500 KVA Transformer-ka-dhajinta-12.47/0.48 KV|USA 2025
Awoodda: 500 kVA
Voltage: 12.47GrdY/7.2-0.48Y/0.277 kV
Feature: Xuddunta leh gaashaanka dhulka
Jiangshan Scotech Electric Co., Ltd waa mid ka mid ah soosaarayaasha ugu kalsoonida badan iyo alaab-qeybiyeyaasha 500 kva transformer pads -12.47/0.48 kv|USA 2025 ee Shiinaha. Fadlan xor u noqo inaad iibsato alaab qiimo jaban oo iib ah halkan oo ka hel jaantusyada warshadeena. Nala soo xidhiidh wixii faahfaahin ah.

Bixinta Awoodda, Ilaalinta Booska. Transformer-ka Smart Pad ku rakiban yahay.
01 Guud
1.1 Sharaxaada Mashruuca
500 kVA saddex weji suuf ku rakiban transformer ayaa la geeyey USA 2025. Awoodda lagu qiimeeyay transformerku waa 500 kVA oo leh qaboojin KNAN. Korantada sare waa 12.47GrdY/7.2 kV oo leh ± 2*2.5% taping range (NLTC), danab hoose waa 0.48Y/0.277 kV, waxay samaysteen koox vector ah YNyn0.
Terminalkan-nooca, sadex{1}}waji, shan{2}lambarka addimada{3}}ku rakiban taransfooriyaha waxa loogu habeeyey isku halaynta sare iyo waxqabadka dalbashada codsiyada qaybinta korantada. Lagu nashqadeeyay -qiimaynta hadda ee 600A ee sare -dhinaca korantada, waxay hubisaa gudbinta awooda adag iyo xasiloonida shabakada
Xudunta dhismaheeda ayaa leh {{0}tayada dabaysha naxaasta ah ee tayada sare leh ee loogu talagalay firfircoonida iyo hufnaanta ugu fiican, oo lagu dhex milmay dareere FR3® ah oo qaali ah. Saliida dielectric-ka ah ee horumarsan, ee nooledegradable waxay bixisaa badbaado gaar ah oo dabka, cimri dhererka dahaarka oo la xoojiyey, iyo maaraynta kulaylka sare marka loo eego saliidaha macdanta dhaqameed.
Naqshadeynta muhiimka ah ayaa diiradda saareysa badbaadada iyo ilaalinta shaqada. Labada korantada sare{1} iyo kuwa hooseeya-Xidadaha korantada waxay ku qalabaysan yihiin gaashaanka korantada ee dhulka, si wax ku ool ah u yareeya halista korontada ku meel gaadhka ah iyo hubinta sahay koronto oo deggan.
La socodka joogtada ah iyo amniga hawlgelinta, transformer-ku waxa uu ku qalabaysan yahay qayb dhammaystiran oo cabbirrada caadiga ah: tusaha heerka dareeraha, tusaha heerkulka dabaysha, iyo cabbirka vacuum/cadaadiska. Qiyaasta vacuum/cadaadiska waxa kale oo lagu rakibay xidhiidho la hagaajin karo si ay u bixiso saacada digniinta dhabta ah ee xaaladaha cadaadiska muhiimka ah, awood u siinaya dayactirka firfircoon iyo ilaalinta nidaamka.
Isku darka walxaha raagaya, tignoolajiyada dareeraha cusub, sifooyinka badbaadada isku dhafan, iyo qalabaynta dhamaystiran, suufkan {0} ku rakiban transformer-ka waxa uu keenaa mid la isku halayn karo, badbaado ah, oo dheer{1}Xal waara oo loogu talagalay nidaamyada qaybinta dhulka hoostiisa casriga ah.
1.2 Tilmaamaha Farsamada
500 kVA suuf ku rakiban nooca tafatirka beddelka iyo xaashida xogta
|
loo geeyey
USA
|
|
Sannadka
2025
|
|
Nooca
suuf ku rakiban transformer
|
|
Heerka
IEEE Std C57.12.34-2022 DOE 2016
|
|
Awood lagu qiimeeyay
500 kVA
|
|
Soo noqnoqoshada
60HZ
|
|
Marxaladda
3
|
|
Quudinta
Radial
|
|
Hore
dhintay
|
|
Nooca qaboojinta
KNAN
|
|
Korantada aasaasiga ah
12.47GrdY/7.2 kV
|
|
Voltage Secondary
0.48Y/0.277 kV
|
|
Qalabka dabaysha
Copper
|
|
Kooxda Vector
YNyn0
|
|
Caqabada
5.75%
|
|
Waxtarka
99.35%
|
|
Taabo Beddelka
NLTC
|
|
Riixista Range
±2*2.5%
|
|
Wax Xamuul ah ma jiro
0.65 kW
|
|
Load Lumista
4.36 kW
|
1.3 Sawirro
500 kVA suuf ku rakiban jaantuska beddelka sawirka iyo cabbirka.
![]() |
![]() |
02 Wax-soo-saarka
2.1 Core

