167 KVA cirifka ugu sarreeya-34.5 / 0.347 KV|Kanada 2025

167 KVA cirifka ugu sarreeya-34.5 / 0.347 KV|Kanada 2025

Dalka: Kanada 2025
Awoodda: 167 kVA
Voltage: 34.5D-0.347/0.6kV
Feature: oo leh xiriiriyaha dhulka
U dir sooji

 

image001

Jawaabtaada Ku Saabsan Korantada Miyiga: Tiirka Wajiga Keliya ee Kordhiyey Kala beddelka.

 

 

01 Guud

1.1 Sharaxaada Mashruuca

167 kVA hal waji oo tiir ku rakiban transformer ayaa la geeyey Kanada sanadka 2025. Awooda lagu qiimeeyey taransfooriyaha waa 167 kVA oo leh qaboojin KNAN. Korontada sare waa 34.5D kV, danab yar waa 0.347/0.6Y kV, waxay samaysteen koox ka mid ah Ii6.

Transformer waxa loo farsameeyay si uu u keeno isku hallayn iyo hufnaan gaar ah oo loogu talagalay shabakadaha qaybinta sare ee casriga ah. Transformer-kan waxa loo nashqadeeyay iyadoo maskaxda lagu hayo utility darajada, oo leh xudunta tayada sare leh ee birta silikoon iyo dabaylaha naxaasta ah si loo hubiyo khasaaraha hooseeya, habdhaqanka sareeyo, iyo-dhaqaalaha hawlgalinta muddada dheer.

Transformer-ka waxaa loo dhisay heerka saxda ah ee CSA C2.2 iyo C802.1, isagoo dammaanad qaadaya u hoggaansanaanta adag ee hufnaanta Waqooyiga Ameerika iyo shuruudaha badbaadada. Waxaa ka buuxsamay dareere FR3® deegaan ahaan u wanaagsan, oo siinaya badbaadada dabka oo la xoojiyey, dahaarka sare, iyo nolosha warqadda oo la dhimay wadarta qiimaha lahaanshaha.

Tilmaamaha hawlgelinta muhiimka ah waxaa ka mid ah 5{4}} boosas badan, 100 Amp taabka beddela ee nidaaminta korantada saxda ah, iyo kor u kaca heerkulka 65 darajo ee cimri dhererka. Transformer-ka waxa lagu goglay -waajib culus oo ah 36kV xidhxidhayaasha aasaasiga ah oo la yimid horay loogu habeeyey hanger biraha si toos ah loogu rakibo. Transformer-kani waa xalka ugu habboon, furaha furaha ee loogu adeegayo si la isku halleyn karo oo loogu adeegayo culeyska guryaha, ganacsiga, iyo miyiga, isagoo hubinaya gaarsiinta koronto ee aad ku kalsoonaan karto.

 

 

 

1.2 Tilmaamaha Farsamada

125 kVA tiirka ku rakiban qalabka beddelka nooca iyo xaashida xogta

loo geeyey
Kanada
Sannadka
2025
Nooca
Transformer ku rakiban tiirarka
Heerka
CSA C2.2-06
Awood lagu qiimeeyay
167 kVA
Soo noqnoqoshada
60HZ
Marxaladda
1
Polarity
Wax lagu daro
Nooca qaboojinta
KNAN
Korantada aasaasiga ah
34.5D kV
Voltage Secondary
0.347/0.6Y kV
Qalabka dabaysha
Copper
Kooxda Vector
II6
Caqabada
2.8%
Taabo Beddelka
N/A
Wax Xamuul ah ma jiro
0.27 kW
Load Lumista
2.36 kW

 

1.3 Sawirro

167 kVA tiirka ku rakiban jaantuska beddelka sawirka iyo cabbirka.

image003 image005

 

 

02 Wax-soo-saarka

2.1 Core

image007

Muujinaya dhisme udub-dhexaad ah oo nabar ah oo ah bir silikoon heerkeedu sareeyo-, transformerkani waxa uu gaaraa hufnaanta birlabeedka gaarka ah. Naqshad wareeg ah oo aan kala go 'lahayn waxay yaraynaysaa qulqulka qulqulka iyo khasaaraha asaasiga ah, iyadoo la siinayo awood farsamo oo dabiici ah. Tiknoolajiyadan asaasiga ah ee horumarsan kaliya maaha inay hoos u dhigto isticmaalka tamarta laakiin sidoo kale waxay hubisaa xasilloonida, hawlgal la isku halleyn karo, taasoo ka dhigaysa doorasho miyir-beeleed oo loogu talagalay nidaamyada awood qaybinta casriga ah.

