12 kVA Qalalan Qaybinta Qaybinta-11/0.22 kV|Imaaraadka Carabta 2025
Awoodda: 12kVA
Voltage: 11000/220V
Sifada: oo leh Lifaaqa: IP20

Awood la isku halayn karo oo qaab is haysta - transformerkaaga aad aaminsantahay ee qaybinta qaybinta
01 Guud
1.1 Sharaxaada Mashruuca
Tan 12kVA Cast Resin Dry-Type Transformer (CRT) waa xal kooban oo la isku halayn karo oo hooseeya{2}}awood sadexaad{3}}qaybinta awooda wejiga. Naqshadeeyay si waafaqsan heerarka IEC, waxa ay ka kooban tahay hadhuudh -ujeedka birta silikoon ku jihaysan iyo dabaylaha naxaasta ah, oo leh qaboojin hawo dabiici ah (AN), danab hoose oo ah 11 kV iyo danab sare oo ah 0.22kV.
Lagu qalabeeyay kooxda Dy11 vector iyo Maya-Load Tap Changer (NLTC) oo wata ±2×2.5% hagaajinta, transformerkan waxa uu leeyahay wax yar oo aan-load ah iyo khasaare 0.09 kW ah iyo 0.39 kW. Dahaarka heerka B wuxuu xaqiijiyaa hawlgal la isku halayn karo oo badbaado leh oo ku jira xaaladaha caadiga ah.
Transformer-ka Cast Resin Transformer (CRT), oo sidoo kale loo yaqaanno Epoxy Cast Resin Resin -Type Transformer, waa nooc qalalan{1}} Dabaylaha ayaa si buuxda loogu daboolay resin epoxy. Uma isticmaasho saliid ama dareere kale si ay u daboolaan. Hawada waxaa loo isticmaalaa in lagu qaboojiyo oo lagu daboolo xudunta iyo dabaylaha.
Xabagta epoxy-ga waxay siinaysaa dahaar xoog leh oo ka joojiya beddelka inuu nuugo qoyaanka. Tani waxay u ogolaanaysaa inay si fiican ugu shaqeyso qoyaan, boodh, ama jawi adag. Xabagta waxa lagu shubaa faakuum. Tani waxay hubinaysaa in gariiradaha gabi ahaanba la xidhay oo la ilaaliyo. Transformer-kan qallalan waxa uu leeyahay awood 12kVA ah iyo 11kV/0.22kV oo lagu qiimeeyo danab Waxay siisaa xal xasiloon dhexdhexaad ah -ilaa{9}} qaybinta danab hoose.
1.2 Tilmaamaha Farsamada
12 kVA Resin tuuray tafatirka nooca qalalan iyo xaashida xogta
|
loo geeyey
Imaaraadka Carabta
|
|
Sannadka
2025
|
|
Nooca
Transformer nooc qalalan oo shub ah
|
|
Qalabka Muhiimka ah
xaashi bir silikoon ku jihaysan hadhuudhka
|
|
Heerka
IEC
|
|
Awood lagu qiimeeyay
12 kVA
|
|
Soo noqnoqoshada
50HZ
|
|
Marxaladda
Saddex
|
|
Kooxda Vector
Dy11
|
|
Nooca qaboojinta
AN
|
|
Korantada aasaasiga ah
11KV
|
|
Voltage Secondary
0.22 kV
|
|
Qalabka dabaysha
Copper
|
|
Caqabada
4%
|
|
Qalabka dabaysha
NLTC
|
|
Caqabada
2.5%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
± 2 * 2.5% @ danab hoose
|
|
Wax Xamuul ah ma jiro
0.09 kW
|
|
Load Lumista
0.39kW
|
|
Heerka dahaarka
B
|
|
Agabka
Xakamaynta heerkulka, Xidhmada
|
1.3 Sawirro
12kVA Resin wuxuu tuuray sawir beddelka nooca qalalan iyo saxanka magaca
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core
Birta silikoonku waxay leedahay qiyaastii 3% silicon. Waxay leedahay waxqabadka magnetic wanaagsan iyo khasaaro hooseeya. Tani waxay kaa caawinaysaa yaraynta qulqulka qulqulka waxayna si fiican ugu shaqeysaa soo noqnoqoshada sare. Waraaqaha la dahaadhay ee birta silikoon ee qaaliga ah waxay yareeyaan khasaaraha hadda jira iyo magnetic hysteresis, iyagoo kor u qaadaya waxtarka tamarta.
2.2 Dabaylaha