Xudunta udub dhexaadka qalabka wax lagu dhejiyo waxa laga dhisay heer sare -, hooseeya-laminations bir koronto oo lumay, si sax ah loo dulsaaray oo si ammaan ah loo dhejiyay si ay u sameeyaan sadex adag Muhiimad ahaan, gaashaanka dhulka elektrostatic-sida caadiga ah bireedyada naxaasta ah-waxaa si isku mid ah loo dhex dhigayaa xudunta iyo dabaylaha hoose-korantada Gaashaankani waxa uu si ammaan ah ugu xidhan yahay teerminalka dhulka ee transformer-ka, isaga oo abuuraya waddo qeexan oo dhulka loo maro. Shaqadeeda aasaasiga ah waa in ay si karti leh u weeciso{10}soo noqnoqoshada danabyada ku meel gaadhka ah iyo dhawaaqa caadiga ah{11}}ka fogaanta dabaylaha, iyada oo ilaalinaysa dahaarka, yaraynaysaa culayska korantada, oo aad u yaraynaysa faafinta faragelinta korantada ee nidaamka qaybinta sare.
2.2 Quudinta shucaaca
Qalab koronto-dhaliye ah oo ku jira qaabeynta quudinta shucaaca ee terminal waxay u adeegtaa sida barta qaybinta kama dambaysta ah ee shabakad koronto shucaac ah, oo ka helaysa koronto hal il oo kor ah. Terminalkeeda aasaasiga ah waxay si toos ah ugu xidhmaan quudiyaha dhexe, iyagoo hoos u dhigaya korantada culaysyada hoose ee soo socda. Qayb ka mid ah terminal ahaan, waxa ay dhaxlisaa halbeegga ku tiirsanaanta nidaamka shucaaca -: cilad korka ah ama go'a ayaa carqaladayn doona awooda taransfooriyaha iyo dhamaan culaysyada ku xidhan ilaa arinta la xalinayo. Naqshadeeda is haysta, dhulka ah-Naqshadeeda rakiban waxay hubisaa in la isku halayn karo, qaybinta awood la heli karo dhamaadka-arjiyada isticmaalaha.

