Jiangshan Scotech Electric Co., Ltd waa mid ka mid ah soosaarayaasha ugu kalsoonida badan iyo soo-saareyaasha 100 kva transformers ee tirarka korontada{6}}13.8/0.347 kv|kanada 2026 ee Shiinaha. Fadlan xor u noqo inaad iibsato alaab qiimo jaban oo iib ah halkan oo ka hel jaantusyada warshadeena. nala soo xidhiidh wixii faahfaahin ah

 

image001

Transformer-ka tirka ku rakiban ee lagu dhex daray hillaaca xidhaaha, u adkaysta hillaaca si hufan.

 

 

01 Guud

1.1 Sharaxaada Mashruuca

100 kVA hal waji oo tiir ku rakiban transformer ayaa la geeyey Kanada 2025. Awoodda la qiimeeyay ee transformerku waa 100 kVA oo leh ONAN qaboojin. Korantada sare waa 13.8 kV oo leh ± 2 * 2.5% garaacista (NLTC), korantada hoose waa 0.347 kV, waxay sameeyeen koox vector ah Ii6.

Transformer-ku waxa uu nashqadeeyey oo la tijaabiyey si buuxda oo waafaqsan CSA C2.2-06 - heerka Kanadiyaanka ee tiirka{3}}ku-xidhka taransfoorayaasha qaybinta. Transformer-kan waxaa si gaar ah loogu talagalay Waqooyiga Ameerika iyo shabakadaha qaybinta ee waafaqsan CSA.

Aagagga codsiga caadiga ah waxaa ka mid ah:
• Khadadka qaybinta sare ee miyiga iyo agagaarkeeda oo u adeegaya meelaha la deggan yahay iyo beeraha;
• Istaag{0}kaligaa sahayda korontada ee dhismayaasha yaryar ee ganacsiga, xarumaha bamgareynta, iyo hoyga isgaarsiinta;
• Keliya-Laamood weji ah oo kabaya saddex{1}}nidaamyada waji.
Si aad ugu adkaysato khataraha kor-ka-dhaafka ah ee caadiga ah ee xadhkaha sare (hillaacu ku dhufto, beddelidda qulqulka), dhinaca aasaasiga ah ayaa si ikhtiyaari ah loogu qalabayn karaa hal xire oo qalliin ah, kaas oo si wax ku ool ah u xaddidaya ballaadhinta kororka soo socda oo ilaaliya nidaamka dahaarka gudaha. Marka lagu daro -mawjadaha BIL ee buuxa ee 95kV (asaasiga ah) iyo korantada la dabaqay ee u adkeysaneysa 34 kV (asaasiga ah, 60 Hz), taransfooriyuhu waxa uu bixiyaa waxqabad dielectric adag.

 

 

 

1.2 Tilmaamaha Farsamada

100 kVA tiirka ku rakiban qalabka beddelka nooca iyo xaashida xogta

loo geeyey
Guyana
Sannadka
2025
Nooca
Transformer ku rakiban tiirarka
Heerka
CSA C2.2-06
Awood lagu qiimeeyay
100 kVA
Soo noqnoqda
60HZ
Marxaladda
1
Polarity
Wax lagu daro
Nooca qaboojinta
ONAN
Korantada aasaasiga ah
13.8 kV
Voltage Secondary
0.347 kV
Qalabka dabaysha
Copper
barokaca xagal
ii6
Caqabada
3.0%
Taabo Beddelka
±2*2.5%
Wax Xamuul ah ma jiro
0.192 kW
Load Lumista
1.52 kW
Waxtarka
98.94%
Midabka
cawl khafiif ah, Number 70, Munsell note 5BG7.0/0.4

 

1.3 Sawirro

100 kVA tiir ku rakiban jaantuska beddelka sawirka iyo cabbirka.

image003 image005

 

 