 

2.2 Dabaylaha

Waxa ay soo saartaa nidaam dabaylo heer sare ah halkaas oo dabaysha hoose -Voltage ka laga sameeyey bireed naxaas ah si ay u bixiso xasilooni firfircoon oo heersare ah iyo waxqabadka kulaylka, halka sare -Voltage dabaysha ay isticmaasho silig naxaas ah oo lakabaysan si ay u hesho awood dielectric aad u fiican. Dhammaan -Dhismaha naxaasta ahi waxa uu xaqiijiyaa khasaaraha ugu yar, culayska culayska badan, iyo -kalsoonida hawlgalka muddada dheer ee dalabka codsiyada qaybinta

image009

 

2.3 Haanta

image011

Taangiga hal - tiirka wejiga - ku rakiban transformer waa xidhid bir silindrical ah, oo badiyaa ka samaysan bir leh daahan - ilaalinta Waxay leedahay baalal qaboojin oo ku dheggan dhinacyadeeda si ay u daadiyaan kulaylka waxtarka leh. Qaybta sare waa la xidhay, waxaana jira qabanqaabo kor u qaadista iyo ilaalinta, taas oo aan ilaalinaynin oo kaliya qaybaha gudaha sida dabaysha laakiin sidoo kale waxay ka caawisaa inay baabi'iso kulaylka ka dhasha hawlgalka transformer-ka.

 

2.4 Kulanka ugu dambeeya

Kulanka kama dambaysta ahi waxa uu isku xidhaa xudunta iyo dabaylaha taangi xidhan iyada oo loo marayo hab si sax ah loo xakameeyay. Tan waxaa ka mid ah qalajinta faakuumka si looga saaro qoyaanka, oo ay ku xigto buuxinta saliidda faakuumka si loo hubiyo daacadnimada ugu habboon. Qaybaha dibadda sida bushings, tuubada beddelayaasha, iyo qalabka ilaalinta ayaa markaa si habaysan loo rakibay oo la tijaabiyey, taasoo keentay in la adkeeyo, diyaarsan-Cutub adeeg oo buuxiya heerar shaqo oo adag

image013

 

 

03 Tijaabinta

Tijaabooyin loogu talagalay hal {0} cirka wejiga - transformers rakiban, oo la qabto si loo hubiyo waxqabadka, badbaadada, iyo u hoggaansanaanta heerarka sida IEEE iyo IEC 60076, sida caadiga ah waxaa ka mid ah jadwalka joogtada ah iyo qiimaynta ogaanshaha: iska caabbinta dahaarka (megger) imtixaanada waxay cabbiraan daacadnimada dahaarka u dhexeeya dabaylaha iyo dabaylaha iyo dhulka, mararka qaarkood xisaabinta xisaabinta qallayl Tijaabooyinka isu-rogid (TTR) waxay xaqiijiyaan saxnaanta beddelka korantada waxayna ogaadaan cilladaha dabaysha ama cilladaha beddelka tuubada; maya-imtixaanada culeyska (LV tamareeyay, HV furan) waxay qiyaasaan khasaaraha asaasiga ah iyo magnetizing hadda, halka gaagaaban-imtixaanada wareegga wareegga (HV tamaraysan, LV gaaban) waxay cabbiraan khasaaraha naxaasta iyo gaaban - impedance ; Tijaabooyin dheeri ah waxaa ka mid ah hubinta dabaylaha si loo xaqiijiyo isku xidhka dabaysha oo sax ah , tijaabooyinka dareeraha ee dareeraha - unugyo dahaaran , iyo tijaabooyin buuxa -mawjadaha si ay ugu adkaystaan ​​korontadu

Maya

Shayga Tijaabada

Unug

Ogolaanshaha

Qiimaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbiraadaha iska caabinta

/

/

/

Gudub

2

Imtixaanada saamiga

/

Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah ± 0.5%

Astaanta isku xirka: II6

0.08~0.11

Gudub

3

Tijaabada polarity

/

Wax lagu daro

Wax lagu daro

Gudub

4

Maya- khasaarooyinka rarida iyo xamaasadda hadda

%

I0 :: Bixi qiimaha la qiyaasay (100%)