2.3 FR3 Saliid

suufka -Transformer-ka ku rakiban waxaa ka buuxa dareere FR3® dielectric, premium, dab{2}}saliid ester dabiici ah oo adkaysi u leh oo laga helay saliidda cuntada. Waxaa loo kala saaraa dareere "Ololi karayn ka yar" ( per ASTM D6871) oo leh meel sare oo dab ah oo ka badan 360 digrii, taasoo si weyn kor ugu qaadaysa badbaadada meelaha dadku ku badan yihiin ama deegaanka xasaasiga ah. Marka laga soo tago badbaadada dabka ee sare, FR3® waxay bixisaa faa'iidooyin deegaan oo gaar ah maadaama ay si diyaar ah u tahay bayoolaji, aan - sun ah, oo ay leedahay raad kaarboon hoose. Marka laga eego dhinaca waxqabadka, dulqaadkeeda qoyaanka ee aadka u wanaagsan iyo xasilloonida kulaylka sare waxay kordhisaa nolosha dahaarka cellulose, si ay u kordhiso awoodda rarka beddelka, daahinta gabowga, iyo ka qayb qaadashada nolol adeeg dheer oo leh hoos u dhac muddo dheer ah{10}} baahiyaha dayactirka.
2.4 Qiyaasta
suufka -Transformer-ka ku rakiban waxa uu ku qalabaysan yahay qalab cabbiraadaha iyo tilmaamayaasha la socodka joogtada ah iyo ilaalinta hawlgalka Qiyaasta heerka dareeraha ayaa bixisa tilmaamo muuqaal ah oo cad oo muujinaya mugga dareeraha dielectric ee hubinta dayactirka. garaac -nooca cabirka heerkulka saliida (WTI) ayaa kormeeraya heerkulka saliida ee ugu sarreeya-si loo qiimeeyo culayska kulaylka. Cadaadiska nidaamka waxa lagu kormeeraa vacuum/cadaadiska isku-dhafka ah, taas oo muujinaysa xaaladaha cadaadiska hoose ee hawada iyo kuwa togan. Muhiimad gaar ah, cabirka cadaadiska waxaa lagu rakibay xiriiro koronto oo hermetically xiran la hagaajin karo. Xidhiidhadaan waxa loo habayn karaa si ay u dhaqaajiyaan alaarmiga fog ama waxay bilaabaan taxanaha xakamaynta marka la ogaado presetka sare -cadaadiska ama sare{10} xaaladaha faakuumka, u badala tilmaame fudud qayb firfircoon oo ka mid ah nidaamka ilaalinta transformerka. Si wada jir ah, aaladahani waxay siiyan hawlwadeenada xogta dhabta ah ee muhiimka ah{12}}iyo digniino badbaado oo firfircoon.

2.4 Man god 20" oo leh quful

Transformer-ku waxa uu ku qalabaysan yahay god 20{3}}inji ah oo lagu xafiday quful Furitaankan gelitaanka, oo lagu shaabadeeyey gaas waarta, waxay siisaa shaqaalaha idman meel ammaan ah oo ammaan ah oo ay ka galaan kormeerka gudaha, dayactirka, iyo baaritaanka. Qufulku wuxuu u adeegaa sidii badbaado iyo sifo ammaan oo muhiim ah, isagoo ka hortagaya gelitaanka aan la oggolayn ee qaybaha nool iyo hubinta daacadnimada xayndaabka, saliidda ka buuxo.
2.5 HV/LV dhulka hoostiisa
suufka -Transformer-ka ku rakiban waxa uu leeyahay nidaam dhamaystiran oo adag oo loogu talagalay qaybaha sare -voltage (HV) iyo kuwa hoose -Voltage (LV). Nidaamkan badbaadada muhiimka ah waxaa ka mid ah HV gaashaanka dabaysha, gaashaanka dabaysha LV, iyo xudunta beddelka lafteeda-dhammaan si joogto ah ugu xidhan baska dhulka la wadaago. Baskan waxa uu markaa si amaan ah ugu xidhan yahay -xakameyn hoose, xidhidhiye go'an oo ku socda shabaqyada dhulka dibadda ah. Samaynta hal, barta tixraaca dhulka ee la isku halayn karo, nidaamku waxa uu hubinayaa kala daadsanaanta nabdoon ee qulqulka cilladaha, daadinta shaqada, iyo ku-meel-gaadhka danabka. Naqshadani waxay si wax ku ool ah u dejisaa awoodda korantada, waxay ilaalisaa shaqaalaha, waxay ilaalisaa qalabka, waxayna kor u qaadaysaa guud ahaan waafaqsanaanta korantada (EMC) ee rakibidda.