Transformer-ka qaybinta qalalan ee 12kVA ah waxa uu isticmaala -waxqabadka kooraska naxaasta si uu u yeesho xoog sare iyo mid gaaban{2}} iska caabin wareeg ah. Dabaysha hoose -korontadu waxay isticmaashaa nashqad xaashida ah si loo hubiyo qaybinta isku midka ah ee hadda jirta. Transformer-ku waxa uu isticmaalaa dahaarka heerka B (130 digrii) iyo tignoolajiyada shubista resin resin ee qoyaanka aad u fiican iyo iska caabinta siigada, iyadoo sidoo kale bixisa ilaalin gaaban oo gaaban oo la isku halayn karo.
2.3 IP20 Xidhmada
Qalabkan qalalan ee gudaha{0}nooc ka mid ah waxa uu leeyahay IP20 lagu qiimeeyay xayndaab ilaalineed, isaga oo si wax ku ool ah uga hortagaya xidhiidhka tooska ah ee u dhexeeya faraha iyo walxaha shisheeye ee adag iyo qaybaha nool, isaga oo hubinaya badbaadada wadayaasha. Xayndaabku waxa kale oo ay ka hortagtaa boodhka, biraha xiiraya, iyo qashin kale in ay galaan transformerka, taas oo yaraynaysa khatarta dahaarka iyo kulaylka deegaanka. Intaa waxaa dheer, xerintu waxay yaraynaysaa qaylada hawlgalka waxayna wanaajisaa bay'adda gudaha.

2.4 Kulanka ugu dambeeya

Qaybaha xudunta u ah ee la sameeyay iyo dabaylaha ayaa la isku keenay, inta lagu gudajiro isku xirka korantada, dahaarka, iyo hagaajinta qaab dhismeedka.
Faakuumka hoostiisa, resin epoxy ayaa lagu shubaa inta u dhaxaysa dabaylaha iyo xudunta, isaga oo samaynaya qaab-dhismeed adag oo la daweeyay.
Ka dib isku-ururinta iyo daaweynta, tijaabooyin taxane ah oo koronto iyo makaanik ayaa la sameeyaa si loo hubiyo in beddelka uu buuxiyo heerarka naqshadeynta iyo badbaadada.
03 Tijaabinta
Imtixaanka Heerka iyo Imtixaanka Joogtada ah
IEC 60076-1-2011 Transformers Power - Qaybta 1: Guud
IEC 60076-3-2013 Transformers Power - Qaybta 3: Heerarka dahaarka, tijaabooyinka dielectric iyo nadiifinta dibadda ee hawada
IEC 60076-11-2018 RLV Transformers Power - Qaybta 11: Nooc qalalan
1. Cabbirka caabbinta dabaysha
2. Cabbirka saamiga korantada iyo hubinta barakaca wejiga
3. Cabbirka gaaban -cidhiidhiga wareegga wareegga iyo rarka luminta
4. Cabbirka aan rarka lumin iyo hadda
5. Tijaabada danabka la dabaqay
6. Imtixaanka adkaysiga danabku keenay
7. Tijaabada dheecaanka qaybeed


