50 kVA Waji Keli ah Tiirka Ku Rakiban Qaybinta Qaybinta-13.8/0.12/0.24 kV|Guyana 2025
Awoodda: 50kVA
Voltage: 13.8-0.12/0.24kV
Feature: oo leh qalabka cadaadiska cadaadiska

Cimilada {{0}U adkaysta, Had iyo jeer shid – Cirifka -Badelayaasha Rakaabka ah ee Haynaya Laydhka.
01 Guud
1.1 Sharaxaada Mashruuca
50 kVA hal waji oo tiir ku rakiban transformer ayaa la geeyey Guyana sanadka 2025. Awoodda la qiimeeyay ee transformerku waa 50 kVA oo leh ONAN qaboojin. Korantada aasaasiga ah waa 13.8 kV oo leh ± 2 * 2.5% garaacid (NLTC), danab labaad waa 0.12 / 0.24 kV, waxay sameeyeen koox vector ah Ii0.
Tiirkan 50kVA{1}ku rakiban transformer-ka waxa loo nashqadeeyay si waafaqsan heerarka IEEE, hubinta waxqabadka la isku halayn karo iyo adkeysiga codsiyada qaybinta dibadda Waxa ay soo saartaa dhismo adag oo leh qaybo lagama maarmaan ah sida aaladda cadaadiska cadaadiska si kor loogu qaado badbaadada iyada oo laga hortagayo xaaladaha cadaadiska xad dhaafka ah iyo daminta- beddelka tuubada wareega ee hagaajinta korantada dabacsan si loo waafajiyo shuruudaha culeyska ee kala duwan. Transformer-ku waxa uu ku qalabaysan yahay isha - nooca terminal (bushings eyelet), oo fududaynaya isku xidhka sugan oo hufan ee xadhkaha sare. Tiirkeeda -Naqshadaynta rakiban waxay wanaajisaa ka faa'iidaysiga booska iyadoo la bixinayo qaybinta tamarta wax ku oolka ah ee miyiga, xaafadaha, ama goobaha warshadaha. Waxaa loo farsameeyay wax ku oolnimada iyo cimri dhererka, Transformer-kani wuxuu ku habboon yahay isticmaalka iyo isticmaalka ganacsiga, isagoo keenaya awood deggan oo ku hoos jirta xaalado shaqo oo kala duwan.
1.2 Tilmaamaha Farsamada
50 kVA tiirka ku rakiban qalabka beddelka nooca iyo xaashida xogta
|
loo geeyey
Guyana
|
|
Sannadka
2025
|
|
Nooca
Transformer ku rakiban tiirarka
|
|
Heerka
IEEE&ANSI C57.12.00
|
|
Awood lagu qiimeeyay
50 kVA
|
|
Soo noqnoqda
60HZ
|
|
Marxaladda
1
|
|
Polarity
Kala goyn
|
|
Nooca qaboojinta
ONAN
|
|
Korantada aasaasiga ah
13.8 kV
|
|
Voltage Secondary
0.12 / 0.24 kV
|
|
Qalabka dabaysha
Copper
|
|
barokaca xagal
Ii0
|
|
Caqabada
2%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
0.16 kW
|
|
Load Lumista
0.512 kW
|
|
Agabka
Habaynta caadiga ah
|
1.3 Sawirro
50 kVA tiir ku rakiban jaantuska beddelka sawirka iyo cabbirka.

02 Wax-soo-saarka
2.1 Core
Xarigga birta silikoonku wuxuu si wareeg ah u dhaawacmay mashiinka dabaysha ee CNC si uu u sameeyo qaab dhismeedka leydi xiran ama toroidal. Xiisadda si taxadar leh ayaa loo xakameeyaa inta lagu jiro dabaylaha si looga fogaado walaaca{1}} xumeynta magnetic. Annealing waxaa lagu sameeyaa jawi hydrogen ah at 800 ~ 850 digrii si loo yareeyo walbahaarka farsamada iyo soo celinta permeability magnetic fiicnayn. Hal dhinac oo xudunta ka mid ah ayaa sax ah{6}}la gooyay si loogu ogolaado galinta gariiradda, iyada oo dusha sare ee la gooyey ay si fiican dhulka u dhigtay si loo yareeyo iska caabbinta magnetka. Keliya -Tirka wajiga-Transformers-ku rakiban ee leh cidhifyada nabarrada waxay keenaan hufnaan sare, khasaare hoose, iyo hawlgal aamusnaan ah, taasoo ka dhigaysa kuwo ku habboon shabakadaha awood qaybinta casriga ah. Horumarka laga sameeyay agabka sida biraha amorphous-ka ah, transformers-yada xudunta u ah nabarrada ayaa door ka sii weyn ka ciyaari doona hababka xariifnimo ee caqliga leh mustaqbalka.

