100 kVA Residential Transformer-13.8/0.12*0.24 kV|Guyana 2024

100 kVA Residential Transformer-13.8/0.12*0.24 kV|Guyana 2024

Dalka la geynayo: Guyana 2024
Awoodda: 100kVA
Voltage: 13.8 / 0.12 * 0.24 kVA
U dir sooji

 

 

100 kVA residential transformer

100kVA Transformer Residential by Scotech - Beddelka Korontada Waxtarka leh ee Guryaha Casriga ah

 

01 Guud

1.1 Sharaxaada Mashruuca

Tan 100kVA hal weji bedbedelka deegaanka waxaa la geeyey Guyana sanadka 2024. Ilaali u hoggaansanaanta heerarka IEEE & ANSI C57.12.00. Polarity-gu waa kala-goyn, kooxda faleebo-na waa Ii0. Awood u leh in uu ka beddelo korantada min 13,800V ilaa 120/240V, transformerkani waxa uu leeyahay qiimaynta kVA ee 100 waxqabad la isku halayn karo. Ka dhigista mid ku habboon guryaha iyo codsiyada ganacsiga fudud. Naqshadeynta dabaylaha naxaasta ah, transformer-kani waxa uu hubinayaa hab-dhaqanka sare iyo hufnaanta hawleed. Habka qaboojinta ONAN waxay hubisaa daadinta kulaylka wax ku ool ah, kor u qaadaysa isku halaynta muddada dheer{13}.

Iyada oo leh ± 2.5% kala duwan oo taabasho ah iyo wadarta guud ee 10%, waxay soo bandhigtay jawaab celin ku meel gaar ah oo heersare ah oo ku saabsan nidaaminta korantada, yaraynta saamaynta kor u kaca culeyska ee ilaalinta la xoojiyey. Tiirka hal wejiga ah ee ku rakiban taransfooriyaha maya - lumitaanka rarka waa 263W, iyo - luminta rarka waa 897W, hubinta tamarta{7}waxqabad hufan. Waxay ka kooban tahay xannibaad dhan 2.4%, iyadoo yaraynaysa hoos u dhaca korantada ee xaaladaha culeyska. Scotech waxay ku takhasustay iibinta transformers polemount macaamiisha goobta ganacsiga iyo warshadaha.

 

1.2 Tilmaamaha Farsamada

100kVAtiirka ku rakiban transformer-ka deegaankaqeexidda iyo xaashida xogta

loo geeyey
Guyana
Sannadka
2024
Nooca
Tiir hal waji ah oo ku rakiban transformer
Heerka
IEEE & ANSI C57.12.00
Awood lagu qiimeeyay
100 kVA
Soo noqnoqoshada
60HZ
Polarity
Kala goyn
Kooxda Vector
Ii0
Korantada aasaasiga ah
13800 V
Voltage Secondary
120/240 V
Qalabka dabaysha
NAxaas
Caqabada
2.4%
Habka qaboojinta
ONAN
Taabo Beddelka
NLTC
Riixista Range
± 2X2.5% (Guud ahaan tirada =10%)
Wax Xamuul ah ma jiro
263 W
Load Lumista
897 W
Agabka
Habaynta caadiga ah

 

1.3 Sawirro

100kVA tiirka ku rakiban cabbirka beddelka guryaha iyo faahfaahinta miisaanka

100 kVA residential transformer drawing 100 kVA residential transformer nameplate

 

 

02 Wax-soo-saarka

2.1 Core

Kooreyada Beddelka Dhaawaca waa codsi naqshad fudud oo wax ku ool ah oo loogu talagalay koofiyadaha birta silikoon ee wareejinta qaybinta. Waxa ay si weyn u yaraynaysaa wakhtiga loo baahan yahay in la isku keeno transformer-ka qaybinta mana jiro xidhid dheeraad ah ama qalab la mid ah oo loo baahan yahay si loo dhamaystiro dhismaha asaasiga ah. Shirkado badan oo awood qaybinta suuqyada Waqooyiga iyo Koonfurta Ameerika waxay door bidaan birta boogta.

100 kVA residential transformer iron core

 

2.2 Dabaylaha

100 kVA residential transformer winding

Dabaylaha transformer-kayadu waxa ay adeegsadaan{0}nadiif sare oo naxaas ah oo lagu naas-nuujiyay silig naxaas ah, oo leh firfircooni koronto oo heersare ah iyo dahaar adag. Ku dheggan dhaldhalaalka xooggan waxay wanaajisaa adkeysiga waxayna xirataa caabbinta. Samee qaab dhismeedka gariiradda la hagaajiyay ee dabaylaha bireedku hooseeya - gariiradaha korantada iyo dabaysha siliga sare - gariiradaha korantada, hubinta xasilloonida hawleed ee wanaagsan, isku halaynta, iyo waxqabadka kulaylka.

