100 kVA Tiirka Ku rakiban Beddelka-7.97/0.12*0.24 kV|Kanada 2024

100 kVA Tiirka Ku rakiban Beddelka-7.97/0.12*0.24 kV|Kanada 2024

Dalka: Kanada 2024
Awoodda: 100kVA
Voltage: 13.8/0.24kV
Feature: oo leh qalabka cadaadiska cadaadiska
U dir sooji

 

 

100 kva pole mounted transformer

Tamarta tiirka, xoogga wadnaha - Keliya-Tiirka wejiga{1}}ku rakiban koronto, samaynta koronto heer sare ah.

 

01 Guud

1.1 Asalkii Mashruuca

SCOTECH waxa ay ku faraxsantahay in ay bixiso - tayadeedu sarayso- Hal -Transformer-ka wejiga ahi waxa uu awood u leeyahay 100kVA, danabka aasaasiga ahi waa 7.97/13.8Y iyo danabka labaad waa 0.12/0.24kV, kaas oo si fudud u dabooli kara baahida korontada ee deegaanka. Tiirka hal wejiga ah ee ku rakiban transformer-ka wuxuu u beddelaa danabka shabkada korantada looga baahan yahay nidaamka ama culeyska, wuxuuna garwaaqsadaa gudbinta iyo qaybinta tamarta korontada. -shaqada baaxada leh ee alaabtani waxay gaadhi kartaa saamayn tamareed oo wanaagsan waxayna yaraynaysaa wasakhowga hawada. Alaabtani waxay si gaar ah ugu habboon tahay koronto yaraan iyo isbedbeddelka culeyska oo ay adag tahay in lagu sameeyo dayactir maalinle ah meelaha. Sababtoo ah Transformer-ku wuxuu qaataa qaab-dhismeed si buuxda u xiran, saliidda daboolaya iyo kuwa daboolaya ma aha mid nijaaseynaya jawiga, sidaas darteed waxay ku shaqeyn kartaa jawi qoyan, waana qalabka ugu habboon ee qaybinta shabakada ballaaran ee magaalooyinka iyo dhulka miyiga ah. Single{15}Transformers waxay si gaar ah ugu habboon yihiin xadhkaha korontada ee miyiga, meelaha buuraleyda fog fog, tuulooyinka kala firirsan, wax soo saarka beeraha, nalka iyo isticmaalka korontada. Waxa kale oo loo isticmaali karaa jidka tareenka, tamarta korantada magaalada{17}}badbaadinta isbeddelka tiirka nooca qaybinta khadadka qaybinta, waxay noqon kartaa hal{18}} hawlgal weji ah ama saddex hal -kooxaha weji sida saddex{20} hawlgal waji.

Qalabkeena 100 kVA ee ku dhejisan tiirka waxaa loogu talagalay tignoolajiyada horumarsan wuxuuna qaataa walxo tayo sare leh iyo qaybo taas oo keenta tayo la isku halayn karo iyo waqti dheer oo hawlgal ah.

 

 

1.2 Tilmaamaha Farsamada

100 kVA nooca tafatirka beddelka iyo xaashida xogta

loo geeyey
Kanada
Sannadka
2024
Nooca
Transformer ku rakiban tiirarka
Heerka
IEEE C57.12.20
Awood lagu qiimeeyay
100kVA
Dabaylaha
Aluminium
Polarity
Wax lagu daro
Soo noqnoqoshada
60HZ
Marxaladda
1
Nooca qaboojinta
ONAN
Korantada aasaasiga ah
7.97/13.8Y kV
Dual Primary Voltage
Maya
Voltage Secondary
0.24/0.12 kV
Kooxda Vector
Ii0
Caqabada
2.2%
Taabo Beddelka
NLTC
Insulant dareere ah
Saliidda Macdanta
Riixista Range
±2*2.5%
Wax Xamuul ah ma jiro
0.068kW
Load Lumista
0.98kW
Dulqaad
10% NLL, 6% Wadarta khasaaraha
Agabka
Habaynta caadiga ah

 

1.3 Sawirro

100 kVA tiir ku rakiban jaantuska beddelka sawirka iyo cabbirka.