2.2 Dabaylaha

Saliida -Tirka la quusiyay-Transformers-ku rakiban waxay caadiyan qaatan isku xidhka hoose -voltage (LV)
• Dabaysha LV: bireedyo naxaas ah oo lakabaysan (0.1-2mm qaro weyn) oo leh warqad is dhexgal ah oo dahaaran, oo bixisa qodob meel sare leh, qaboojin hufan, iyo gaaban oo gaaban-awood u adkeysiga wareegga wareegga.
• Dabaysha HV: Multi-Lakab dhalaalay silig naxaas ah, oo lagu xoojiyey waraaqo dahaadh ah iyo dhuumaha saliidda ee la xoojiyey ee xoogga dielectric iyo taabo{1}}isbeddelka dabacsanaanta.
Dabaysha ayaa si xoog leh loo habeeyey (LV gudaha, HV dibadda) waxaana si buuxda loogu dhex milmay saliidda beddelka, iyadoo la isticmaalayo saliid{0}}Nidaamka dahaarka warqadda qaboojinta iyo go'doominta korontada.
2.3 Haanta
Tiirka kaliya ee - wajiga -ku rakiban taangiga taangiga waxa laga soo saaray qabow{2}}taariko bir duuban oo loo sameeyay qaab cylindrical mashiinada qalooca. Darbiyada dhinacyadu waa la riixaa{4}}oo lagu qurxiyey baalal jiingado joogto ah oo si sax ah loo alxanayo iyadoo la isticmaalayo alxanka TIG. Daboolka haanta waa flange{6}}ku xidhan jidhka oo leh saliid{1} Dhammaan alxanka ayaa mara tijaabada gelitaanka kerosene iyo 0.05MPa tijaabada daadinta cadaadiska hawada. Daawaynta dusha sare waxa ka mid ah ciid-qarxinta oo ay ku xigto laba{11}}jaakad rinjiyeyn ah (epoxy primer + polyurethane topcoat) ilaalinta daxalka dibadda.

2.4 Kulanka ugu dambeeya

1. Golaha dabaysha:Ku rux -voltage-ka sare iyo kan hoose- dabaylaha korantada ee xudunta, hubinta toosinta dahaarka saxda ah, oo xafid taageereyaasha dabaylaha
2. Isku xirka Korontada:Alxan ama jar tiirarka, ku xidh beddelaha tuubada, duub walxaha dahaarka, oo hagaaji fiilooyinka meesha.
3. Xudunta - Qalajinta gariiradda:Geli qaybta firfircoon ee isku dhafan (xuddunta iyo dabaylaha) foornada qallajisa, mari kuleyliyaha faakuumka si aad uga saarto qoyaanka, oo hubi iska caabbinta dahaarka inay buuxisay heerarka.
4. Rakibaadda Haamaha:Kor u qaad qaybta firfircoon ee engegan oo si taxadar leh ugu dheji taangiga, ku toosi biinanka meelaynta, oo xidh boolalka saldhigga.
5. Rakibaadda Agabka:Duurka buushka, waalka cadaadiska cadaadiska iyo qalabyada kale, xirida dhammaan kala-goysyada.
6. Buuxinta & Xidhida Saliidda:Vacuum-Ka buuxi saliidda dahaadhka ilaa heerka la cayimay, hubi inay soo daadanayaan ka dib dejinta, oo dhamaystir kulanka u dambeeya.
03 Tijaabinta
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
1 |
Cabbiraadaha iska caabinta |
/ |
/ |
/ |
Gudub |
|
2 |
Imtixaanada saamiga |
/ |
Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5% Astaanta isku xirka: Ii0 |
-0.05 |
Gudub |
|
3 |
Tijaabada polarity |
/ |
Kala goyn |
Kala goyn |
Gudub |
|
4 |
Maya- khasaarooyinka rarida iyo xamaasadda hadda |
% kW |
I0 :: bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay Dulqaadka wax qabad la'aan waa +10% |
0.34 0.121 |
Gudub |
|
5 |
Khasaaraha culeyska, korantada impedance, wadarta khasaaraha iyo hufnaanta |
/ kW kW |
t:85 darajo Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay dulqaadka impedance waa ± 10% dulqaadka wadarta rarka luminta waa +6% |
2.12 0.514 0.635 99.06 |
Gudub |
|
6 |
Tijaabada Korantada ee La dabaqay |
/ |
HV: 34KV 60s LV: 10kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
7 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV): 2 Uur Muddada: 48 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
8 |
Cabbirka iska caabinta dahaarka |
GΩ |
HV -LV ilaa Ground LV-HV ilaa Ground HV&LV ilaa Ground |
80.8 63.2 59.7 |
Gudub |
|
9 |
Tijaabada daadinta |
/ |
Cadaadiska la dabaqay: 20kPA Muddada: 12h |
Wax daadsan iyo maya Waxyeello |
Gudub |
|
10 |
Tijaabada Dielectric Oil |
kV |
Ka weyn ama la mid ah 45 |
56.96 |
Gudub |