 

2.3 Haanta

Samaynta taangiyada beddelka waxay ku lug leedahay injineernimada saxda ah iyo farsamada gacanta si loo hubiyo cimriga taangiyada. Dhammaan alxanka taangigu waa inay ahaadaan kuwo toosan, siman, iyo labis ah, oo aan lahayn kala goysyo qabow, kuul alxan leh, dalool, ama barar, waana in lagu sameeyaa hal baas oo joogto ah halka ay suurtagal tahay. Alxanadu waa inay ahaadaan kuwo siman oo aan dildilaac lahayn. Daboolka haanta waa in aanay lahayn biyo la dareemi karo{3}} meelaha ururinta

 

2.4 Kulanka ugu dambeeya

1. Golaha dabaysha:U jiid dabaylaha HV/LV oo dul saar xudunta dahaarka leh, adoo hubinaya toosinta saxda ah iyo hufnaanta dahaarka.

2. Isku xirka Korontada:Isku-xidhka dabaysha waxay u horseedaa beddelka tuubada, baadiyaha, iyo qaybaha kale, ka dibna ilaali oo dahaadh kala-goysyada.

3. Xudunta - Qalajinta gariiradda:Geli qaybta firfircoon ee la soo ururiyey (core + windings) foornada qallajisa si loogu kululeeyo faakuumka si looga saaro qoyaanka.

4. Rakibaadda Haamaha:Ku rid qaybta firfircoon ee engegan taangiga, u dhig si ammaan ah, oo hubi in dahaarka saxda ah ee gidaarada haanta.

5. Kordhinta Agabka:Ku rakib bushings, valve gargaarka cadaadiska iyo qalabyada kale, ka dibna ka hubi inay jiraan.

6. Buuxinta & Dejinta Saliidda:Vacuum-ku buuxi saliid dahaarka, degsooyinka, oo oggolow degitaanka ka hor intaadan hubin heerarka saliidda iyo xoogga tamarta.

100 kVA residential transformer assembly

 

 

03 Tijaabinta

Imtixaanka joogtada ah

1. Cabbiraadaha iska caabinta

2. Imtixaanada saamiga

3. Tijaabada Polarity

4. Wax Khasaare ah oo Xamuul ah oo Hadda socda ma jiro

5. Load Khasaaraha iyo Korantada Waxyeelada

6. Tijaabada Voltage ee la dabaqay

7. Tijaabada adkaysiga korantada ee keentay

8. Cabbirka iska caabbinta dahaarka

9. Tijaabada Diidida oo leh Cadaadis loogu talagalay Beddeleyaasha Dareeraha Immersed

10. Tijaabada Dielectric Oil

100 kVA residential transformer test

 

Natiijooyinka Imtixaanka

Maya

Shayga Tijaabada

Unug

Qiimaha Ogolaanshaha

Qiimaha la qiyaasay

Gabagabo

1

Cabbiraadaha iska caabinta

/

/

/

Gudub

2

Imtixaanada saamiga

/

Weecashada saamiga danab ee taabashada maamulaha: In ka yar ama la mid ah 0.5%

Astaanta isku xirka: Ii0

-0.03

Gudub

3

Tijaabada polarity

/

Kala goyn

Kala goyn

Gudub

4

Maya- khasaarooyinka rarida iyo xamaasadda hadda

%

kW

I0:: bixiyaan qiime la qiyaasay

P0: bixi qiimaha la qiyaasay

U dulqaadasho la'aanta rarka waa +10%

0.88

0.211

Gudub

5

Khasaaraha culeyska, korantada impedance, wadarta khasaaraha iyo hufnaanta

/

kW

kW

t:85 darajo

Z%: qiimaha la qiyaasay

Pk: qiimaha la qiyaasay

Pt: qiimaha la qiyaasay

Dulqaadka impedance waa ± 10%

Dulqaadka wadarta rarka luminta waa +6%

2.29

0.823

1.034

99.21

Gudub

6

Tijaabada Korantada ee La dabaqay

/

HV: 34KV 60s

LV: 10kV 60s

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

7

Tijaabada adkaysiga korantada ee keentay

/

Danab la dabaqay (KV):

2 Uur

Muddada: 48

Inta jeer (HZ): 150

Ma jiro burbur ku yimaada tamarta tijaabada ah

Gudub

8

Cabbirka iska caabinta dahaarka

HV -LV ilaa Ground

LV-HV ilaa Ground

HV&LV ilaa Ground

66.7

59.4

60.5

/

9

Tijaabada daadinta

/

Cadaadiska la dabaqay: 20kPA

Muddada: 12h

Wax daadsan iyo maya

Waxyeello

Gudub

10

Tijaabada Dielectric Oil

kV

Ka weyn ama la mid ah 45

52.33

Gudub

 

 

04 Baakaynta iyo dhoofinta

100 kVA residential transformer packing
 
 

05 Goobta iyo Kooban

Tani100kVA hal -tirka wejiga{2}}ku rakiban waxaa loogu talagalay qaybinta tamarta la deggan yahay iyo tan fudud ee ganacsiga. Iyada oo leh dabaylo naxaas ah oo hufan, dhismo waara, iyo xakamaynta tayada adag, waxay keentaa waxqabad xasiloon iyo - adeeg muddo dheer oo deegaan baahi badan leh.