100 kva pole mounted transformer diagram 100 kva pole mounted transformer nameplate

 

 

02 Wax-soo-saarka

2.1 Core

Faa'iidooyinka xudunta gariiradda transformer ayaa inta badan ka muuqda waxqabadkeeda korantada ee aad u wanaagsan iyo awoodda gudbinta tamarta hufan. Waxtarka is-beddelka waa la wanaajiyey sababtoo ah habka dabaysha ayaa yareynaya farqiga hawada iyo luminta. Naqshadani waxay caawisaa dhimista qaylada iyo gariir waxayna hagaajinaysaa waxqabadka guud. Xudunta gariiradda ayaa si wax ku ool ah u yareeyn karta khasaaraha hadda jira sababtoo ah qaybinta qulqulka labbiska ah. Intaa waxaa dheer, geeddi-socodka duubista wuxuu bixiyaa qaab-dhismeed adag, wuxuu hagaajiyaa xoogga farsamada iyo cimri dhererka, iyo ADAPTS heerkul sare iyo jawi qoyan. Xuddunta gariiradda ayaa sidoo kale yaraynaysa qaylada iyo gariirka hawlgalka, samaynta qalabku mid xasiloon, awood u leh inuu la qabsado jawiga shaqada ee kala duwan, iyo kordhinta nolosha adeegga qalabka.

100 kva pole mounted transformer iron core

 

2.2 Dabaylaha

Iyada oo qayb ka ah dabaysha, dabaylaha foil hooseeya - korantada dabaysha ayaa si wax ku ool ah u ilaalin karta goobta korantada ee sare -voltage winding, sidaas darteed hoos u dhigida saamaynta faragelinta korantada (EMI). Marka transformer-ku uu meel la wadaago aaladaha kale ee elektiroonigga ah, waxa ay yarayn kartaa faragelinta u dhaxaysa aaladaha elegtarooniga ah oo ay wanaajiso ku-habboonka korantada ee nidaamka guud. Iyada oo qayb ka ah dabaysha, dabaylaha foil hooseeya ee -ku-wareejinta korantada ayaa si wax ku ool ah u ilaalin karta goobta korantada ee sare -, sidaas darteed hoos u dhigidda faragelinta korantada (EMI). Marka transformer-ku uu meel la wadaago aaladaha kale ee elektiroonigga ah, waxa ay yarayn kartaa faragelinta u dhaxaysa aaladaha elegtarooniga ah oo ay wanaajiso ku-habboonka korantada ee nidaamka guud. Sababo la xiriira sifooyinka qaab dhismeedka hoose ee dabaylaha foil-ka, waxa ay si wax ku ool ah u kala firdhi kartaa kulaylka maxaliga ah ee ay dhaliso qaladka wareegga gaaban, waxa ay yaraynaysaa halista saamaynta degdega ah ee hadda socda ee wareegga gaaban ee dabaysha, oo wanaajiso badbaadada iyo isku halaynta beddelka. Qaabka macquulka ah ee hooseeya{10}voltage iyo sare{11}Nashqada dabaysha danabku waxa ay si wax ku ool ah u dhimi kartaa ifafaale daadinta birlabeedka waxa ayna sii wanaajisaa hufnaanta tamarta iyo wax qabadka isbedbedelka. Marka la wanaajiyo habaynta u dhaxaysa dabaylaha, isku xidhka qulqulka wanaagsan ayaa la gaadhi karaa, si loo hagaajiyo waxtarka guud ee transformerka.

 

2.3 Haanta

100 kva pole mounted transformer oil tank

Sida laga soo xigtay sawirada naqshadeynta, qalabka sida mashiinka goynta balaasmaha, mashiinka goynta laser ama mindida biyaha, ayaa loo isticmaalaa in lagu gooyo walxaha birta ah ee qaybaha kala duwan ee taangiga, oo ay ku jiraan saxanka hoose ee taangiga, darbiga dhinaca dhululubada, daboolka sare, iwm. Qaybaha gaarka ah ee taangiga ayaa si buuxda loo alxanayaa iyadoo la isticmaalayo habab ay ka mid yihiin alxanka gaashaanka gaaska (MIG alxanka) ama alxanka arc, alxanka waa in uu noqdaa mid isku mid ah oo siman oo leh xidhid wanaagsan. Alxanka ka dib, dusha taangiga waa in la wasakheeyaa si meesha looga saaro alxanka, lakabka oksaydhka iyo saliidda. Daaha ka-hortagga daxalka ayaa lagu buufiyaa haanta bannaankeeda si looga hortago daxalka ay keento saameynta deegaanka ee isticmaalka maalinlaha ah. Derbiga gudaha waxa kale oo lagu daawayn karaa anti-daxalka si loo kordhiyo nolosha adeegga saliidda dahaadhka.