03 Tijaabinta
suufka - Tijaabada taangiga taangiga ku rakiban waxay koobeysaa qiimayno muhiim ah si loo hubiyo sharafta qaabdhismeedka, shaabadaynta waxqabadka, iyo la jaanqaadka saliida dahaadhka, oo la jaan qaada heerarka sida ANSI C57.12.28, ANSI C57.12.00, iyo GB 50148-2010. Tijaabooyinkan waxaa ka mid ah tijaabooyinka cadaadiska halkaasoo haanta ay tahay inay u adkeyso ugu yaraan 15 pig iyada oo aan saliidda laga saarin ama qayb ka mid ah, oo u adkaysata 7 psi iyada oo aan lahayn qallooc joogto ah; Tijaabada qallafsanaanta faakuumka ee ku lug leh dalbashada -67 kPa vacuum, cabirida qallafsanaanta 10 dhibcood oo muhiim ah (tusaale, darbiyada taangiga, daboolka, xoojinta) ka hor iyo ka dib fakuumka sii daynta si loo hubiyo in ugu yar ee dhalanrog joogto ah (sida caadiga ah 0.01-0.03 mm); iyo tijaabooyinka daadinta-ama adoo cadaadinaya haanta madaxa (kadib markii meesha laga saaro waalka gargaarka cadaadiska) ama la socoshada isbeddelada cadaadiska, maadaama maqnaanshaha joogtada ah ee cadaadiska togan/ taban waxay muujin kartaa gaaska ama tolnimada dillaacsan. Intaa waxaa dheer, saliidda dahaadhka ee taangiga ku jira waxay maraan tijaabooyinka xoogga dielectric, qoyaanka, iyo falanqaynta gaaska kala diri (sida ASTM D3487) si loo hubiyo inay taageerto dahaarka korantada iyo xasiloonida taangiga, iyada oo hubinta tijaabada ka dib ay xaqiijinayso wax dhaawac ah oo taangiga ah, xidhmooyin dhawrsan, iyo u hoggaansanaanta xaddidaadaha qallafsanaanta si loo xaqiijiyo hawlgalka badbaadada leh ee dibadda.

04 Baakaynta iyo dhoofinta


05 Goobta iyo Kooban
Gebagebadii, suufkan -Transformer-ka ku rakiban waxa uu ka dhigan yahay casri, sare{1}xalin daacad ah oo loo habeeyey baahida shabakadaha qaybinta dhulka hoostiisa ee maanta.
Naqshaddeeda oo leh -oo ka muuqda shan - xuddun adag, dabaylo naxaas ah oo hufan, dab{2}} dareere FR3® badbaado leh iyo noole deg deg ah, iyo nidaam gaashaamo sal leh oo dhamaystiran{4}} waxa uu xaqiijiyaa hawlgal la isku halayn karo, badbaado la xoojiyey, iyo waxqabadka korantada ee sare. Qalabka isku dhafan ee la socodka, oo ay weheliyaan dhibco gelitaan oo sugan iyo khalad{6}}nidaam dhul dejineed oo dulqaad leh, ayaa hawlwadeenada siiya muuqaal iyo ilaalin muhiim ah. Isku dhafkan agabka horumarsan, injineernimada fekerka leh, iyo lagu dhisay - ee ogaanshaha waxa ay keenaysaa hanti waara, hoose{9}}taasi oo mudnaan siinaysa xasiloonida shabakada, badbaadada shaqaalaha, iyo masuuliyada deegaanka ee mustaqbalka fog.

Hot Tags: suufka lagu rakibo transformer, saaraha, alaab-qeybiyaha, qiimaha, qiimaha
You Might Also Like
400 kVA Padmount Transformer-23/0.4 kV|Chile 2024
2500 kVA suuf Ku rakiban Beddelayaasha Qaybinta-25/0...
1500 kVA suuf ku rakiban beddelka qiimaha-23.9/0.416...
500 kVA Saddex Waji oo Qaybinta Qaybinta-4.16/0.6 kV...
300 KVA suuf Ku rakiban Beddelka Guryaha -12.47*4.16...
2000 KVA Barta-xarunta Tamarta Ku Rakiban Tamarta-24...
U dir sooji