02 Wax-soo-saarka

2.1 Core

image007

Xuddunta waxaa laga soo saaray daxalgal sare, bir silikoon ku jihaysan hadhuudh hoose, oo si sax ah loo sameeyay si loo sameeyo wareeg birlab ah oo xiran. Farsamadan lamination waxay si wax ku ool ah u yaraynaysaa jahawareerka hadda jira iyo khasaaraha hysteresis, taas oo si toos ah uga qayb qaadanaysa taransfooriyaha wax ku oolnimada wax qabad la'aan. Cabbiraadda wax qabad la'aan ah waa 165 W oo keliya 100% danab lagu qiimeeyay iyo 200 W oo ah 105% danab lagu qiimeeyay. Tidcan naxaas ah oo raagaya ayaa bixiya saldhig la isku hallayn karo oo udub dhexaadka u ah labada dhinac, isaga oo meesha ka saaraya khatar kasta oo iman karta sabayn. Natiijo ahaan, transformer-ku wuxuu u shaqeeyaa aamusnaan, wuu qaboojinayaa, wuxuuna ilaaliyaa waxtarka sare xitaa xaaladaha culeyska fudud.

 

2.2 Dabaylaha

Labada dabaylaha korantada sare iyo kuwa hooseeya labaduba waxay gabi ahaanba ka dhaawacmaan naxaasta korantada, iyagoo bixiya korantada korantada ee sare iyo awood farsamo oo heersare ah oo ka dhan ah xoogagga wareegga gaaban. Habaynta dabaysha ee xoogga leh, oo ay weheliso marinnada saliidda ee istiraatiijiga ah, waxay kor u qaaddaa wareegga saliidda dabiiciga ah (ONAN) ee daadinta kulaylka waxtarka leh. Dabaysha aasaasiga ahi waxay leedahay qiimaynta BIL oo ah 95kV, halka dabaysha labaad lagu qiimeeyay 30kV, iyada oo hubinaysa ka ilaalin adag oo ka dhanka ah hillaaca iyo beddelka qulqulka. Khasaaraha culeyska ee 85 digrii ee tuubada maamulaha waxaa lagu diiwaangeliyaa 1,459 W. Nashqada nabartan naxaasta ah waxay dammaanad qaadaysaa isku halaynta muddada dheer, khasaaraha iska caabbinta hooseeya, iyo waxqabadka kulaylka oo aad u wanaagsan.

image009

 

2.3 Haanta

image011

Taangiga beddelka waxa laga sameeyay bir qafiif ah oo tayadeedu sarreyso oo leh dhismo si buuxda u xidhan (hermetic) oo alxan leh, oo ka hortagaysa wax kasta oo saliidda ah ama qoyaan soo galaya. Waxay si guul leh uga gudubtaa tijaabada cadaadiska adag ee 20 kPa muddo 12 saacadood ah, iyada oo aan lahayn wax daadsan oo la ogaan karo ama qallooc joogto ah. Dusha sare waxa lagu dhammeeyaa cawl khafiif ah ANSI 70 (Munsell 5BG7.0/0.4) koodhka dushiisa, kaas oo siinaya iska caabin cimilo oo heersare ah iyo ilaalinta daxalka. Qalabka wax ka beddelka (transformer Fittings) waxa ka mid ah giraanta nooca jiidista waalka cadaadiska, beddelaha tuubada, lugaha culayska qaadista, iyo suunka isku dhafan ee dhulka. Dhinac kasta oo ka mid ah naqshadeynta taangiga ayaa diiradda lagu saarayaa nolosha adeegga dheer iyo dayactirka hooseeya ee jawiga dibadda.