04 Baakaynta iyo dhoofinta
4.1 Xirxirida
Tiirka kaliya ee - wajiga -ku rakiban transformer-ka waxa ku jira saxan alwaax adag oo qoyaan - adkaysi u leh, oo gudaha lagu xafiday boolal iyo xumbo barkinta. Daasadaha rinjiga buufinta waxaa lagu duuduubay filim ka hortag ah{4} waxaana lagu hagaajiyaa meel nabdoon oo korka ah ama agteeda taransfooraha. Dhadhanka dhammaantiis waxa lagu duuduubay go'a aan biyuhu lahayn ee PVC, oo leh kulayl{6}} tolmo xidhan iyo cidhifyo laalaabsan xagga hoose ee ilaalinta roobka. Calaamadaha dibadda waxaa ku jira xarunta-calamadaha cufisjiidadka, astaanta roobka, iyo digniinta walxaha guban kara. Meelaha Forklift iyo xargaha birta ah waxay xoojiyaan saldhigga gaadiidka badbaadada leh.

4.2 dhoofinta

Marka loo eego shuruudaha CIF ee Georgetown, Guyana, iibiyuhu wuxuu u habeeyaa gaadiidka gudaha, xamuulka badweynta iyo caymis loogu talagalay tiirarka -ku rakiban Transformers, kuwaas oo ay tahay in lagu soo buuxiyo shoog iyo qoyaan - weel cad (oo leh qallajiye haddii loo baahdo). Sababtoo ah saliid -buuxday, transformers-yadu waxay u baahan yihiin cadeynta xamuulka khatarta ah (MSDS waa la bixiyay). Iibsaduhu wuxuu gacanta ku hayaa nadiifinta soo dejinta iyo gaarsiinta gudaha, isagoo xusaya awoodda wax-qaadista ee Dekedda Georgetown iyo xadka miisaanka waddada. Waqtiga safarka waa 35-50 maalmood; dukumeentiyada muhiimka ah waxaa ka mid ah B/L, qaansheeg ganacsi, liiska baakadaha, siyaasadda caymiska, iyo COO (tusaale, Foomka E).
05 Goobta iyo Kooban
Tiirka wejiga{0}{1}kujiray transformerka kaliya ayaa u taagan inuu yahay xalka ugu haboon ee shabakadaha awood qaybinta,isagoo siinaya hufnaan sare, nakhshad kooban, iyo rakibid fudud. Waxaa naga go'an inaan keeno alaab la isku halayn karo oo waara, oo ay taageerayaan xakamaynta tayada adag iyo hal-abuurka tignoolajiyada si loo hubiyo waxqabadka xasilloon ee deegaanno kala duwan. Markaad doorato transformers-yadayada, waxaad helaysaa dammaanad waxqabad oo gaar ah iyo taageero dhamaystiran kadib{4}}, adoo xoojinaya nidaamkaaga awooda badbaado iyo hufnaan. Waxaan rajeyneynaa inaan kula shaqeyno si aan u dhisno mustaqbal tamar wanaagsan!

Hot Tags: hal weji tiir ku rakiban transformer qaybinta, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
50 kVA Beddeleyaasha Cirifka Utility-34.5/0.12*0.24 ...
75 kVA Nooca Cirifka -34.5 / 0.12 * 0.24 kV|Kanada 2024
167 kVA Badelaha Qaybinta Cirifka-14.4/0.6 kV|Kanada...
37.5 kVA Tiirka Ku Rakiban Beddelka-2.4/0.12 kV|Kana...
100 kVA Transformer tiir Ku rakiban-13.8/0.24 kV|Guy...
75 kVA Utility Transformer-24.94/0.12 kV|Kanada 2025
U dir sooji