2100 kVA Nooca Qalalan ee Qaybinta Qaybinta-13.8/0.46 kV|Koonfur Afrika 2024

2100 kVA Nooca Qalalan ee Qaybinta Qaybinta-13.8/0.46 kV|Koonfur Afrika 2024

Dalka la geynayo: Koonfur Afrika 2024
Awoodda: 2100kVA
Voltage: 13.8 / 0.46 kVA
Muuqaalka: oo leh CT (5000/1)
U dir sooji

 

 

image001

Qalalan 2100 kVA ah oo wax ku ool ah oo nooc qalalan leh oo leh dahaar sare iyo ilaalin caqli badan.

 

 

01 Guud

1.1 Sharaxaada Mashruuca

Waxaa loo soo saaray macmiil Koonfur Afrikaan ah sanadka 2024, 2100 kVA nooca qalalan ee qaybinta nooceedu waxa uu leeyahay dabaylo si buuxda ugu daboolan resin epoxy. Saliida oo xor ah -, waxay hoos u dhigtaa halista dabka iyo wasakhowga deegaanka. Iyada oo leh dahaarka heerka F ee lagu qiimeeyay heerkulka shaqaynta ilaa 155 digrii.

Korontada waxaa lagu qiimeeyaa 2100 kVA, oo leh danab hoose oo ah 13.8 kV iyo koronto labaad oo ah 0.468 kV (468 V). Waxay ku habboon tahay in lagu shido miinada iyo qalabka culus ee ka shaqeeya 468 V.

Kooxdeedu waa D (+15℃)d0, halkaas oo dhinaca sare - dhinaca korantada ay muujiso +15 marxalad wareeg ah. Naqshadani waxay buuxisay shuruudaha wajiga nidaamka waxayna caawisaa dhimista iswaafajinta iyo qulqulka wareega inta lagu jiro hawlgalka barbar socda.

Xuddunta waxa ay ka samaysan tahay bir silikoon ku jihaysan hadhuudh, kaas oo bixiya khasaare hoose iyo cufnaanta birlabeedka sare, taas oo ka qayb qaadanaysa luminta rarka hoose {{0} 3.2 kW.

Ku qalabaysan heerkul-ilaaliyaha iyo beddelka hadda jira (5000/1 CT), Transformer-ku waxa uu taageeraa la socodka iyo ilaalinta heerkulka dabaysha, iyo sidoo kale cabbirka hadda, fududaynta is dhexgalka nidaamka ilaalinta iyo la socodka.

 

 

1.2 Tilmaamaha Farsamada

2100kVA Resin tuurista nooca qallalan qeexida iyo xaashida xogta

loo geeyey
Koonfur Afrika
Sannadka
2024
Nooca
Transformer nooc qalalan oo shub ah
Qalabka muhiimka ah
xaashi bir silikoon ku jihaysan hadhuudhka
Heerka
IEC60076
Awood lagu qiimeeyay
2100 kVA
Soo noqnoqoshada
60HZ
Marxaladda
Saddex
Kooxda Vector
D (+15 darajo )d0
Nooca qaboojinta
AN
Korantada aasaasiga ah
13.8 kV
Voltage Secondary
0.468 kV
Qalabka dabaysha
AL
Caqabada
7.5%
Taabo Beddelka
/
Riixista Range
/
Wax Xamuul ah ma jiro
3.2 kW
Load Lumista
3.2 kW
Heerka dahaarka
F
Agabka
Xakamaynta heerkulka, CT (5000/1)

 

 

1.3 Sawirro

2100kVA Resin tuuray sawir beddelka nooca qalalan

Resin cast dry type transformer drawing

 

 

02 Wax-soo-saarka

2.1 Core

Saddexda 2100 kVA -waji qalalan nooca qaybinta xudunta waxay isticmaashaa hadhuudh{2}} xaashiyo bir silikoon ku jihaysan oo leh awood birlabeed sare leh, hagaajinaysa hufnaanta korantada iyo yaraynta khasaaraha asaasiga ah. Xaashiyahani waxay leeyihiin sifooyin farsamo oo xoog leh si ay ugu adkaystaan ​​habaynta iyo walbahaarka muddada dheer- SCOTECH waxay hubisaa in burooyinka ka yar ama le'eg yahay 0.02mm oo aan cillad lahayn. Xudunta is dulsaaran waxa lagu dahaadhay qoyaan{8}} caddayn resin epoxy for adkaysiga iyo ilaalinta qoyaanka.

image005

 

2.2 Dabaylaha

image007

Beddelka nooca qalalan wuxuu leeyahay laba dabaylo, oo labadaba lagu dhisay aluminium dabadheeraad ah si loo hubiyo waxqabadka wanaagsan iyo nolosha adeeg dheer. Dhammaan dabaylaha waxaa lagu dahaaray agabka dahaarka heerka F, iyo gariiradda oo dhan waa faakuum lagu galiyay resin Fasalka F epoxy, samaynta qoyaan adag, - u adkaysta iyo habka kulaylka deggan

 

2.3 kulanka ugu dambeeya

Qaybaha xudunta u ah ee la sameeyay iyo dabaylaha ayaa la isku keenay, inta lagu gudajiro isku xirka korantada, dahaarka, iyo hagaajinta qaab dhismeedka.