0.21

Gudub

kW

P0: bixi qiimaha la qiyaasay (100%)

0.265

%

I0 :: Bixi qiimaha la qiyaasay (105%)

0.48

kW

P0: bixi qiimaha la qiyaasay (105%)

0.323

/

Dulqaadka wax qabad la'aan waa +0%

/

5

Load khasaaraha , danab impedance, khasaaraha guud iyo hufnaan

/

t:85 darajo

dulqaadka impedance waa ± 7.5%

dulqaadka wadarta rarka luminta waa +0%

/

Gudub

%

Z%: qiimaha la qiyaasay

2.60

kW

Pk: qiimaha la qiyaasay

2.012

kW

Pt: qiimaha la qiyaasay

2.277

%

Waxtarka aan ka yarayn 99.05%

99.14

6

Tijaabada Korantada ee La dabaqay

/

LV: 10kV 60s

HV: 50kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada adkaysiga korantada ee keentay

/

Danab la dabaqay (KV):0.694

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

Muddada:40

Inta jeer (HZ): 180

8

Cabbirka iska caabinta dahaarka

HV-LV·to·Ground

1.31

Gudub

LV-HV ilaa Ground

1.69

HV&LV ilaa Ground

2.08

9

Tijaabada daadinta

/

Cadaadiska la dabaqay: 20kPA

Wax daadsan iyo maya

Waxyeello

Gudub

Muddada: 12h

10

Tijaabada Saliida

kV

Xoogga Dielectric

51.2

Gudub

mg/kg

Nuxurka qoyaanka

179.7

%

Qodobka Burburinta

2.238

mg/kg

Falanqaynta Furan

/

/

Falanqaynta Chromatography ee Gaaska

/

 

 

04 Baakaynta iyo dhoofinta

4.1 Xirxirida

image015

Midka kaliya ee - tiirka wajiga - ku rakiban transformer-ka waxaa badanaa la baakadeeyaa iyadoo marka hore lagu duuduubo transformerka filim balaastik ah si looga ilaaliyo qoyaanka iyo boodhka. Kadibna, waxaa la geliyaa sanduuq alwaax ah oo adag, kaas oo bixiya difaac farsamo inta lagu jiro safarka. Sanduuqa alwaaxdu waxa kale oo lagu calaamadeeyay calaamado wax-ku-qabasho iyo tilmaamo si loo hubiyo qaadista iyo kaydinta saxda ah, sidaas awgeedna transformer-ka ayaa ilaalinaya inta lagu jiro gaadiidka laga soo qaadayo warshadda ilaa goobta lagu rakibay.

 

4.2 dhoofinta

Transformer-ka waxaa lagu bixiyaa shuruudaha CIF (Qiimaha, Caymiska, iyo Xamuulka) ee dekedda Montreal. Qiimaha waxaa ku jira dhammaan kharashyada gaadiidka badda iyo caymiska ilaa dekedda loo socdo. Dhammaan dukumeentiyada rarida lagama maarmaanka ah - oo ay ku jiraan biilasha rarista, shahaadada caymiska, iyo qaansheegta ganacsiga - ayaa la bixin doonaa si loo fududeeyo fasaxa kastamka ee Montreal.

image017

 

 

05 Goobta iyo Kooban

Isku soo wada duuboo, tiirkayaga hal - wajiga -ku dhejiyay taransfoorayaasha waxa uu keenaa qiime aan caadi ahayn iyada oo loo marayo naqshadaynteeda iyo dhismaheeda adag. Marka la isku daro - tignoolajiyada xudunta u ah hufnaanta sare, habab dabaylo la isku halayn karo, iyo ilaalinta taangiga waarta, waxa ay hubisaa -waxqabadka muddada dheer ee kharashyada meertada nolosha Transformer-kani waxa uu u taagan yahay maalgashi caqli-gal ah oo loogu talagalay yutiilitida kuwaas oo doonaya in ay kor u qaadaan isku halaynta xadhkaha iyadoo la ilaalinayo dhaqaalaha shaqaynta, taas oo ka dhigaysa doorashada ugu habboon ee shabakadaha qaybinta casriga ah.