 

2.4 Kulanka ugu dambeeya

100 kva pole mounted transformer assembly
100 kva single phase pole mounted transformer assembly

 

 

03 Tijaabinta

Maya

Shayga Tijaabada

Unug

Ogolaanshaha

Qiimaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbiraadaha iska caabinta

%

/

/

Gudub

2

Imtixaanada saamiga

%

Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5%

Astaanta isku xirka: II6

-0.02

Gudub

3

wajiga- imtixaanada xidhiidhka

/

Wax lagu daro

Wax lagu daro

Gudub

4

Maya- khasaarooyinka rarida iyo xamaasadda hadda

%

kW

t: 85 darajo

I0:  bixiyaan qiime la qiyaasay

P0: bixi qiimaha la qiyaasay

Dulqaadka wax qabad la'aan waa +10%

0.39(100%)

1.00(105%)

0.056(100%)

0.067(105%)

Gudub

5

Load khasaaraha danab impedance iyo hufnaan

%

kW

kW

t: 85 darajo

Z%: qiimaha la qiyaasay

Pk: qiimaha la qiyaasay

Pt: qiimaha la qiyaasay

Dulqaadka impedance waa ± 10%

dulqaadka wadarta rarka luminta waa +6%

2.20

0.868

0.927

99.49

Gudub

合格

6

Tijaabada Korantada ee La dabaqay

kV

HV: 34kV 60s

LV: 10kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada adkaysiga korantada ee keentay

kV

Danab la dabaqay (KV): 15.94

Muddada: 40

Inta jeer (HZ): 150

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

8

Tijaabada daadinta

kPa

Cadaadiska la dabaqay: 20kPA

Muddada: 12h

Wax daadsan iyo maya

Waxyeello

Gudub

9

Cabbirka iska caabinta dahaarka

GΩ

HV&LV ilaa Dhulka:

90.7

/

HV -LV ilaa Ground

16.4

LV-HV ilaa Ground

16.9

10

Tijaabada Dielectric Oil

kV

Ka weyn ama la mid ah 45

55.38

Gudub

11

Tijaabada dareenka hillaaca

kV

mawjad buuxda, hirka badh

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

 

100 kva pole mounted transformer testing
100 kva single phase pole mounted transformer test

 

 

04 Baakaynta iyo dhoofinta

4.1 Xirxirida

1. Ku rid qalabka qalajiyaha gudaha baakidhka beddelka, ka dibna faakiyum si aad uga fogaato miridhku intii suurtogal ah.

2. Qayb kastaa waxay ku qalabaysan tahay usha shaqada ee wareejinta culeyska, oo lagu hagaajiyay taageerada alwaax;

3. Cutub kasta waxa lagu qalabeeyay T{1}}wrench

4. Saldhig alwaax adag (bir kanaalka ayaa loo baahan yahay)

5. Ku rid warqadda tijaabada daadinta saxaaradda beddelka

6. Marka hore xidh bacda daasadaha, ka tag dalool, isticmaal faakuum nadiifiye si aad u bamgarayso, ugu dambayntiina godka kala soo bax shaabad.

7. Afarta gees ee ku wareegsan transformer-ka waxaa lagu ilaaliyaa ilaalinta geesaha ka dibna filimku waa dhaawac

8. Ku buufi aqoonsiga forklift, xarunta aqoonsiga cufisjiidka

100 kva pole mounted transformer packing

 

4.2 dhoofinta

100 kva pole mounted transformer shipping

1. Soo dejinta iyo dejinta: Qalabka kor u qaadista waxaa loo isticmaalaa habka rarista iyo dejinta si loo hubiyo in aysan jirin culeys dheeri ah oo farsamo inta lagu jiro gaadiidka transformerka.

2. Go'an: Inta lagu jiro gaadiidka, Transformer-ku wuxuu u baahan yahay in si sax ah loo hagaajiyo si looga hortago leexinta ama isku dhaca, taasoo keenta burbur farsamo.

3. Ilaalinta: Waxa loo baahan yahay in la qaado tallaabooyin lagu ilaalinayo qaybta dahaaran ee Transformer-ka iyo qaab-dhismeedka dibadda si looga hortago wasakh ama dhaawac.

 

 

05 Goobta iyo Kooban

Waad ku mahadsan tahay xiisayntaada Kelida ah-Tiirka Wajiga{1}}Tarsoome Dusha! Iyada oo ay ku jirto waxtarkeeda sare, xasilloonida, iyo cimri dhererka, alaabtan ayaa si weyn loogu isticmaalaa gudbinta awoodda kala duwan iyo xaaladaha qaybinta, bixinta xalal awoodeed oo lagu kalsoonaan karo macaamiisheena. Waxaan had iyo jeer mudnaanta siinnaa baahiyaha macaamiisha, diiradda saara hal-abuurnimada tignoolajiyada iyo horumarinta tayada, waxaana naga go'an inaan bixinno adeeg sare iyo khibrado wax soo saar. Wixii macluumaad dheeraad ah ama taageero, fadlan xor u tahay inaad nala soo xidhiidho!

100 kva pole mounted transformers

 

Hot Tags: 100 kva tiir ku rakiban transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha

U dir sooji