Faakuumka hoostiisa, resin epoxy ayaa lagu shubaa inta u dhaxaysa dabaylaha iyo xudunta, isaga oo samaynaya qaab-dhismeed adag oo la daweeyay.

Ka dib isku-ururinta iyo daaweynta, tijaabooyin taxane ah oo koronto iyo makaanik ah ayaa la sameeyaa si loo hubiyo in beddelka uu buuxiyo heerarka naqshadeynta iyo badbaadada.

image009

 

 

03 Tijaabinta

image011
image013

 

Imtixaanka joogtada ah

1. Cabbirka caabbinta dabaysha

2. Cabbirka saamiga korantada iyo hubinta barakaca wejiga

3. Cabbirka gaaban -cidhiidhiga wareegga wareegga iyo rarka luminta

4. Cabbirka wax - lumitaanka rarka iyo hadda

5. Tijaabada danabka la dabaqay

6. Imtixaanka adkaysiga danabku keenay

7. Tijaabada dheecaanka qaybeed

8. Tijaabada Dielectric Oil

 

Natiijooyinka Imtixaanka

Maya

Shayga Tijaabada

Unug

Qiimaha Ogolaanshaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbirka caabbinta dabaysha

/

Qiyaasta dheelitir la'aanta iska caabbinta ugu badan

Iska caabinta khadka: In ka yar ama la mid ah 2%

HV (khadka)

LV (khadka)

Gudub

0.18%

1.61%

2

Cabbirka saamiga korantada iyo hubinta barakaca wejiga

/

Dulqaadka saamiga korantada ee taabashada maamulaha: ± 1/10

Astaanta isku xidhka: D (+15℃)d0

-0.18% ~ -0.07%

D (+15 darajo )d0

Gudub

3

Cabbirka Gaaban -Caaqadaha Wareega iyo Luminta Culayska

/

kW

kW

t: 120 digrii

Z%: qiimaha la qiyaasay

Pk: qiimaha la qiyaasay

Pt: qiimaha la qiyaasay

8.13%

12.662

16.261

Gudub

4

Cabbirka maya{0}} lumitaanka rarka iyo hadda 90% iyo 110% ee danab la qiimeeyay

/

kW

I0 :: bixiyaan qiime la qiyaasay

P0: bixi qiimaha la qiyaasay

90% Uur

110% Uur

Gudub

0.162%

0.198%

2.3265

2.8435

5

Tijaabada Korantada ee La dabaqay

/

HV: 38kV 60s

LV: 3kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

6

Tijaabada adkaysiga korantada ee keentay

/

Danab la dabaqay (KV):

2 Uur

Danab la kiciyay (KV): 0.936

Muddada:40

Inta jeer (HZ): 150

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada Bixinta Qaybeed

pC

Heerka ugu badan ee sii daynta qayb ahaan waa in ay ahaataa 10 pc

<10

Gudub

 

 

04 Baakaynta iyo dhoofinta

image015
image017

 

05 Goobta iyo Kooban

Qalabkan 2100 kVA resin kabka ah ee nooc qaybinta qalalan waxaa si gaar ah loogu talagalay macaamiisha Koonfur Afrika. Transformer-kani waxa uu si gaar ah ugu habboon yahay -mashiinnada waajibaadka culus, matoorada waaweyn, iyo qalabka habaynta ee macdanta iyo codsiyada warshadaha u baahan culays sare. SCOTECH waxay diyaar u tahay inay bixiso habayn xirfadeed iyo adeeg tayo leh si loo daboolo baahiyahaaga.

Sida xirfadle soo saaraha is beddelka nooca qalalan, SCOTECH waxay soo bandhigtaa alaabo waafaqsan heerarka caalamiga ah sida IEC, ANSI/IEEE, NEMA, CSA, iyo BS. Transformers-yada nooca qallalan ee nooca qallalan ayaa daboolaya awoodaha la qiimeeyay min 50 kVA ilaa 15 MVA, oo leh danab sare ilaa 36 kV. Labada jeer ee 50 Hz iyo 60 Hz waa la heli karaa, oo leh xiriirinta delta ama xiddigaha. Dabaylaha korantada dhexdhexaadka ah waxaa lagu soo koobay resin epoxy, oo leh fasalo dahaarka oo u dhexeeya A, E, B, F ilaa H, iyo heerarka ilaalinta laga beddeli karo IP 2X ilaa IP 4X.

Ikhtiyaarada qaboojinta waxaa ka mid ah qaboojinta hawada dabiiciga ah (ONAN) iyo qaboojinta hawada qasabka ah (ONAF), oo lagu qalabeeyay dareeme heerkul badan iyo relays kulaylka ilaalinta kulaylka la isku halayn karo. Waxa kale oo aanu bixinaa agabka ay ka midka yihiin taayirrada, transformers-ka hadda jira, -kumbuyuutarrada shubka (OLTC), iyo sanduuqyada wax lagu shubo si loo daboolo baahiyaha kala duwan ee macaamiisha.