqaadka wax qabad la'aan waa +10% |
/ |
||||
|
5 |
Load khasaaraha danab impedance iyo hufnaan |
/ |
t:85 darajo dulqaadka impedance waa ± 7.5% dulqaadka wadarta rarka luminta waa +6% |
/ |
Gudub 合格 |
|
Z%: qiimaha la qiyaasay |
5.37% |
||||
|
Pk: qiimaha la qiyaasay |
15.863kW |
||||
|
Pt: qiimaha la qiyaasay |
17.462 kW |
||||
|
Waxtarka aan ka yarayn 99.26% |
99.31% |
||||
|
6 |
Tijaabada Korantada ee La dabaqay |
kV |
HV: 10kV 60s LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
kV |
Danab la dabaqay (KV):2Ur |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
Muddada:40 |
|||||
|
Inta jeer (HZ): 150 |
|||||
|
8 |
Tijaabada daadinta |
kPa |
Cadaadis la dabaqay: 50kPA |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
Muddada:12h |
|||||
|
9 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV -LV to Ground : |
16.3 |
/ |
|
LV-HV ilaa Dhulka: |
22.5 |
||||
|
10 |
Tijaabada Dielectric Oil |
kV |
Ka weyn ama la mid ah 45 |
57.6 |
Gudub |


04 Baakaynta iyo dhoofinta
4.1 Xirxirida
1. Ilaalinta qoyaanka - Ku rakib qalajiyaha gudaha unugga ka hor inta aan la xidhin faakuumka.
2. Agabka - Raad - beddel usha qalliinka ee lagu rakibay taageerada alwaax; T -furaha lagu daray unug kasta.
3. Saldhig - Qoryo adag oo alwaax ah oo leh xoojinta birta.
4. Leak Check - Saliid - warqada wax lagu ogaanayo ku hoos geli qalabka wax beddelka.
5. Xidhid - Vacuum -ku xidh bacda xaashiyaha adiga oo isticmaalaya xidhidhiyaha warshadaha.
6. Ilaalinta - Ku rakib ilaalada geesaha oo si adag ugu duub filim.
7. Calaamadaynta - Si cad u calaamadee dhibcaha fargeetada iyo xarunta cufisjiidka.

4.2 dhoofinta

Xirmada 1500kVA{1}ku rakiban, oo ay weheliso unug 500kVA ah, waxa lagu soo rari doonaa shuruudaha CIF iyada oo la geynayo dekedda Kingston. Iibiyuhu waxa uu u habeeyaa gaadiidka gudaha ee ka yimaada warshada ilaa dekeda raritaanka isaga oo isticmaalaya{4}} baabuur xamuul ah oo adag oo leh xidhid sugan, oo ay ku xigto xamuulka badweynta iyada oo loo sii marayo sidayaal (tusaale, MSC ama Maersk). Haddii transformers-ku ay ku habboon yihiin cabbirrada weelka, 40'HQ ama rakado fidsan ayaa la isticmaali doonaa; haddii kale, rarida jaban ayaa khuseysa.
Safarka badda wuxuu qaataa qiyaastii 25-35 maalmood, iyadoo iibiyuhu uu daboolayo Dhammaan Khataraha safarka oo dhan. Marka uu yimaado Kingston, iibsaduhu waxa uu gacanta ku hayaa fasaxa kastamka iyo dejinta, halka iibiyuhu uu bixiyo dukumentiyada rarida oo buuxa (tusaale, B/L, siyaasadda caymiska).
05 Goobta iyo Kooban
Nakhshad is haysta, hufnaan sare, iyo la qabsiga deegaanka ee aadka u wanaagsan, suufkayada{0}ku rakibay Transformers ayaa ah doorashada ugu habboon ee awood qaybinta magaalooyinka, xarumaha warshadaha, iyo mashaariicda tamarta la cusboonaysiin karo. Lagu soo saaray heerar caalami ah oo adag, waxay keenaan badbaado, la isku halayn karo, oo hooseeya-waxqabadka dayactirka. waxaanu bixinaa habayn la habeeyey si loo daboolo baahiyaha kala duwan ee arjiga, doorashadayada suufka -Transformers ee rakiban macnaheedu waa maalgelinta xasiloonida awooda muddada dheer iyo taageerada farsamo ee khabiirka ah. Faahfaahin dheeraad ah, waxaad xor u tahay inaad la xiriirto kooxdayada maanta!

Hot Tags: 1500 kva suuf ku rakiban qiimaha transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
75 kVA 3 Wajiga suufka Buur beddelka-24.94/0.208 kV|...
225 kVA Pad Mount Transformer-34.5/0.208 kV|USA 2024
300 kVA Saliid Buuxiyey Beddelka-13.2 / 0.48 kV|Guya...
500 kVA suuf ku rakiban beddelka qiimaha-22.86/0.208...
500 kVA Utility Pad Ku rakiban Beddelka-24/0.48 kV|U...
1000 kVA Dhintay Beddelka Hore-24/0.48 kV|USA 2024
U dir sooji