 

2.4 Kulanka ugu dambeeya

Loogu talagalay in lagu dhejiyo tiirka ku habboon, transformer-ku waxa uu la imanayaa iyada oo dhammaystiran oo leh biraha hanger-ka adag. Dhinaca aasaasiga ah, laba 15 kV daboolka buurta buushka ayaa lagu rakibay: H1 terminal waa nooc isku dhejis ah oo 4 ah oo loogu talagalay isku xirka khadka sare ee fudud, halka terminalka H2 uu gudaha gudaha ugu xiran yahay taangiga, fududaynta dhulka dibedda. Dhinaca labaad waxa uu leeyahay laba bushings spade nooca G ah oo leh 3/{7}} istaarad iyo laba dalool halkii taargo, hubinta isku xidhka badbaadsan, iska caabin hoose ee kirishbooyada danab yar. 5 meel ka baxsan beddelka tuubada wareegga waxay bixisaa ± 2 × 2.5% hagaajinta korantada (ie, +5%, +2.5%, magac ahaan, -2.5%, -5%) si loo waafajiyo kala duwanaanshaha shatiga. Taariko bir ah oo aan lahayn waxaa lagu xardhay lambarka dalabka macmiilka iyo tixraaca wax soo saarka si loo helo raad-raac cad.

image013

 

2.5 Xarigga

image015

Ilaalinta korantada xad-dhaafka ah ee la xoojiyey, nooca Evolution 12kV polymer-ka culus ee xiraha qalliinka culus ayaa la keeni karaa (hal waji), oo ay ku dhammaystiran tahay garab kor u go'an. Guryaha polymer-ka waa mid fudud, jabka adkaysi u leh, wuxuuna bixiyaa waxqabad aad u wanaagsan meelaha wasakhaysan ama huurka sareeyo. Xiruhu wuxuu isticmaalaa tignoolajiyada birta oksaydh-varistor (MOV) si uu u bixiyo xajin sax ah oo degdeg ah oo ku dhufanaya danab iyo beddelidda ku-meel-gaadhka. Iyada oo nuugaysa oo leexinaysa tamarta qallafsan, waxay si wax ku ool ah uga ilaalisaa habka dahaarka beddelka ee waxyeellada. Xiritaankan ikhtiyaariga ah ayaa aad loogu talinayaa meelaha ay ka jiraan dhaqdhaqaaqyada hillaaca joogtada ah ama khadadka khadka sare ee bannaan.

 

2.6 Cadaadiska Relief Valve

Nooca giraanta jiidista YSF ee taxanaha cadaadiska cadaadiska (PRD) ayaa loo rakibay sidii qalab caadi ah. Cadaadiskeeda siideynta waxaa lagu qiyaasaa 0.03 ± 0.01 MPa, waxayna bixisaa awoodda socodka 35 SCFM, taas oo u oggolaanaysa in si degdeg ah u neefsato gaasaska gudaha inta lagu jiro xaaladaha cilladda. Hawlgalka caadiga ah, waalka waxa uu ahaanayaa mid si adag u xidhan habka guga lagu raray; marka cadaadisku u kaco si lama filaan ah, si toos ah ayuu u furmaa oo dib u dejiyaa marka heerar nabdoon la soo celiyo. Giraanta jiidista ee gacanta ayaa u oggolaanaysa shaqaalaha adeegga inay sameeyaan hawo-mareen la xakameeyey inta lagu jiro buuxinta saliidda, dayactirka, ama baaritaanka. PRD-dan waxay markaa u adeegtaa sidii aalad badbaado toos ah iyo qalab dayactir oo habboon, taasoo si weyn kor ugu qaadeysa badbaadada hawlgalka.

image017

 

 

03 Tijaabinta

Transformer kasta waxa uu maraa imtixaanada caadiga ah oo dhamaystiran si waafaqsan CSA C2.2 06, iyada oo dhamaan natiijooyinka lagu diiwaan galiyay warbixin imtixaan oo saxeexan. Qiimaha muhiimka ah ee la cabbiray waxaa ka mid ah leexashada saamiga kaliya -0.01% ee tuubada maamulaha iyo xannibaadda 3.21% (si fiican ugu dhex jira ± 7.5% dulqaadka). Transformer-ku waxa uu gaaraa hufnaan dhan 99.02%, isaga oo dhaafa CSA C802.1 13 shardiga ugu yar ee 98.94%. Tijaabooyin danab ah oo la dabaqay (34 kV aasaasiga ah, sare 10 kV) iyo tijaabada korantada ee la kiciyay (150 Hz, 48 s) dhamaantood waa la dhammaystiray iyada oo aan burbursanayn. Tijaabada shaabaddii taangiga ee 20 kPa muddo 12 saacadood ah ayaa xaqiijisay daadinta eber, iyo falanqaynta saliidda ayaa muujisay awoodda dielectric ee 65.1 kV oo leh qoyaanka kaliya ee 13.4 mg / kg. Natiijooyinkani waxay xaqiijinayaan u hoggaansanaan buuxda iyo isku halaynta wanaagsan.