Natiijooyinka Imtixaanka
|
Maya |
Shayga Tijaabada |
Unug |
Qiimaha Ogolaanshaha |
Qiimaha la qiyaasay |
Gabagabo |
|
|
1 |
Cabbirka caabbinta dabaysha |
/ |
Qiyaasta dheelitir la'aanta iska caabbinta ugu badan Iska caabinta khadka: In ka yar ama la mid ah 2% |
HV (khadka) |
LV (khadka) |
Gudub |
|
0.68% |
0.53% |
|||||
|
2 |
Cabbirka saamiga korantada iyo hubinta barakaca wejiga |
/ |
Dulqaadka saamiga korantada ee taabashada maamulaha: ± 1/10 Astaanta isku xirka: Dy11 |
0.01% ~ 0.12% Dy11 |
Gudub |
|
|
3 |
Cabbirka Gaaban -Caaqadaha Wareega iyo Luminta Culayska |
/ kW kW |
t: 100 darajo Z%: qiimaha la qiyaasay Pk: qiimaha la qiyaasay Pt: qiimaha la qiyaasay |
3.64% 0.259 0.317 |
Gudub |
|
|
4 |
Cabbirka maya{0}} lumitaanka rarka iyo hadda 90% iyo 110% ee danab la qiimeeyay |
/ kW |
I0 :: bixiyaan qiime la qiyaasay P0: bixi qiimaha la qiyaasay |
90% Uur |
2.88 0.083 |
Gudub |
|
100% Uur |
3.21 0.093 |
|||||
|
110% Uur |
3.53 0.102 |
|||||
|
5 |
Tijaabada Korantada ee La dabaqay |
/ |
HV: 28kV 60s LV 3kV 60s |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
|
6 |
Tijaabada adkaysiga korantada ee keentay |
/ |
Danab la dabaqay (KV): 2 Uur Danab la kiciyay (KV): 0.44 Muddada:40 Inta jeer (HZ): 150 |
Ma jiro burbur ku yimaada tamarta tijaabada ah |
Gudub |
|
|
7 |
Tijaabada Bixinta Qaybeed |
pC |
Heerka ugu badan ee sii daynta qayb ahaan waa in ay ahaataa 10 pc |
<10 |
Gudub |
|
04 Baakaynta iyo dhoofinta
![]() |
![]() |
05 Goobta iyo Kooban
Dhismayaasha warshadaha iyo ganacsiga, sahay koronto oo deggan ayaa aad muhiim u ah. Scotech 12 kVA Cast Resin Dry -Type Transformer (CRT) waxa uu siinayaa dhexdhexaad nabdoon oo hufan{3}} ilaa hoose-awood koronto.
Waxay leedahay dabeylo naxaas ah iyo xudunta birta silikoon. Dabaysha ayaa si buuxda loogu daboolay resin epoxy iyo hawo{1}}qaboojis, markaa saliid looma baahna. Resin-ku waxa uu ka ilaaliyaa qoyaanka iyo siigada, taas oo u oggolaanaysa in muddo dheer{3}} loogu isticmaalo degaannada adag.
Waxa ay leedahay kooxda Dy11 vector iyo Maya -Load Tap Changer (NLTC) ee hagaajinta danab dabacsan. Maya yar - rarka iyo rarka rarka ayaa ka dhigaya mid hufan. Xerada IP20 waxay dadka ka ilaalisaa ammaan waxayna joojisaa siigada soo gasha, iyadoo ay sidoo kale yarayso buuqa gudaha.

Hot Tags: Transformer qaybinta qalalan, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
2500 kVA Beddelka Qalalan-10/0.4 kV|Georgia 2025
250 kVA Qalalan Qalalan Resin Transformers-10/0.4 kV...
630 kVA Cast Resin Nooca Qalalan-66.6/0.55 kV|Koonfu...
500 kVA Beddelka Xabagta Qalalan-13.8/0.46 kV|Koonfu...
1.25 MVA Cast Resin Type Transformer-0.415/3.3*6.6 k...
3 MVA Qalalan Nooca Qalalan-13.8 / 0.48 kV|Jamaica 2025
U dir sooji