image019
image021

 

 

04 Baakad

4.1 Baakad

Transformer-ku waxa uu si toos ah ugu xidhan yahay gudaha sanduuq adag oo alwaax ama bir ka samaysan, gaar ahaan loogu farsameeyay in uu u adkaysto maaraynta adag iyo gaadiidka masaafo dheer. Dhammaan qaybaha soo baxaya ama xasaasiga ah - baadiyaha, cadaadiska cadaadiska, cabbirka heerka saliidda, iyo xidhiyaasha ikhtiyaarka ah - ayaa si gaar ah loogu ilaaliyay suuf xumbo ah oo la jarjaray iyo, haddii loo baahdo, lagu xidho sanduuqyo gudaha ah oo gaar ah. bannaanka sanduuqa waxaa si cad loogu calaamadeeyay lambarka dalabka macmiilka iyo tixraaca wax soo saarka si loo aqoonsado si fudud meesha loo socdo. Baakadu waxay la kulmeysaa ISPM-15 shuruudaha daawaynta alwaax ee dhoofinta caalamiga ah, hubinta nadiifinta kastamku siman. Liis baakad dhammaystiran ayaa ku dheggan bannaanka sanduuqa.

 

4.2 dhoofinta

Transformer-ku wuxuu ku habboon yahay weelka badda iyo raridda xamuulka sariirta leh, taasoo bixisa doorashooyin saadka oo dabacsan. Kormeerka hore ee shixnadda oo dhammaystiran waxa uu xaqiijiyaa cabbirrada guud, dhammaystirka isu-ururinta, dhammaystirka dusha sare, iyo calaamadaynta taarikada. Inta lagu jiro rarka, xarunta dhexe ee cuf-jiidadka waxaa si taxadir leh ula jaan qaada baabuurka ama weelka, iyo wax-qaadista dharbaaxayaasha waxaa lagu hayaa xagal ka yar ama la mid ah 30 digrii si loo hubiyo in xitaa qaybinta miisaanka. Xadhkaha xoogga sarreeya iyo xargaha ayaa si ammaan ah u garaaca sanduuqa si ay uga hortagaan beddelka gaadiidka. Shixnad kasta waxaa ku jira warbixinta imtixaanka rasmiga ah, buug-tilmaameedka rakibaadda, liiska baakadaha oo faahfaahsan, iyo qaansheeg ganacsi. Kormeerka rarista qolo saddexaad waxa la diyaarin karaa marka la codsado ammaan dheeraad ah.

 

 

05 Kooban

Tani 100 kVA, 13.8 / 0.347 kV hal weji tiir ku rakiban transformer wuxuu isku daraa xudunta birta silikoon khasaaraha hoose, dhammaan dabaylaha naxaasta ah, qaboojinta ONAN, iyo taangiga birta khafiifka ah oo dhamaystiran. Waxaa loo dhisay si ay ula kulanto CSA C2.2 06 iyo CSA C802.1 13 heerarka hufnaanta, oo leh hufnaan la qiyaasay 99.02% – aad uga sarreeya 98.94% ee la dammaanad qaaday. Haddi aad mas'uul ka tahay cusboonaysiinta xadhkaha korantada magaalooyinka ama mashaariicda korantada ee meelaha fog fog, kooxdayada farsamadu waxay bixin doontaa{9} taageero wareeg ah oo buuxda laga bilaabo xulashada qalabka ilaa isku xidhka khadka.